APPENDIX F: Guidelines to System Level Data Collection & Analysis<br />

Condenser water<br />

pumps<br />

Cooling towers<br />

Air handling units/<br />

Fan coil units<br />

Diesel generator sets<br />

Water pumping<br />

systems<br />

Motors and other<br />

drives (Shredding<br />

Briquetting/CVPS<br />

system)<br />

Uninterrupted Power<br />

Supply (UPS)<br />

Inventory of pumps to record type,<br />

rating, and operating hours of individual<br />

pumps. Pump discharge flow, Suction<br />

head, Discharge head, water distribution<br />

pipeline network <strong>for</strong> calculating the<br />

pressure drop across the pipeline.<br />

Inventory of cooling towers make,<br />

model, type, rating and operating hours<br />

of individual tower. Water & Air flow<br />

rate, Hot & Cold water temperature<br />

(Inlet/outlet water temp), Ambient dry<br />

and wet bulb temperature<br />

Inventory of AHU’s make, model, type,<br />

rating and operating hours of individual<br />

AHU. Chilled water flow rate.<br />

IN/OUT water temperature, Air delivery<br />

CFM, Return air temperature<br />

Delivery air temperature, Pressure<br />

drop across the cooling coil, Power<br />

consumption KW, power factor, shaft<br />

RPM, Fresh air intake<br />

Technical specification, rating and<br />

operating hours of individual DG set.<br />

Pumps type, rating, and operating hours<br />

of individual pumps. Pump discharge<br />

flow Suction head, Discharge head,<br />

Operating hour,<br />

Inventory of motors/drives rating,<br />

operating hours. Voltage, frequency,<br />

line current, power factor, power drawn<br />

and the shaft RPM at the operating<br />

conditions.<br />

Technical spec., Connected Load on the<br />

UPS<br />

Actual power consumption, System<br />

efficiency, Pump efficiency, Motor<br />

efficiency, Piping pressure drop<br />

estimation<br />

Heat rejection capacity, Tower approach<br />

Delta T, Power consumption<br />

Heat transfer capacity.<br />

Loading of the motor and load factor<br />

Power consumption<br />

Temperature profile and RH of the<br />

conditioned space<br />

Loading pattern of the DG sets<br />

Specific <strong>energy</strong> consumption – (KWh/<br />

Litres)<br />

Actual power consumption, System<br />

efficiency, Pump efficiency, Motor<br />

efficiency, Piping pressure drop<br />

estimation<br />

Loading of the motors and load factor<br />

Power factor, Power consumption,<br />

Drive efficiency<br />

Loading and Efficiency of the UPS<br />

52