25.04.2014 Views

WS Series - autocentrated

WS Series - autocentrated

WS Series - autocentrated

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

I<br />

Product design which pursues greater use ease by wide variations<br />

Interchangeable Relay Unit<br />

To enhance flexibility, the Mitsubishi<br />

<strong>WS</strong> <strong>Series</strong> is equipped with<br />

interchangeable relay units (available<br />

in thermal or electronic types).<br />

The move has been made to<br />

AC/DC common use, while the<br />

expanded adjustment range enables<br />

reduction in the number of 250AF<br />

relays from 10 to 7 types.<br />

A magnetic adjustable function has<br />

been added to the thermal type,<br />

while 4P neutral protection has also<br />

been enhanced.<br />

(Note: Only authorized members<br />

available to replace)<br />

Thermal type unit<br />

4 10<br />

Electronic type unit<br />

Thermal Adjustable Relay<br />

6 8<br />

Ii(DC)=1.3XIi(AC) 4 10<br />

Ii(X250A AC)<br />

T<br />

Ir<br />

Ii<br />

MODEL<br />

RT<br />

250<br />

In 250 A<br />

50/60Hz<br />

40 3P3E<br />

160<br />

200<br />

Ir(A)<br />

250<br />

MADE IN JAPAN<br />

LN326N433-1<br />

Rating<br />

Type<br />

In (A)<br />

NF250-SGW / HGW<br />

NF160-SGW / HGW<br />

NF125-SGW / HGW<br />

Tripping threshold Ir (A)<br />

(note 1)<br />

Neutral protection<br />

4P 3E<br />

4P 4E<br />

25 40 63 100 125 160 250<br />

● ●<br />

●<br />

● ● ● ● ●<br />

Overload Protection (Thermal)<br />

Adjustable<br />

16-25 25-40 40-63 63-100 80-125 125-160<br />

No Protection<br />

1 × Ir<br />

160-250 (160-225)<br />

Tripping threshold Ii<br />

Short-Circuit Protection (Magnetic)<br />

Fixed<br />

10 × In<br />

Adjustable<br />

4 to 10 × In<br />

Note: (1) The type 4P 3E is standard. If the type 4P 4E is required, specify the type 4P 4E separately and explicitly.<br />

Ir Ii I<br />

Electronic Relay<br />

LN326N429-11<br />

MODEL<br />

T<br />

Ir<br />

MADE IN JAPAN<br />

Ip<br />

TL<br />

RE250 In<br />

250<br />

A<br />

Is<br />

AC only<br />

50/60Hz<br />

Ii 70% PAL<br />

Ts<br />

Ir (A) TEST T L(s) Is (XIr) Ts (s)<br />

Ip (XIr)<br />

200<br />

80<br />

4 5<br />

160<br />

60<br />

3.5<br />

6<br />

2 Ii (X250A) 8<br />

85<br />

1<br />

10<br />

8<br />

9<br />

3<br />

7<br />

6<br />

12<br />

95<br />

2.5<br />

8<br />

75<br />

125<br />

250 12 100 2 10 06<br />

3 4 14 7<br />

1.0<br />

OVER<br />

I pN<br />

4P3E 4P4E<br />

Rating In (A) (40°C)<br />

NF250-SGW / HGW<br />

Type NF160-SGW / HGW<br />

NF125-SGW / HGW<br />

LTD<br />

Tripping threshold Ir (A)<br />

Tripping time<br />

TL(s)<br />

Neutral protection (Slectable)<br />

32 63 100 125 160 250<br />

●<br />

●<br />

● ● ● ●<br />

Overload Protection<br />

Adjustable<br />

16-32 32-63 63-100 75-125 80-160 125-250<br />

12-60-80-100 step adjustable (at 2 × Ir)<br />

0-1 × Ir (Step adjustable)<br />

T<br />

Ip<br />

TL<br />

Ir<br />

Is<br />

Ts<br />

Ii<br />

I<br />

STD<br />

INST<br />

PAL<br />

Pickup current Is<br />

Tripping time Ts(s)<br />

Tripping threshold Ii<br />

Pickup current Ip<br />

Operating time Tp<br />

70%-LED (green)<br />

PAL-LED (orange)<br />

Over -LED (red)<br />

Short-Circuit Protection<br />

2-2.5-3-3.5-4-5-6-7-8-10 × Ir step adjustable<br />

0.06-0.1-0.2-0.3 step adjustable (at 1.5 × Is)<br />

4 to 14 × In continuous adjustable<br />

Pre-Alarm<br />

0.7-0.75-0.8-0.85-0.9-0.95-1.0 × Ir step adjustable<br />

TL/2<br />

Indicator (LED)<br />

Lit at 0.7 × Ir<br />

Flashing at lp and lit at Tp<br />

Lit at 1.15 × Ir<br />

6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!