6-2 Troubleshooting with the Indicators<br />
Indication<br />
Network Status<br />
Off<br />
Flashing Green<br />
Green<br />
Flashing Red<br />
Red<br />
Flashing<br />
Red/Green<br />
Probable Cause<br />
Device is not on-line<br />
- Device has not completed dup_MAC_id test.<br />
- Device not powered - check module status indicator<br />
Device is on-line but has no connections in the established<br />
state.<br />
Device on-line and has connections in the established state.<br />
One or more I/O connections in timed-out state<br />
Critical link failure - failed communication device. Device<br />
detected error that prevents it communicating on the<br />
network.<br />
Communication faulted device - the device has detected a<br />
network access error and is in communication faulted state.<br />
Device has received and accepted an Identify<br />
Communication Faulted Request - long protocol message.<br />
Indication<br />
Input Status<br />
Off<br />
Yellow<br />
Probable Cause<br />
Input inactive<br />
Input is active and under control<br />
Indication<br />
Output Status<br />
Off<br />
Yellow<br />
Flashing Yellow<br />
Flashing Red<br />
Flashing<br />
Red/Yellow<br />
Probable Cause<br />
Output inactive<br />
Output is active and under control<br />
Output is toggling<br />
Output is faulted (open, short or no output power)<br />
Output is toggling and faulted (possibly open)<br />
Publication 1734-UM003A-EN-P - August 2000