Page 12 of 16<br />

TFP1310<br />

Supply<br />

Maximum Pilot Height,<br />

(2)<br />

Pressure,<br />

(1)<br />

Feet (Meters)<br />

PSI<br />

1-1/2" 2" 3"<br />

4" 6"<br />

(Bar) (DN40)<br />

(DN50)<br />

(DN80) (DN100) (DN150)<br />

20<br />

7 3<br />

7<br />

17<br />

18<br />

(1,4) (1,4) (0,9) (1,4) (5,2) (5,5)<br />

40<br />

24 19<br />

30<br />

39 38<br />

(2,8) (7,3) (5,8) (9,1) (11,9) (11,6)<br />

60<br />

46 38<br />

52<br />

54 56<br />

(4,1) (14,0) (11,6) (15,8) (16,5) (17,1)<br />

80<br />

58 54<br />

70<br />

60 70<br />

(5,5) (17,8) (16,5) (21,3) (18,3) (21,3)<br />

100<br />

78 78<br />

93<br />

78 99<br />

(6,9) (23,8) (23,8) (28,3) (23,8) (30,2)<br />

120<br />

87 87<br />

117<br />

115 130<br />

(8,3) (26,5) (26,5) (35,7) (35,10 (39,6)<br />

140<br />

105 107<br />

139<br />

142 154<br />

(9,7) (32,0) (32,6) (42,4) (43,3) (46,9)<br />

160<br />

127 123<br />

161<br />

176 161<br />

(11,0) (38,7) (37,5) (49,1) (53,6) (49,1)<br />

175<br />

134 138<br />

172<br />

171 194<br />

(12,1) (40,8) (42,1) (52,4) (52,1) (59,1)<br />

200<br />

160 160<br />

206<br />

223 216<br />

(13,8) (48,8) (48,8) (62,8) (68,0) (65,8)<br />

225<br />

185 166<br />

237<br />

233 246<br />

(15,5) (56,4) (50,6) (72,2) (71,0) (75,0)<br />

250<br />

201 199<br />

251<br />

247 275<br />

(17,2) (61,3) (60,7) (76,5) (75,3) (83,8)<br />

8"<br />

(DN200)<br />

9<br />

(2,7)<br />

38<br />

(11,6)<br />

44<br />

(13,4)<br />

58<br />

(17,8)<br />

65<br />

(19,8)<br />

96<br />

(29,3)<br />

141<br />

(43,0)<br />

170<br />

(51,8)<br />

194<br />

(50,1)<br />

206<br />

(62,8)<br />

250<br />

(76,2)<br />

257<br />

(78,3)<br />

(1)<br />

(2)<br />

(3)<br />

If supply pressure is variable, assume minimum expected value.<br />

Maximum pilot height for up to 500 feet (150 meters) of equivalent<br />

length of pilot line (pipe plus fittings).<br />

Interpolation between data points is permitted.<br />

TABLE A<br />

1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVE<br />

WET PILOT DESIGN CRITERIA FOR UP TO<br />

500 FEET OF EQUIVALENT LENGTH OF PILOT LINE (PIPE PLUS FITTINGS)