Technical specifications<br />
Econcept 101<br />
Output max/min.<br />
Heat input kW 99.6/11.2<br />
Useful heat output 80°C - 60°C kW 97.6/11.0<br />
Useful heat output 50°C - 30°C kW 106.0/12.0<br />
Efficiency (net)<br />
80°C - 60°C Full load % 98.0<br />
50°C - 30°C % 106.4<br />
Part load (30%) % 109.0<br />
NOx emissions<br />
Class 5<br />
Gas supply (natural gas G20)<br />
Supply pressure mbar 20.0<br />
Flow rate max/min m 3 /h 10.54/1.19<br />
TREVERSE FLAME CERAMIC BURNERS<br />
The ECONCEPT 101 modules feature<br />
premix ceramic burners with reverse<br />
micro-flame, each made up of six plates<br />
fastened via a special gasket to a metal<br />
frame capable of absorbing thermal<br />
expansion. These burners have very low<br />
polluting emissions, both NOx and CO2.<br />
HEAT EXCHANGERS<br />
The heat exchangers design, build and<br />
materials ensure high efficiency, constant<br />
performances reliability.<br />
CASCADING OPERATION<br />
The ECONCEPT101 series modules have<br />
been developed for connection in series to<br />
make up a single heat generator that, in<br />
steps of 50kW, can have a total output of<br />
around 500kW. Each with electronic<br />
programming to ensure the optimum<br />
operation from 11kW to 500kW.<br />
Gas supply (LPG G31)<br />
Supply pressure mbar 37.0<br />
Flow rate max/min kg/h 7.8/0.88<br />
Central heating<br />
Maximum operating pressure bar 6<br />
Hot water content litres 12.8<br />
Dimensions, weights, fittings<br />
Height mm 1650<br />
Width mm 704<br />
Depth mm 410<br />
Weight (empty) kg 150<br />
Gas fitting<br />
Central heating fittings<br />
DN50<br />
DN80<br />
Power supply<br />
Max power input W 380<br />
Power supply voltage/frequency V/Hz 230V/50Hz<br />
Index of protection IP X5D<br />