TROUBLESHOOTING THE SLAVE SUBROUTINE<br />
Troubleshooting the Slave Subroutine<br />
The slave subroutine has a status table and a port status table to help verify and troubleshoot the<br />
operation of the subroutine.<br />
Status Table<br />
String Table, stMBStatusS2.<br />
• Index 0 = TX String (RTU and TCP use Hexadecimal to view)<br />
• Index 1 = Status port 1<br />
This is the status of the last packet.<br />
– Listen TCP<br />
– Open RTU<br />
– Open ASCII<br />
– Too Many Characters<br />
– CRC Mismatch<br />
– Wrong Slave Address<br />
– LRC Mismatch<br />
– Exception code<br />
– OK RTU<br />
– OK ASCII<br />
– OK TCP<br />
– Not Configured<br />
– TX Error + Error code<br />
• Index 2 = Status port 2<br />
• Index 3 = Status port 3<br />
• Index 4 = Status port 4<br />
• Index 5 = RX String (RTU and TCP use Hexadecimal to view)<br />
Port Status Table<br />
Integer 32 Table, ntMBPortStatusS2<br />
• Index 0 = Not Used<br />
• Index 1 = Port 1 Status<br />
– 0 = OK<br />
– Any negative number = Error<br />
On ports configured <strong>for</strong> <strong>Modbus</strong>/TCP, -52 and -442 are normal until the <strong>Modbus</strong> master<br />
opens the session or after the <strong>Modbus</strong> master closes the session.<br />
• Index 2 = Port 2 Status<br />
• Index 3 = Port 3 Status<br />
• Index 4 = Port 4 Status<br />
42<br />
<strong>Modbus</strong> <strong>Integration</strong> <strong>Kit</strong> <strong>for</strong> <strong>PAC</strong> <strong>Control</strong> User’s <strong>Guide</strong>