<strong>PV</strong> <strong>System</strong> 27® <strong>Metal</strong>-<strong>Clad</strong> <strong>Switchgear</strong><br />
A SYSTEM SOLUTION FOR 27kV POWER DISTRIBUTION<br />
POWERFUL, CAPABLE AND FUNCTIONAL<br />
Designed, engineered and manufactured by <strong>Powell</strong>,<br />
the <strong>PV</strong> <strong>System</strong> 27® switchgear system is a cost effective<br />
solution for 27kV class voltage systems. Design<br />
features include:<br />
• Circuit breaker design incorporates cycloaliphatic<br />
epoxy insulation elements.<br />
• Standard main bus supports are cycloaliphatic<br />
epoxy inserts mounted in high-strength glass<br />
polyester frame. Porcelain inserts available as<br />
an option.<br />
• Current transformers are mounted around<br />
capacitance-graded insulating spouts.<br />
• 125 kV BIL for high system insulation integrity.<br />
• Finish is a corrosion resistant electrostatic<br />
polyester powercoat paint process.<br />
• Circuit breakers roll in and out of the switchgear<br />
compartment assembly at floor level without<br />
the need for additional ramps or tools.<br />
True 27kV Design - Not just a 15kV<br />
Upgrade<br />
125kV BIL Insulation<br />
True Closed Door Circuit Breaker<br />
Racking<br />
Remote Racking Available<br />
Cycloaliphatic Epoxy Insulation <strong>System</strong><br />
SAFETY BY DESIGN<br />
<strong>Powell</strong> considers safety a critical design element, and<br />
<strong>PV</strong> <strong>System</strong> 27 is no exception. Designed and tested to<br />
meet or exceed all ANSI metal-clad requirements.<br />
• Grounded aluminum safety shutters<br />
automatically cover line and load stabs when<br />
circuit breaker is removed.<br />
• Design included closed door racking mechanism<br />
for improved operator safety.<br />
• Front-connected umbilical cord allows for<br />
testing of circuit breaker with actual control<br />
circuitry with circuit breaker disengaged. No<br />
operator needs to climb into the cell to<br />
acheive connectivity.<br />
Powered by Safety ®
Rated<br />
Maxiumum<br />
Voltage<br />
<strong>PV</strong> <strong>System</strong> 27 Circuit Breaker Rated on Symmetrical Rating Basis (ANSI C37.06)<br />
Rated<br />
Voltage<br />
Range Factor<br />
Insulated Withstand Test<br />
Voltages<br />
Low<br />
Frequency<br />
Full Wave<br />
Impulse<br />
Rated<br />
Continuous<br />
Current at<br />
60 Hz<br />
Rated Short<br />
Circuit (at Rated<br />
Maximum kV)<br />
Rated<br />
Interrupting<br />
Time<br />
Maximum Symmetrical<br />
Interrupting Capacity<br />
and Short Time Current<br />
Closing and<br />
Latching Capability<br />
2.7K times Rated<br />
Short Circuit Current<br />
kV rms K kV rms kv Crest Amps rms kA rms Cycles kA rms kA Crest<br />
27.0 1.0 60 125 1200 25 3 25 67<br />
27.0 1.0 60 125 2000 25 3 25 67<br />
27.0 1.0 60 125 1200 40 3 40 108<br />
27.0 1.0 60 125 2000 40 3 40 108<br />
SUPERIOR CAPABILITIES<br />
<strong>Powell</strong>’s <strong>PV</strong> <strong>System</strong> 27® switchgear design provides<br />
the user with the flexability to achieve a distribution<br />
system design without compromise. This is not simply<br />
an upgraded version of our 15KV switchgear pushed<br />
to its limits at 27kV, but instead a fully designed<br />
system engineered for application at 27kV.<br />
• 27kV vacuum circuit breakers are available with<br />
25kA or 40kA interrupting capacity and 3 cycle<br />
interrupting time.<br />
• Circuit breakers available with 1200A or 2000A<br />
continuous current ratings.<br />
• All circuit breakers fully rated for K factor =1.<br />
• Circuit breakers have been tested as definite<br />
purpose circuit breakers and a rated for back-toback<br />
capacitor switching at 250 amperes.<br />
• Full 125kV BIL rating on the bussing system.<br />
• Generous instrument compartment allows for<br />
highly complex control systems.<br />
• Power cables can enter from above or below.<br />
• Rear cable compartment provides plenty of<br />
room for ground CTs, cable terminations, and<br />
cable bending.<br />
TESTING<br />
<strong>PV</strong> <strong>System</strong> 27 meets or exceeds all applicable ANSI,<br />
IEEE, NEMA standards. It has been fully tested and test<br />
reports are available upon request.<br />
Publication No. 02067<br />
<strong>Powell</strong> Electrical <strong>System</strong>s, <strong>Inc</strong>.<br />
PO Box 12818<br />
Houston, TX • 77217<br />
Powered by Safety ®<br />
©2008 <strong>Powell</strong> <strong>Industries</strong>, <strong>Inc</strong>. • All rights reserved.<br />