Response Rating<br />
80 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (<strong>TY</strong>3332)<br />
Coverage Area (1)<br />
m x m (ft x ft)<br />
Minimum<br />
Flow (2)<br />
l/min (gpm)<br />
Minimum Pressure<br />
(2) ,<br />
bar (psi)<br />
Deflector-To-<br />
Ceiling Distance<br />
(3)<br />
mm (in)<br />
Sprinkler Temperature<br />
Rating<br />
°C<br />
Minimum Spacing<br />
(4)<br />
m (ft)<br />
Quick 4,9 x 4,9 (16 x 16) 98 (26) 1,48 (21.6) 100 - 300 (4 - 12) 57, 68, 79 3,1 (10)<br />
Quick 4,9 x 5,5 (16 x 18) 110 (29) 1,85 (26.8) 100 - 300 (4 - 12) 57, 68, 79 3,1 (10)<br />
Quick 4,9 x 6,1 (16 x 20) 121 (32) 2,25 (32.7) 100 - 150 (4 - 6) 57 3,1 (10)<br />
Quick 4,9 x 6,7 (16 x 22) 133 (35) 2,70 (39.1) 100 - 150 (4 - 6) 57 3,1 (10)<br />
Standard 4,9 x 6,1 (16 x 20) 121 (32) 2,25 (32.7) 100 - 150 (4 - 6) 68 3,1 (10)<br />
Standard 4,9 x 6,7 (16 x 22) 133 (35) 2,70 (39.1) 100 - 150 (4 - 6) 68, 79 3,1 (10)<br />
115 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (<strong>TY</strong>4332)<br />
Response Rating<br />
Coverage Area (1)<br />
m x m (ft x ft)<br />
Minimum<br />
Flow (2)<br />
l/min (gpm)<br />
Minimum Pressure<br />
(2) ,<br />
bar (psi)<br />
Deflector-To-<br />
Ceiling Distance<br />
(3)<br />
mm (in)<br />
Sprinkler Temperature<br />
Rating<br />
°C<br />
Minimum Spacing<br />
(4)<br />
m (ft)<br />
Quick 4,9 x 4,9 (16 x 16) 98 (26) 0,73 (10.6) 100 - 300 (4 - 12) 57, 68, 79 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 5,5 (16 x 18) 110 (29) 0,90 (13.1) 100 - 300 (4 - 12) 57, 68, 79 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 6,1 (16 x 20) 121 (32) 1,10 (16.0) 100 - 150 (4 - 6) 57 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 6,1 (16 x 20) 125 (33) 1,17 (17.0) 100 - 300 (4 - 12) 57 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 6,7 (16 x 22) 133 (35) 1,32 (19.1) 100 - 150 (4 - 6) 57 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 6,7 (16 x 22) 136 (36) 1,59 (20.3) 100 - 300 (4 - 12) 57 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 7,3 (16 x 24) 148 (39) 1,64 (23.8) 100 - 150 (4 - 6) 57 10 (3,1)/13 (4,0) (5)<br />
Quick 4,9 x 7,3 (16 x 24) 151 (40) 1,72 (25.0) 100 - 300 (4 - 12) 57 10 (3,1)/13 (4,0) (5)<br />
Standard 4,9 x 6,1 (16 x 20) 121 (32) 1,10 (16.0) 100 - 150 (4 - 6) 68 10 (3,1)/13 (4,0) (5)<br />
Standard 4,9 x 6,1 (16 x 20) 125 (33) 1,17 (17.0) 100 - 300 (4 - 12) 68 10 (3,1)/13 (4,0) (5)<br />
Standard 4,9 x 6,7 (16 x 22) 133 (35) 1,32 (19.1) 100 - 150 (4 - 6) 68, 79 10 (3,1)/13 (4,0) (5)<br />
Standard 4,9 x 6,7 (16 x 22) 136 (36) 1,59 (20.3) 100 - 300 (4 - 12) 68, 79 10 (3,1)/13 (4,0) (5)<br />
Standard 4,9 x 7,3 (16 x 24) 148 (39) 1,64 (23.8) 100 - 150 (4 - 6) 68, 79 10 (3,1)/13 (4,0) (5)<br />
Standard 4,9 x 7,3 (16 x 24) 151 (40) 1,72 (25.0) 100 - 300 (4 - 12) 68, 79 10 (3,1)/13 (4,0) (5)<br />
NOTES<br />
1. Backwall (where sprinkler is located) by sidewall (length of throw).<br />
2. Requirement is based on minimum flow in GPM from each sprinkler. The indicted residual pressures are based on the nominal K-factor.<br />
3. The centerline of the sprinkler waterway is located 11,1 mm (7/16”) below the deflector (Ref. Figures 1 and 2).<br />
4. Miinimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall<br />
sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection<br />
area of the extended coverage sidewall sprinkler being utilized.<br />
5. Minimum spacing is 4,0 m (13 feet) when design pressure exceeds 12,1 bar (175 psi), otherwise the minimum spacing is 3,1 m<br />
(10 feet).<br />
TABLE C<br />
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA