TFP296_EN Page 5 of 8<br />
Response Rating<br />
80 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (<strong>TY</strong>3332)<br />
Coverage Area (1)<br />
m x m (ft x ft)<br />
Minimum<br />
Flow (2)<br />
l/min (gpm)<br />
Minimum Pressure<br />
(2) ,<br />
bar (psi)<br />
Deflector-To-<br />
Ceiling Distance<br />
(3)<br />
mm (in)<br />
Sprinkler Temperature<br />
Rating<br />
°C<br />
Minimum Spacing<br />
(4)<br />
m (ft)<br />
Quick 4,9 x 4,9 (16 x 16) 98 (26) 1,51 (22) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Quick 4,9 x 5,5 (16 x 18) 114 (30) 2,00 (29) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Quick 4,9 x 6,1 (16 x 20) 125 (33) 2,41 (35) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Standard 4,9 x 4,9 (16 x 16) 98 (26) 1,51 (22) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Standard 4,9 x 5,5 (16 x 18) 114 (30) 2,00 (29) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Standard 4,9 x 6,1 (16 x 20) 125 (33) 2,41 (35) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Response Rating<br />
115 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (<strong>TY</strong>4332)<br />
Coverage Area (1)<br />
m x m (ft x ft)<br />
Minimum<br />
Flow (2)<br />
l/min (gpm)<br />
Minimum Pressure<br />
(2) ,<br />
bar (psi)<br />
Deflector-To-<br />
Ceiling Distance<br />
(3)<br />
mm (in)<br />
Sprinkler Temperature<br />
Rating<br />
°C<br />
Minimum Spacing<br />
(4)<br />
m (ft)<br />
Quick 4,9 x 4,9 (16 x 16) 121 (32) 1,10 (16.0) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Quick 4,9 x 5,5 (16 x 18) 136 (36) 1,38 (20) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Quick 4,9 x 6,1 (16 x 20) 151 (40) 1,72 (25.0) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Quick 4,9 x 6,7 (16 x 22) 167 (44) 2,06 (30) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Quick 4,9 x 7,3 (16 x 24) 182 (48) 2,48 (36) 100 - 300 (4 - 12) 57, 68 3,1 (10)<br />
Standard 4,9 x 4,9 (16 x 16) 121 (32) 1,10 (16.0) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Standard 4,9 x 5,5 (16 x 18) 136 (36) 1,38 (20) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Standard 4,9 x 6,1 (16 x 20) 151 (40) 1,72 (25.0) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Standard 4,9 x 6,7 (16 x 22) 167 (44) 2,06 (30) 100 - 300 (4 - 12) 79 3,1 (10)<br />
Standard 4,9 x 7,3 (16 x 24) 182 (48) 2,48 (36) 100 - 300 (4 - 12) 79 3,1 (10)<br />
NOTES<br />
1. Backwall (where sprinkler is located) by sidewall (length of throw).<br />
2. Requirement is based on maintaining both minimum flow and minimum residual pressure.<br />
3. The centerline of the sprinkler waterway is located 11,1 mm (7/16”) below the deflector (Ref. Figures 1 and 2).<br />
4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall<br />
sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection<br />
area of the extended coverage sidewall sprinkler being utilized.<br />
TABLE D<br />
FM COVERAGE AND FLOW RATE CRITERIA