5.3 CONTROL SYSTEMS<br />

DIGITAL CONTROLLER OPERATION<br />

Flow Temp.<br />

Manual operation<br />

Set Point Temp<br />

Control system ready<br />

Modulating valve closing<br />

Modulating valve opening<br />

6<br />

6<br />

Not used<br />

Limit Comparator<br />

Increase value button<br />

Decrease value button<br />

PGM<br />

Program set button<br />

PGM<br />

EXIT<br />

EXIT<br />

Program exit button<br />

WRF 40<br />

DESCRIPTION<br />

The sophisticated digital thermostat controller provides display of water flow temperature, set point temperature<br />

and operating status of the boiler.<br />

TEMPERATURE DISPLAY<br />

The RED display indicates the flow water temperature from the boiler. The GREEN display indicates the boiler<br />

water flow set temperature.<br />

The controller is set to <strong>Hurlcon</strong> factory default settings at the time of manufacture. These settings are suitable for a<br />

wide range of applications but may require fine tuning depending on individual project specifications and<br />

characteristics. A detailed Siemens RWF 40 product manual is available on request which details how all settings<br />

are made and the auto tune function is activated.<br />

Standard settings are as follows<br />

Radiator & Fan Coil System -<br />

Set temp Dead zone High limit<br />

Automatic reset<br />

High Limit<br />

Manual Reset<br />

80 ˚C ± 5 ˚C 85 ˚C 90 ˚C<br />