6. Characteristics and Dimensions<br />

Earth-Leakage Circuit Breakers<br />

NV250-RW<br />

Type NV250-RW<br />

<strong>Series</strong><br />

Group<br />

Frame size 250<br />

Type name<br />

Rated current In (Amp.)<br />

R series<br />

<strong>WS</strong>S G3<br />

NV250-RW<br />

Number of poles 3<br />

Rated operational voltage Ue (V AC)<br />

High-speed type<br />

Time-delay type<br />

Earth-leakage indication system<br />

Rated breaking capacity (kA)<br />

IEC60947-2 (Icu/Ics)<br />

Rated current sensitivity I∆n (mA)<br />

Max. operating time at 5I∆n (s)<br />

Rated current sensitivity I∆n (mA)<br />

Max. operating time at 5I∆n (s)<br />

Inertial non-operating time at 2I∆n (s)<br />

AC440V<br />

AC400V<br />

AC230V<br />

125 150 175<br />

200 225<br />

230–400–440<br />

Multi-voltage type<br />

30 • 100 • 500<br />

Selectable<br />

0.04<br />

100 • 300 • 500<br />

Selectable<br />

0.45 • 1.0 • 2.0<br />

Selectable<br />

0.1 • 0.5 • 1.0<br />

Button<br />

125/125<br />

125/125<br />

125/125<br />

■Operating Characteristics<br />

■Earth-Leakage Tripping Characteristics<br />

Operating time<br />

4h<br />

2h<br />

1h<br />

30min<br />

20min<br />

14min<br />

10min<br />

6min<br />

4min<br />

2min<br />

1min<br />

30s<br />

20s<br />

10s<br />

5s<br />

2s<br />

1s<br />

0.5s<br />

0.2s<br />

0.1s<br />

0.05s<br />

0.02s<br />

0.01s<br />

Min.<br />

■Internal Accessories<br />

NV250-RW<br />

Max.<br />

Max.total<br />

breaking time<br />

Time-delay trip<br />

Instantaneous trip<br />

1 1.3 2 3 4 5 6 7 10 15 20 30 40<br />

100% of Rated current<br />

Operating time<br />

4h<br />

2h<br />

1h<br />

30min<br />

10min<br />

4min<br />

2min<br />

1min<br />

30s<br />

10s<br />

5s<br />

2s<br />

1s<br />

0.5s<br />

0.2s<br />

0.1s<br />

0.04s<br />

0.02s<br />

0.01s<br />

Rated nonoperating current<br />

Highspeed<br />

type<br />

Rated current sensitivity<br />

25 50 100<br />

Time-delay type<br />

0.45s(MAX)<br />

Inertial<br />

nonoperating time<br />

500 25 50 100 5001000<br />

Time-delay type<br />

1s(MAX)<br />

Inertial<br />

nonoperating time<br />

25 50 100 5001000<br />

Ground-fault current (% of rated current sensitivity)<br />

■Ambient Compensating Curve<br />

Rated nonoperating current<br />

Rated current sensitivity<br />

Rated nonoperating current<br />

Rated current sensitivity<br />

Rated nonoperating current<br />

Time-delay type<br />

2s(MAX)<br />

Rated current sensitivity<br />

Inertial<br />

nonoperating time<br />

25 50 100 5001000<br />

Left-side<br />

mounting<br />

<br />

NV250-RW<br />

Operating handle<br />

Right-side<br />

mounting<br />

Lead wire<br />

direction<br />

Curreny rating (%)<br />

130<br />

120<br />

110<br />

100<br />

90<br />

Rated ambient<br />

Remark: (1) refer to 24.<br />

■External Accessories<br />

80<br />

–10 0 10 20 30 40 50 60<br />

Ambient temperature (°C)<br />

(rated ambient 40°C)<br />

■Internal Wiring Diagram<br />

Enclosure<br />

Accessories<br />

Operating handle<br />

Dustproof<br />

Waterproof<br />

Handle lock device<br />

Type name<br />

Reference<br />

page<br />

Accessories<br />

Type name<br />

F F2UW<br />

Mechanical<br />

27<br />

S S2SW<br />

interlock<br />

MI MI-05SW3 (*1)<br />

V V2UW<br />

28<br />

Small TC-S TCS-2SW3W (*1)<br />

R R2UW<br />

29<br />

Large TC-L TCL-2SW3W (*1)<br />

S –<br />

Skeleton TTC TTC-2SW3 (*1)<br />

I – –<br />

Rear BTC BTC-2SW3W (*1)<br />

W –<br />

LC<br />

(*2)<br />

HL<br />

HL-S<br />

LC-2SW<br />

HLF-2SW<br />

HLN-2SW<br />

HLS-2SW<br />

32<br />

Terminal cover<br />

Plug-in PTC PTC-2SW3W (*1)<br />

Electrical<br />

operation device<br />

(*3)<br />

Notes: (*1) The designation depends on the number of poles. Refer to the reference page.<br />

(*2) HLF types are used for OFF-lock, and HLN types for ON-lock.<br />

(*3) An order should be placed at the same time as an order of circuit breaker main body.<br />

Reference<br />

page<br />

34<br />

30<br />

Line side<br />

Magnetic<br />

device<br />

Leakage<br />

indication button<br />

Test button<br />

Senstivity<br />

selector<br />

<br />

Load side<br />

53