09.11.2014 Views

GEA MultiMAXX ® - Aspectenvironmental.com

GEA MultiMAXX ® - Aspectenvironmental.com

GEA MultiMAXX ® - Aspectenvironmental.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>GEA</strong> <strong>MultiMAXX</strong><br />

HN range: heating or cooling<br />

Model sizes IP 54 wide-blade fan Duty<br />

1 2 3 4<br />

HN 1 Air flow for basic air outlet m³/h 1,900 1,640 1,460 1,330<br />

Air-projection range for wall installation m 6.7 5.6 4.1 3.5<br />

Heating / cooling duty kW 7/3 11/4 14/6 16/8<br />

Air flow for secondary-air louver m³/h 1,610 1,440 1,310 1,220<br />

Air-projection range for wall installation m 7.6 5.9 4.9 4.3<br />

Heating / cooling duty kW 6/2 10/4 13/6 15/8<br />

HN 2 Air flow for basic air outlet m³/h 3,160 2,780 2,470 2,220<br />

Air-projection range for wall installation m 7.9 6.0 5.0 4.3<br />

Heating / cooling duty kW 11/5 18/7 22/9 26/13<br />

Air flow for secondary-air louver m³/h 2,740 2,430 2,190 2,010<br />

Air-projection range for wall installation m 9.2 7.1 6.0 5.2<br />

Heating / cooling duty kW 11/4 16/6 20/8 24/12<br />

HN 3 Air flow for basic air outlet m³/h 4,860 4,350 3,940 3,620<br />

Air-projection range for wall installation m 8.6 6.6 5.5 4.8<br />

Heating / cooling duty kW 17/7 28/11 35/15 41/20<br />

Air flow for secondary-air louver m³/h 4,300 3,900 3,580 3,330<br />

Air-projection range for wall installation m 10.2 7.9 6.7 5.9<br />

Heating / cooling duty kW 16/7 26/10 33/14 39/19<br />

HN 4 Air flow for basic air outlet m³/h 7,680 6,990 6,390 5,870<br />

Air-projection range for wall installation m 9.8 7.2 6.4 5.5<br />

Heating / cooling duty kW 26/11 43/17 55/23 66/32<br />

Air flow for secondary-air louver m³/h 6,920 6,310 5,810 5,390<br />

Air-projection range for wall installation m 11.6 9.6 7.7 6.7<br />

Heating / cooling duty kW 25/10 41/16 51/22 62/31<br />

HN 5 Air flow for basic air outlet m³/h 9,210 8,630 8,030 7,530<br />

Air-projection range for wall installation m 9.4 7.6 6.5 5.7<br />

Heating / cooling duty kW 34/14 55/21 70/30 85/42<br />

Air flow for secondary-air louver m³/h 8,440 7,970 7,460 7,050<br />

Air-projection range for wall installation m 11.8 9.5 8.2 7.3<br />

Heating / cooling duty kW 33/13 53/21 67/29 82/40<br />

System characteristics<br />

Wide-blade fan<br />

2-speed motor; 3-phase 400 V; IP 54<br />

Fan-speed ranges: MED – MIN<br />

Technical data for MED speed level<br />

Heat exchanger: Cu/Al<br />

Heating medium: PWW 70/50 °C; air entry 18 °C<br />

Cooling medium: PCW 6 / 12 °C; air entry 27 °C / 46 %<br />

Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />

design enclosures width height depth weight level (Lw) level (Lp) 1<br />

Wall installation mm mm mm kg dB(A) dB(A)<br />

HN 1 642 665 631 33 ... 37 66 51<br />

HN 2 738 761 646 40 ... 46 67 53<br />

HN 3 866 889 647 57 ... 66 68 54<br />

HN 4 1,026 1,049 727 80 ... 96 73 59<br />

HN 5 1,154 1,177 709 106 ... 126 71 57<br />

1<br />

Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />

01/2010 – PR-2010-0003-GB · Subject to modification 13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!