Understanding (EMC) phenomena<br />

Type<br />

Source<br />

Transmission<br />

Types of electromagnetic<br />

interference<br />

Transients<br />

1<br />

2<br />

3<br />

4<br />

5<br />

The term «transient» denotes impulsive spikes picked up by electric circuits and encountered in conducted form<br />

on power supply cables and at control and signal inputs of electrical or electronic equipment.<br />

Characteristics of standardised transients (IEC 1000-4-4 type)<br />

The significant features of these disturbances are as follows:<br />

- Very short duration of pulse rise time 5 ms<br />

- Pulse duration 50 ms<br />

- Repetitive phenomenon: pulse bursts for roughly 15 ms<br />

- Repetition frequency : successive bursts roughly every 300 ms<br />

- Low energy pulses 1-10 -3 joule<br />

- High amplitude of overvoltage ≤ 4 kV<br />

Example :<br />

U<br />

Pulse<br />

t<br />

Time<br />

representation<br />

100 µs<br />

5 ms<br />

Repetition period depends on the level of the test voltage<br />

U<br />

Pulse burst<br />

t<br />

15 ms<br />

Length of burst<br />

Burst period 300 ms<br />

Te<br />

14