Solutions / Malfunctions<br />

Electronic speed controller<br />

Distribution transformer<br />

OBSERVED MALFUNCTIONS<br />

• Heating of the distribution transformer possibly resulting in its destruction.<br />

1<br />

2<br />

PROPOSED ACTIONS<br />

Origin: conducted interference, harmonic currents<br />

(1) Design the transformer to take account of the RMS currents consumed by all<br />

devices that generate harmonic currents (electronic speed controllers, etc.)<br />

instead of the nominal load currents (motors, etc.).<br />

(2) Insert line inductances on the speed controller input (upstream)<br />

(3) Insert an anti-harmonic filter at the line head (downstream of the transformer).<br />

Recommended<br />

implementation<br />

(See chapter 2)<br />

(p. 56)<br />