30.03.2014 Views

Commercial Heating - Ferroli

Commercial Heating - Ferroli

Commercial Heating - Ferroli

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Vjltkm<br />

Rjl<br />

Pfdjlcrjq yjvth<br />

Ntgkjghjbpdjlbntkmyjcn<br />

m<br />

Gjktpyfz Ntgkjdfzvjoyjcnm<br />

Vfrc= hf,jxtt lfdktybt<br />

Vfrc= hf,jxfz ntvgthfnehf<br />

J,mtv rjnkjdjq djls<br />

Jg h tccjd jxyjt lfdktybt#Lfnf<br />

' ktrnhjgbnfybt<br />

Technical specifications<br />

2360 3000 3600 4000 4500 5000 6000<br />

Heat output min. kW 1535 1950 2340 2600 2926 3251 3902<br />

max. kW 2360 3000 3600 4000 4500 5000 6000<br />

Heat input min. kW 1668 2113 2536 2819 3165 3515 4215<br />

max. kW 2565 3250 3900 4334 4868 5407 6483<br />

Water content dm 3 2150 2600 2950 4500 4950 6250 7000<br />

Energy marking (Directive 92/42 EEC) ★★ ★★ ★★ ★★ ★★ ★★ ★★<br />

Efficiency at Pn max (Tm 70°C) % 92.00 92.30 92.31 92.30 92.45 92.47 92.55<br />

Efficiency at Pn min (Tm 70°C) % 93.20 93.51 93.72 93.51 93.40 93.30 93.50<br />

Efficiency at 30% Pn max (Tm 50°C) % 93.65 93.76 94.21 93.76 94.05 93.90 94.35<br />

Δt smokes-environment gas 179.1/120 172.5/113 172.3/114 174.7/113 171.4/105 171.4/106 169.2/109<br />

CO 2 gas 10 10 10 10 10 10 10<br />

CO 2 oil 13 13 13 13 13 13 13<br />

Specific Thermic load mW/m 2 h 52.4 49.1 52.9 45.4 46.3 45.0 43.7<br />

Volumetric Thermic load mW/m 2 h 1.22 1.16 1.21 1.14 1.18 1.12 1.20<br />

Shell loss* % 0.5 0.5 0.5 0.4 0.4 0.4 0.4<br />

Loss at chimney burner on % 7.4 7.2 7.19 7.3 7.15 7.13 7.05<br />

Loss at chimney burner off ** % 0.1 0.1 0.1 0.1 0.1 0.1 0.1<br />

Working pressure bar 6 6 6 6 6 6 6<br />

Water side pressure drop Δt 10°C Δp mbar 150 145 190 250 280 200 215<br />

Δt 20°C Δp mbar 42 45 61 70 80 55 65<br />

Combustion chamber Internal Ø mm 980 1130 1130 1174 1174 1278 1278<br />

Length mm 2750 3000 3300 3300 3300 3300 3300<br />

Volume m 3 2.10 2.80 3.20 3.80 4.10 4.80 5.40<br />

Surface total m 2 45 61 68 88 97 111 137<br />

Flue gas side pressure drop Δp mbar 7.2 7.5 8.2 9.5 10.5 10.8 12.0<br />

Flue gas flow-rate gas Kg/h 3870 4904 5884 6539 7344 8158 9781<br />

oil Kg/h 4108 5205 6246 6941 7795 8660 10383<br />

Boiler weight (empty) kg 3900 5300 5800 7500 8000 9600 11500<br />

Dimensions Height mm 1950 2140 2140 2325 2325 2525 2525<br />

Width mm 1610 1800 1800 1980 1980 2180 2180<br />

Length mm 3232 3446 3816 4086 4436 4458 4958<br />

Connections T1 DN 150 200 200 200 200 250 250<br />

T2 DN 150 200 200 200 200 250 250<br />

T3 DN 100 125 125 125 125 150 150<br />

T4 DN 1 1 /2 " 1 1 /2 " 1 1 /2 " 1 1 /2 " 1 1 /2 " 1 1 /2 " 1 1 /2 "<br />

T5 Ø mm 450 500 500 600 600 650 650<br />

* Air Blocked, temperature 20ºC<br />

** Combustion air closed<br />

W<br />

T1 - T3 - T2<br />

T1<br />

L<br />

T3 T2 T2 - T3 - T1<br />

KEY<br />

T1 Central heating flow outlet<br />

T2 Central heating return inlet<br />

T6<br />

H<br />

T5<br />

T5<br />

T3 Expansion vessel attachment<br />

T4 Boiler drain<br />

T5 Flue attachment<br />

T4<br />

T4<br />

T6 Burner attachment fitting<br />

25

Hooray! Your file is uploaded and ready to be published.