5.3 CONTROL SYSTEMS<br />
DIGITAL CONTROLLER OPERATION<br />
Flow Temp.<br />
Manual operation<br />
Set Point Temp<br />
Control system ready<br />
Modulating valve closing<br />
Modulating valve opening<br />
6<br />
6<br />
Not used<br />
Limit Comparator<br />
Increase value button<br />
Decrease value button<br />
PGM<br />
Program set button<br />
PGM<br />
EXIT<br />
EXIT<br />
Program exit button<br />
WRF 40<br />
DESCRIPTION<br />
The sophisticated digital thermostat controller provides display of water flow temperature, set point temperature<br />
and operating status of the boiler.<br />
TEMPERATURE DISPLAY<br />
The RED display indicates the flow water temperature from the boiler. The GREEN display indicates the boiler<br />
water flow set temperature.<br />
The controller is set to <strong>Hurlcon</strong> factory default settings at the time of manufacture. These settings are suitable for a<br />
wide range of applications but may require fine tuning depending on individual project specifications and<br />
characteristics. A detailed Siemens RWF 40 product manual is available on request which details how all settings<br />
are made and the auto tune function is activated.<br />
Standard settings are as follows<br />
Radiator & Fan Coil System -<br />
Set temp Dead zone High limit<br />
Automatic reset<br />
High Limit<br />
Manual Reset<br />
80 ˚C ± 5 ˚C 85 ˚C 90 ˚C<br />
Inst195 <strong>HM</strong> <strong>Series</strong> <strong>Hydronic</strong> <strong>Boiler</strong> V10_10 13