APPENDIX F: Guidelines to System Level Data Collection & Analysis<br />
Condenser water<br />
pumps<br />
Cooling towers<br />
Air handling units/<br />
Fan coil units<br />
Diesel generator sets<br />
Water pumping<br />
systems<br />
Motors and other<br />
drives (Shredding<br />
Briquetting/CVPS<br />
system)<br />
Uninterrupted Power<br />
Supply (UPS)<br />
Inventory of pumps to record type,<br />
rating, and operating hours of individual<br />
pumps. Pump discharge flow, Suction<br />
head, Discharge head, water distribution<br />
pipeline network <strong>for</strong> calculating the<br />
pressure drop across the pipeline.<br />
Inventory of cooling towers make,<br />
model, type, rating and operating hours<br />
of individual tower. Water & Air flow<br />
rate, Hot & Cold water temperature<br />
(Inlet/outlet water temp), Ambient dry<br />
and wet bulb temperature<br />
Inventory of AHU’s make, model, type,<br />
rating and operating hours of individual<br />
AHU. Chilled water flow rate.<br />
IN/OUT water temperature, Air delivery<br />
CFM, Return air temperature<br />
Delivery air temperature, Pressure<br />
drop across the cooling coil, Power<br />
consumption KW, power factor, shaft<br />
RPM, Fresh air intake<br />
Technical specification, rating and<br />
operating hours of individual DG set.<br />
Pumps type, rating, and operating hours<br />
of individual pumps. Pump discharge<br />
flow Suction head, Discharge head,<br />
Operating hour,<br />
Inventory of motors/drives rating,<br />
operating hours. Voltage, frequency,<br />
line current, power factor, power drawn<br />
and the shaft RPM at the operating<br />
conditions.<br />
Technical spec., Connected Load on the<br />
UPS<br />
Actual power consumption, System<br />
efficiency, Pump efficiency, Motor<br />
efficiency, Piping pressure drop<br />
estimation<br />
Heat rejection capacity, Tower approach<br />
Delta T, Power consumption<br />
Heat transfer capacity.<br />
Loading of the motor and load factor<br />
Power consumption<br />
Temperature profile and RH of the<br />
conditioned space<br />
Loading pattern of the DG sets<br />
Specific <strong>energy</strong> consumption – (KWh/<br />
Litres)<br />
Actual power consumption, System<br />
efficiency, Pump efficiency, Motor<br />
efficiency, Piping pressure drop<br />
estimation<br />
Loading of the motors and load factor<br />
Power factor, Power consumption,<br />
Drive efficiency<br />
Loading and Efficiency of the UPS<br />
52