04.10.2014 Views

SL280DFV Gas Furnace Installation Manual - Lennox

SL280DFV Gas Furnace Installation Manual - Lennox

SL280DFV Gas Furnace Installation Manual - Lennox

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

chilled air from entering the furnace (see figure 1). If the<br />

damper is manually operated, it must be equipped to prevent<br />

operation of either the heating or the cooling unit, unless<br />

it is in the full HEAT or COOL setting.<br />

GAS UNIT<br />

Dampers<br />

(open during heating<br />

operation only)<br />

FIGURE 1<br />

AIR HANDLER<br />

Dampers<br />

(open during cooling<br />

operation only)<br />

When installed, this furnace must be electrically grounded<br />

according to local codes. In addition, in the United States,<br />

installation must conform with the current National Electric<br />

Code, ANSI/NFPA No. 70. The National Electric Code<br />

(ANSI/NFPA No. 70) is available from the following address:<br />

National Fire Protection Association<br />

1 Battery March Park<br />

Quincy, MA 02269<br />

NOTE − This furnace is designed for a minimum continuous<br />

return air temperature of 60°F (16°C) or an intermittent<br />

operation down to 55°F (13°C) dry bulb for cases<br />

where a night setback thermostat is used. Return air temperature<br />

must not exceed 85°F (29°C) dry bulb.<br />

The <strong>SL280DFV</strong> furnace may be installed in alcoves, closets,<br />

attics, basements, garages, and utility rooms in the<br />

downflow position.<br />

This furnace design has not been CSA International certified<br />

for installation in mobile homes, recreational vehicles,<br />

or outdoors.<br />

Use of <strong>Furnace</strong> as Construction Heater<br />

<strong>Lennox</strong> does not recommend the use of <strong>SL280DFV</strong> units<br />

as a construction heater during any phase of construction.<br />

Very low return air temperatures, harmful vapors and operation<br />

of the unit with clogged or misplaced filters will damage<br />

the unit.<br />

<strong>SL280DFV</strong> units may be used for heating of buildings or<br />

structures under construction, if the following conditions<br />

are met:<br />

The vent system must be permanently installed per<br />

these installation instructions.<br />

A room thermostat must control the furnace. The use of<br />

fixed jumpers that will provide continuous heating is not<br />

allowed.<br />

The return air duct must be provided and sealed to the<br />

furnace.<br />

Return air temperature range between 60°F (16°C) and<br />

80°F (27°C) must be maintained.<br />

Air filters must be installed in the system and must be<br />

maintained during construction.<br />

Air filters must be replaced upon construction completion.<br />

The input rate and temperature rise must be set per the<br />

furnace rating plate.<br />

One hundred percent (100%) outdoor air must be provided<br />

for combustion air requirements during construction.<br />

Temporary ducting may supply outdoor air to the<br />

furnace. Do not connect duct directly to the furnace.<br />

Size the temporary duct following these instructions in<br />

section for Combustion, Dilution and Ventilation Air in a<br />

confined space with air from outside.<br />

The furnace heat exchanger, components, duct system,<br />

air filters and evaporator coils must be thoroughly<br />

cleaned following final construction clean−up.<br />

All furnace operating conditions (including ignition, input<br />

rate, temperature rise and venting) must be verified<br />

according to these installation instructions.<br />

General<br />

These instructions are intended as a general guide and do<br />

not supersede local codes in any way. Consult authorities<br />

having jurisdiction before installation.<br />

In addition to the requirements outlined previously, the following<br />

general recommendations must be considered<br />

when installing a <strong>SL280DFV</strong> furnace:<br />

Place the furnace as close to the center of the air distribution<br />

system as possible. The furnace should also be<br />

located close to the chimney or vent termination point.<br />

Do not install the furnace where drafts might blow directly<br />

into it. This could cause improper combustion and unsafe<br />

operation.<br />

Do not block the furnace combustion air openings with<br />

clothing, boxes, doors, etc. Air is needed for proper<br />

combustion and safe unit operation.<br />

When the furnace is installed in an attic or other insulated<br />

space, keep insulation away from the furnace.<br />

NOTE − The Commonwealth of Massachusetts stipulates<br />

these additional requirements:<br />

<strong>Gas</strong> furnaces shall be installed by a licensed plumber<br />

or fitter only.<br />

Page 5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!