04.10.2014 Views

SL280DFV Gas Furnace Installation Manual - Lennox

SL280DFV Gas Furnace Installation Manual - Lennox

SL280DFV Gas Furnace Installation Manual - Lennox

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Generator Use − Voltage Requirements<br />

The following requirements must be kept in mind when<br />

specifying a generator for use with this equipment:<br />

The furnace requires 120 volts (Range: 102 volts to<br />

132 volts)<br />

The furnace operates at 60 Hz + 5% (Range: 57 Hz to<br />

63 Hz)<br />

<br />

<br />

The furnace integrated control requires both correct<br />

polarity and proper ground. Both polarity and proper<br />

grounding should be checked before attempting to operate<br />

the furnace on either permanent or temporary<br />

power<br />

Generator should have a wave form distortion of less<br />

than 5% THD (total harmonic distortion)<br />

icomfort Touch ® Thermostat with <strong>SL280DFV</strong><br />

and Non−Communicating Outdoor Unit<br />

icomfort Touch ® Thermostat<br />

icomfort−Enabled <strong>SL280DFV</strong> Indoor <strong>Furnace</strong><br />

Non−Communicating Outdoor Air Conditioner<br />

icomfort Touch ® Thermostat with <strong>SL280DFV</strong><br />

and icomfort−ENABLED Outdoor Unit<br />

icomfort Touch ® Thermostat<br />

icomfort−Enabled <strong>SL280DFV</strong> Indoor <strong>Furnace</strong><br />

icomfort−Enabled Outdoor Air Conditioner or Heat Pump<br />

OPTIONAL<br />

DISCHARGE<br />

AIR SENSOR<br />

icomfort Touch®<br />

THERMOSTAT<br />

icomfort−<br />

ENABLED<br />

<strong>SL280DFV</strong><br />

FURNACE<br />

OPTIONAL<br />

OUTDOOR<br />

AIR SENSOR<br />

OPTIONAL<br />

DISCHARGE<br />

AIR SENSOR<br />

OPTIONAL<br />

OUTDOOR<br />

AIR SENSOR<br />

icomfort Touch®<br />

THERMOSTAT<br />

icomfort−<br />

ENABLED<br />

<strong>SL280DFV</strong><br />

FURNACE<br />

icomfort− ENABLED<br />

OUTDOOR AIR CONDITIONING<br />

OR HEAT PUMP UNIT<br />

NON−COMMUNICATING<br />

OUTDOOR AIR<br />

CONDITIONING UNIT −<br />

1 OR 2 STAGE<br />

CLIP ON−BOARD LINK<br />

W915 (Y1 TO Y2) FOR<br />

TWO−STAGE OPERATION<br />

NOTE − On communicating systems, extra wires must terminate on the "C" RSBus terminal. Use an additional wire and come<br />

off "C" terminal and wire nut all the extra wires together. Termination on the outdoor control must match the indoor control.<br />

Outdoor Unit<br />

icomfort Integrated Control<br />

icomfort Touch ®<br />

FIGURE 21<br />

Page 23

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!