Troubleshooting: Heating Sequence of Operation (Continued)<br />

CALL FOR SECOND−STAGE HEAT<br />

2<br />

CALL FOR 2ND STAGE HEAT<br />

(HIGH FIRE)<br />

1<br />

2 STAGE THERMOSTAT<br />

SINGLE STAGE<br />

THERMOSTAT<br />

2<br />

RECOGNITION DELAY<br />

(30 SECONDS)<br />

ONLY FOR 1ST EXPIRED?<br />

REQUEST FOR<br />

2ND STAGE HEAT<br />

YES<br />

YES<br />

2ND STAGE<br />

ON DELAY<br />

EXPIRED?<br />

INDUCER SWITCHED<br />

TO HIGH SPEED<br />

HIGH<br />

PRESSURE SWITCH<br />

CLOSED WITHIN 10<br />

SECONDS?<br />

NO<br />

INDUCER SWITCHED<br />

TO LOW SPEED<br />

5 MINUTE DELAY<br />

(ERROR CODE FLASHES)<br />

3<br />

YES<br />

2ND STAGE GAS VALVE<br />

ENERGIZED<br />

INDOOR BLOWER ENERGIZED<br />

ON HIGH HEAT SPEED<br />

3<br />

CALL FOR HEAT SATISFIED<br />

1<br />

2<br />

SYSTEM WILL ALWAYS LIGHT ON LOW FIIRE, EVEN IF 2ND STAGE HEAT IS IN PLACE.<br />

WHEN USED WITH A SINGLE STAGE THERMOSTAT, SET SW1 TO THE ON POSITION IN DIP SWITCH S4.<br />

3<br />

IF THE HIGH FIRE PRESSURE SWITCH DOES NOT CLOSE WITHIN 5 ATTEMPTS, THE SYSTEM WILL OPERATE AT<br />

LOW FIRE FOR THE REMAINDER OF THE CALL FOR HEAT REQUEST.<br />

Page 57