ITEM NO. 21: Providing & laying C.C. (1: 2 : 4 )/M-15 or C.C. using 12mm to 20mm size<br />
black trap machine crushed metal for all types of RCC structure like coping, lintels, slabs,<br />
RCC parapet, Paradi, staircase, steps, landing slab, chhajas, shelves, footing, columns,<br />
beams etc. including mixture machine, necessary shuttering, ramming watering and<br />
finishing honey combed surface if any, scaffolding etc. completed for all floors.<br />
The general specification of cement concrete shall be applicable. Item provides for all kinds of<br />
RCC work for building, for building, for all floors i.e. all elevations as per drawings, item includes<br />
shuttering work also.<br />
Honey combed surface, if any, shall be finished with C.M. 1:2, However if it is felt by Engineerin-charge<br />
that Honey combing is more and structure is required to be recast it shall be done by<br />
contractor with dismantling of original concrete. <strong>No</strong>thing extra shall be payable for dismantling as<br />
well as recasting work.<br />
Whenever surface if bulged or not found in line & level, contractor will have chip out, finish and<br />
bring in line & level without any extra c<br />
ITEM NO. 22 : Providing and laying c.c. (1:3:6) for foundation and plinth with brickbat or<br />
gravel or picked up metal or hand broken stone, of size 20mm to 25 mm as coarse<br />
aggregate, including mixing, watering, ramming, consolidation etc., complete as directed.<br />
General specification for concrete work shall be applicable. Coarse aggregate to be used shall<br />
be approved quality of well-burnt brickbats, gravel or metal. Proportion of ingredients shall 1:4:8<br />
i.e. one part of cement 4 parts of sand & 8 parts of coarse aggregate.<br />
Coarse and fine aggregate shall be clean, free from foreign materials. Brickbats shall be from<br />
well-burnt bricks. <strong>No</strong> debris or used bricks with mortar shall be allowed as brickbats. Aggregates<br />
shall be well graded of size specified. Where thickness of concrete is mote than 150 mm it shall<br />
be laid in 2 layers. Each layer to be consolidated with rammers properly. Second layer shall be<br />
laid only after first layer is completed and cleared for laying second layer.<br />
Before placing concrete for base in trenches or below column footing etc., area shall be<br />
cleared of all injurious and foreign materials, bottom shall be moisten with water so as not to<br />
absorb water of concrete.<br />
After laying of concrete, it shall be checked for top level to be provided and for correct<br />
thickness.<br />
Curing shall be done for minimum period of 8 days. If sufficient arrangements of curing is not<br />
found satisfactory, <strong>Board</strong> may arrange for curing work at the cost of contractor.<br />
Payment shall be made for cu. mtrs. of concrete laid as per details given in drawing or as<br />
directed as site.<br />
ITEM NO. 23 :Providing & laying M.S. reinforcement in position including cutting, bending,<br />
hooking &binding the reinforcement with approved quality of binding wire etc. completed as per<br />
design(Providing chairs &supports etc. will be paid for under the item)<br />
(A) Plain bars:<br />
Plain bars to be used shall confirm to grade Fe-415 to IS 1786. The specification specified above<br />
shall be applicable. Rerolled bars shall not be used. Wherever specified in drawing or where<br />
instructed plain bars shall be used.<br />
(B) Tor steel:<br />
The general specifications as specified above shall be applicable. Bars shall confirm to grade Fe-<br />
415 and IS 1786.<br />
Item <strong>No</strong>. 24. Providing and placing 40 mm thick and 300 mm to 450 mm wide PSC/RCC cover<br />
(for clear span upto 1.2 meters) in proportion (1:1.5:3) or M. 200 with necessary reinforcement<br />
or 10 mm , 4 <strong>No</strong>s. of bars and 6 mm distribution bars at 150 mm c/c as per drawing and<br />
design including finishing the all surfaces with cement plaster, curing by placing in water<br />