Page 12 of 16<br />
TFP1310<br />
Supply<br />
Maximum Pilot Height,<br />
(2)<br />
Pressure,<br />
(1)<br />
Feet (Meters)<br />
PSI<br />
1-1/2" 2" 3"<br />
4" 6"<br />
(Bar) (DN40)<br />
(DN50)<br />
(DN80) (DN100) (DN150)<br />
20<br />
7 3<br />
7<br />
17<br />
18<br />
(1,4) (1,4) (0,9) (1,4) (5,2) (5,5)<br />
40<br />
24 19<br />
30<br />
39 38<br />
(2,8) (7,3) (5,8) (9,1) (11,9) (11,6)<br />
60<br />
46 38<br />
52<br />
54 56<br />
(4,1) (14,0) (11,6) (15,8) (16,5) (17,1)<br />
80<br />
58 54<br />
70<br />
60 70<br />
(5,5) (17,8) (16,5) (21,3) (18,3) (21,3)<br />
100<br />
78 78<br />
93<br />
78 99<br />
(6,9) (23,8) (23,8) (28,3) (23,8) (30,2)<br />
120<br />
87 87<br />
117<br />
115 130<br />
(8,3) (26,5) (26,5) (35,7) (35,10 (39,6)<br />
140<br />
105 107<br />
139<br />
142 154<br />
(9,7) (32,0) (32,6) (42,4) (43,3) (46,9)<br />
160<br />
127 123<br />
161<br />
176 161<br />
(11,0) (38,7) (37,5) (49,1) (53,6) (49,1)<br />
175<br />
134 138<br />
172<br />
171 194<br />
(12,1) (40,8) (42,1) (52,4) (52,1) (59,1)<br />
200<br />
160 160<br />
206<br />
223 216<br />
(13,8) (48,8) (48,8) (62,8) (68,0) (65,8)<br />
225<br />
185 166<br />
237<br />
233 246<br />
(15,5) (56,4) (50,6) (72,2) (71,0) (75,0)<br />
250<br />
201 199<br />
251<br />
247 275<br />
(17,2) (61,3) (60,7) (76,5) (75,3) (83,8)<br />
8"<br />
(DN200)<br />
9<br />
(2,7)<br />
38<br />
(11,6)<br />
44<br />
(13,4)<br />
58<br />
(17,8)<br />
65<br />
(19,8)<br />
96<br />
(29,3)<br />
141<br />
(43,0)<br />
170<br />
(51,8)<br />
194<br />
(50,1)<br />
206<br />
(62,8)<br />
250<br />
(76,2)<br />
257<br />
(78,3)<br />
(1)<br />
(2)<br />
(3)<br />
If supply pressure is variable, assume minimum expected value.<br />
Maximum pilot height for up to 500 feet (150 meters) of equivalent<br />
length of pilot line (pipe plus fittings).<br />
Interpolation between data points is permitted.<br />
TABLE A<br />
1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVE<br />
WET PILOT DESIGN CRITERIA FOR UP TO<br />
500 FEET OF EQUIVALENT LENGTH OF PILOT LINE (PIPE PLUS FITTINGS)