07.11.2014 Views

Wärtsilä 32 Product Guide

Wärtsilä 32 Product Guide

Wärtsilä 32 Product Guide

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Wärtsilä <strong>32</strong> - <strong>Product</strong> <strong>Guide</strong><br />

14. Automation System<br />

14. Automation System<br />

Wärtsilä Unified Controls – UNIC is a modular embedded automation system. UNIC C2 has a hardwired<br />

interface for control functions and a bus communication interface for alarm and monitoring.<br />

14.1 UNIC C2<br />

UNIC C2 is a fully embedded and distributed engine management system, which handles all control functions<br />

on the engine; for example start sequencing, start blocking, speed control, load sharing, normal stops and<br />

safety shutdowns.<br />

The distributed modules communicate over a CAN-bus. CAN is a communication bus specifically developed<br />

for compact local networks, where high speed data transfer and safety are of utmost importance.<br />

The CAN-bus and the power supply to each module are both physically doubled on the engine for full redundancy.<br />

Control signals to/from external systems are hardwired to the terminals in the main cabinet on the engine.<br />

Process data for alarm and monitoring are communicated over a Modbus TCP connection to external<br />

systems.<br />

Figure 14.1 Architecture of UNIC C2<br />

Short explanation of the modules used in the system:<br />

MCM<br />

ESM<br />

LCP<br />

LDU<br />

Main Control Module. Handles all strategic control functions (such as start/stop sequencing<br />

and speed/load control) of the engine.<br />

Engine Safety Module handles fundamental engine safety, for example shutdown due to<br />

overspeed or low lubricating oil pressure. The safety module is the interface to the shutdown<br />

devices and backup instruments.<br />

Local Control Panel is equipped with push buttons and switches for local engine control,<br />

as well as indication of running hours and safety-critical operating parameters.<br />

Local Display Unit offers a set of menus for retrieval and graphical display of operating<br />

data, calculated data and event history. The module also handles communication with<br />

external systems over Modbus TCP.<br />

136 <strong>Product</strong> <strong>Guide</strong> W<strong>32</strong> - 1/2013

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!