SL280DFV Gas Furnace Installation Manual - Lennox
SL280DFV Gas Furnace Installation Manual - Lennox
SL280DFV Gas Furnace Installation Manual - Lennox
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
chilled air from entering the furnace (see figure 1). If the<br />
damper is manually operated, it must be equipped to prevent<br />
operation of either the heating or the cooling unit, unless<br />
it is in the full HEAT or COOL setting.<br />
GAS UNIT<br />
Dampers<br />
(open during heating<br />
operation only)<br />
FIGURE 1<br />
AIR HANDLER<br />
Dampers<br />
(open during cooling<br />
operation only)<br />
When installed, this furnace must be electrically grounded<br />
according to local codes. In addition, in the United States,<br />
installation must conform with the current National Electric<br />
Code, ANSI/NFPA No. 70. The National Electric Code<br />
(ANSI/NFPA No. 70) is available from the following address:<br />
National Fire Protection Association<br />
1 Battery March Park<br />
Quincy, MA 02269<br />
NOTE − This furnace is designed for a minimum continuous<br />
return air temperature of 60°F (16°C) or an intermittent<br />
operation down to 55°F (13°C) dry bulb for cases<br />
where a night setback thermostat is used. Return air temperature<br />
must not exceed 85°F (29°C) dry bulb.<br />
The <strong>SL280DFV</strong> furnace may be installed in alcoves, closets,<br />
attics, basements, garages, and utility rooms in the<br />
downflow position.<br />
This furnace design has not been CSA International certified<br />
for installation in mobile homes, recreational vehicles,<br />
or outdoors.<br />
Use of <strong>Furnace</strong> as Construction Heater<br />
<strong>Lennox</strong> does not recommend the use of <strong>SL280DFV</strong> units<br />
as a construction heater during any phase of construction.<br />
Very low return air temperatures, harmful vapors and operation<br />
of the unit with clogged or misplaced filters will damage<br />
the unit.<br />
<strong>SL280DFV</strong> units may be used for heating of buildings or<br />
structures under construction, if the following conditions<br />
are met:<br />
The vent system must be permanently installed per<br />
these installation instructions.<br />
A room thermostat must control the furnace. The use of<br />
fixed jumpers that will provide continuous heating is not<br />
allowed.<br />
The return air duct must be provided and sealed to the<br />
furnace.<br />
Return air temperature range between 60°F (16°C) and<br />
80°F (27°C) must be maintained.<br />
Air filters must be installed in the system and must be<br />
maintained during construction.<br />
Air filters must be replaced upon construction completion.<br />
The input rate and temperature rise must be set per the<br />
furnace rating plate.<br />
One hundred percent (100%) outdoor air must be provided<br />
for combustion air requirements during construction.<br />
Temporary ducting may supply outdoor air to the<br />
furnace. Do not connect duct directly to the furnace.<br />
Size the temporary duct following these instructions in<br />
section for Combustion, Dilution and Ventilation Air in a<br />
confined space with air from outside.<br />
The furnace heat exchanger, components, duct system,<br />
air filters and evaporator coils must be thoroughly<br />
cleaned following final construction clean−up.<br />
All furnace operating conditions (including ignition, input<br />
rate, temperature rise and venting) must be verified<br />
according to these installation instructions.<br />
General<br />
These instructions are intended as a general guide and do<br />
not supersede local codes in any way. Consult authorities<br />
having jurisdiction before installation.<br />
In addition to the requirements outlined previously, the following<br />
general recommendations must be considered<br />
when installing a <strong>SL280DFV</strong> furnace:<br />
Place the furnace as close to the center of the air distribution<br />
system as possible. The furnace should also be<br />
located close to the chimney or vent termination point.<br />
Do not install the furnace where drafts might blow directly<br />
into it. This could cause improper combustion and unsafe<br />
operation.<br />
Do not block the furnace combustion air openings with<br />
clothing, boxes, doors, etc. Air is needed for proper<br />
combustion and safe unit operation.<br />
When the furnace is installed in an attic or other insulated<br />
space, keep insulation away from the furnace.<br />
NOTE − The Commonwealth of Massachusetts stipulates<br />
these additional requirements:<br />
<strong>Gas</strong> furnaces shall be installed by a licensed plumber<br />
or fitter only.<br />
Page 5