Cassettes<br />

New HEE impeller<br />

included<br />

COADIS 2<br />

COADIS 2 reaches new heights in comfort...<br />

... greater performance, lower energy consumption.<br />

Motor in option<br />

GLOBAL SATISFACTION FOR<br />

.… the end user: optimal air diffusion and the guarantee of global comfort.<br />

.… the architect: discreet integration inside the suspended ceiling.<br />

.… the designer: the proposition of an innovative solution<br />

.… the building occupier: an orientated air jet diffusion.<br />

.… the installer: a complete integrated “All-in-One” air diffusion system.<br />

.… the operator, thanks to real savings: low energy consumption, easy maintenance, ...<br />

USE<br />

COADIS 2 is a non-independent terminal air conditioning unit<br />

installed in suspended ceilings which combines low cost<br />

installation and operating advantages of central hot/chilled<br />

water production with individual temperature control for each<br />

room. Hydraulic connections can be installed in the suspended<br />

ceiling of the corridor adjacent to the room, and condensates<br />

can be drained by gravity (water pump not required).<br />

OPERATING PRINCIPLE<br />

The centrifugal fan uses a high-efficiency impeller to draw in air<br />

through a perforated return air register. The air is filtered then<br />

warmed or cooled as it passes through a high-efficiency heat<br />

exchanger containing hot or chilled water and/or an electric<br />

heater. Air is then pulsed horizontally into the room by<br />

COANDA effect through several directional diffusion nozzles<br />

with a high induction rate.<br />

RANGE<br />

COADIS 2 is particuarly adapted to office configurations up to<br />

3 panels wide (3 x 1.35 m) and 6 m long max.<br />

The 3 sizes of the COADIS 2 cover a range of air flows from<br />

130 to 800 m3/h, meeting the most stringent sound level<br />

requirements.<br />

Type 235/11 fits into 600 × 600 mm panels<br />

Type 235/22 fits into 600 × 900 mm panels<br />

Type 235/33 fits into 600 × 1200 mm panels<br />

Two models, Classic and Raised, are available, and in most<br />

cases there is no need for a draining pump (and therefore<br />

maintenance is reduced).<br />

The white RAL 9010 panel integrates perfectly into suspended<br />

ceilings.<br />

Consult us for special panel sizes: 650 × 650, 650 × 1300,<br />

675 × 675, 675 × 1350, etc.<br />

CIAT takes part in the EUROVENT fan coil unit certification programme, see performances in Eurovent mode, on last page of the range.<br />

The list of products and certified characteristics is given in the EUROVENT directory and on the web site www.eurovent-certification.com .<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

1


Cassettes<br />

COADIS 2<br />

COADIS 2 integrated<br />

inside the suspended ceiling<br />

Hydraulical<br />

pipings<br />

Condensates<br />

evacuation<br />

COADIS 2 are non-independent terminal air conditioning units<br />

installed at the end of a room. Their dimensions are suitable for<br />

integration into standard 600 × 600 suspended ceiling panels.<br />

The units are easy to install on four threaded rods, preferably<br />

with resilient mounts. The unit is designed so as to avoid the<br />

installation of a draining pump in most cases. The hydraulic<br />

connections can be made from pipes in the suspended ceiling<br />

of the corridor adjacent to the room, and condensates can be<br />

drained by gravity directly into the main evacuation pipe.<br />

Figure A<br />

COADIS 2 solves indoor air quality problems by a comfort-type<br />

approach, optimising air diffusion and minimising power<br />

consumption. The entire air diffusion system is included in the<br />

intake/outlet panel, with no additional ducts or grilles.<br />

To optimise air diffusion, we use nozzles with a high induction<br />

coefficient, causing the ambient air to be drawn along by the<br />

discharge air. This enables the air stream to stick to the ceiling<br />

by Coanda effect, avoiding draughts in the occupied area of the<br />

room. The units are designed for offices up to 5 or 6 metres<br />

long.<br />

The directional nozzles enable the range of the air jet and the<br />

lateral component to be adjusted (see Figure A).<br />

Similarly, the air jet can be directed at a chosen angle, allowing<br />

the COADIS 2 to be installed in a corner and still maintain good<br />

air distribution.<br />

2<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

COADIS 2 “GLOBAL COMFORT IS A REALITY”<br />

● Isovelocity curves at medium speed<br />

Room height (m)<br />

2.2<br />

0.16<br />

1.6<br />

1.4<br />

0.2<br />

0.16<br />

0.6<br />

0.11<br />

1.4<br />

1.0<br />

0.2<br />

1.4<br />

1.0<br />

0.6<br />

1.0<br />

0.6 0.6<br />

0.2<br />

0,16<br />

0.11<br />

0.2<br />

2.5<br />

2.1<br />

1.7<br />

1.3<br />

0.9<br />

COADIS 2<br />

0.16<br />

0.11<br />

0.16<br />

0.21<br />

0.21<br />

0.5<br />

0.1<br />

● Isotemperatures curve at medium speed<br />

0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0<br />

Room length (m)<br />

18<br />

18<br />

20 20<br />

20<br />

22<br />

22<br />

24 24<br />

24<br />

22<br />

24<br />

24<br />

2.5<br />

2.1<br />

Room height (m)<br />

25.5 25.5<br />

26.0 26.0<br />

25.0<br />

25.0<br />

24.5<br />

24.5<br />

24.5<br />

24.5<br />

25.0<br />

25.0<br />

25.0<br />

24.5<br />

25.0<br />

25.0<br />

24.5<br />

1.7<br />

1.3<br />

0.9<br />

0.5<br />

24.5<br />

25.0<br />

24<br />

0.1<br />

0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0<br />

Room length (m)<br />

Note: Cooling test drawings: cold water 7/12°C<br />

- inlet air 27°C<br />

- room air 25°C<br />

The COADIS 2 is designed in accordance with the<br />

requirements of the ISO 7730 standard: “Determination of the<br />

PMV and PPD indexes and specification of the conditions for<br />

thermal comfort conditions”.<br />

In short, the COADIS 2 is designed for optimal reduction of<br />

local discomfort factors in the occupied volume, as shown on<br />

the graphs above:<br />

● Recommended vertical temperature gradient with max.<br />

difference of 3°C.<br />

● Asymmetric radiation minimised by effective air mixing (cold<br />

wall phenomenon).<br />

● Recommended floor temperature between 23 and 25°C for a<br />

seated person.<br />

● No draught felt by the user, with air speeds not exceeding<br />

0.25 m/s in normal operating conditions.<br />

Acoustic comfort has not been overlooked, as shown by the<br />

comfort levels on next pages.<br />

We have defined the occupied zone in accordance with the<br />

CEN TC 156 WG6 European working group “Design criteria for<br />

the indoor environment”, that is:<br />

■ Distance from external window: 1.0 m<br />

■ Distance from external wall: 0.5 m<br />

■ Distance from entrance door: 1.0 m<br />

■ Distance from internal wall: 0.5 m<br />

■ Distance from floor: 1.8 m<br />

Obstacles in the air stream (beams, light fittings, etc.) should<br />

be avoided as the air jet can behave in one of three ways:<br />

■ Breaks away from the ceiling and drops, disturbing comfort.<br />

■ Breaks away from the ceiling then rises again downstream<br />

from the obstacle.<br />

■ Ignores the obstacle.<br />

It is clear that various construction trades must work together<br />

to ensure thermal and acoustic comfort and high quality air<br />

diffusion for users. On site tests should be carried out in order<br />

to optimise air diffusion and other parameters to obtain the<br />

desired comfort level.<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

3


Cassettes<br />

THE ADVANTAGES OF COADIS 2<br />

THIRD GENERATION CASSETTE<br />

COADIS 2<br />

The reference<br />

on the market<br />

Top-of-the-range polymer diffuser allowing<br />

an operation with high temperature hot<br />

water conditions of traditional boiler<br />

(90/70°C).<br />

Internal insulation with film for<br />

easy cleaning, avoids eroding<br />

the insulation and prevents dust<br />

build-up, greater exchange<br />

surface for higher power.<br />

4 lines of circular nozzles<br />

allowing air induction of<br />

over 40%.<br />

Nozzles flush to the panel<br />

Electrical box adapted to<br />

accommodate most of the<br />

existing control devices.<br />

1 motor per unit to minimise<br />

breakdowns and maintenance<br />

costs<br />

The high-efficiency, wide<br />

diameter (160 mm) impellers<br />

developed by CIAT maintain<br />

performance at suitable levels<br />

even when the filters are<br />

clogged.<br />

Hydraulic coils optimized to<br />

limit the latent power:<br />

energy saving, more<br />

exchange surface for<br />

more capacity.<br />

Condensates drain pan in<br />

polymer without water<br />

retention:<br />

→ No internal corrosion<br />

→ No proliferation of bacteria.<br />

New panel lined with<br />

protective, non-hazardous<br />

and environmentally-friendly<br />

acoustic and thermal<br />

insulation.<br />

Electric battery sheathed without resistive<br />

wire:<br />

→ Smooth stainless pipe inserted in the<br />

finned coil, for safety and optimal comfort<br />

→ Electric battery placed after the hydraulic<br />

coil (energy saving in heating/cooling +<br />

electric operation)<br />

Protected use:<br />

→ access to the fan motor<br />

assembly thanks to a CIAT<br />

tool delivered with the unit<br />

→ An exterior front panel<br />

screwed and not clipped.<br />

11 years’ experience for optimum quality.<br />

4<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

TECHNICAL DESCRIPTION<br />

Air return/discharge lower panel<br />

Perfectly adaptable to the dimensions of 600 x 600 panels to<br />

be integrated inside or outside the suspended ceiling.<br />

Uniform colour of all components White Ral 9010.<br />

Punched aluminium air inlet grille, quick dismantling by clips.<br />

Air discharge by directional circular nozzles with a high<br />

induction rate allowing the air jet adhesion to the ceiling<br />

by “Coanda effect”, avoiding cold air falling into the comfort<br />

zone. Clipped nozzles in thermoplastic material, V0 RAL 9010<br />

fire rating.<br />

One-piece sheet of protective, non-hazardous and<br />

environmentally-friendly insulation. M1 fire rating.<br />

Water coil (2-pipe or 4-pipe system)<br />

Galvanised sheet metal, copper tubes, aluminium fins.<br />

One-element connector with 40 mm between axis for direct<br />

control valve mounting.<br />

Air vent and draining.<br />

Working pressure 16 Bar (20°C).<br />

Test pressure 24 Bar.<br />

Max water temperature: 110°C (PN10).<br />

Water coil connectors on the left or right side of the unit when<br />

facing the discharge (to be mentioned on the order).<br />

Electrical battery (2-pipe system +<br />

electric)<br />

230/1/50 shrouded mono-tube electric heating element(s)<br />

set inside the water coil finned block ensuring an excellent<br />

distribution of the heating energy.<br />

2 capillary tube temperature limiters, with manual and<br />

automatic reset, inserted in the aluminium housing.<br />

Condensates recovery tray<br />

Self-extinguishing polymer material, fire resistance M1<br />

Without water retention, condensates drain at the same level<br />

as inside the sloping drain pan.<br />

Manually reversible connectors at the front or the rear of the<br />

drain pan.<br />

4 evacuation diameters: Ø 15, 16, 22 or 28 mm<br />

Mounted on slide together with the coil for easy dismantling.<br />

Ancillary pan<br />

Pan delivered separately. Clips onto pan made of<br />

self-extinguishing polymer,<br />

M1 fire rating.<br />

Fan motor assembly<br />

■ Motor<br />

7 speeds, 3 of them pre-wired in factory (possibility of<br />

modifying this wiring on site).<br />

Closed type, tropicalised, with protected shaft and ballbearings.<br />

Automatic thermal protector with standard opening on the winding<br />

Resilient mounts.<br />

Supply 230/1/50.<br />

Reduced consumption.<br />

■ Fan(s)<br />

Galvanised sheet metal casing(s).<br />

CIAT dia. 160 mm dynamically balanced ABS impeller(s) with<br />

forwared-curved blades and dual inlets.<br />

V0 Fire rating.<br />

Air filter<br />

Installed before the fan assembly.<br />

Flexible filtering media in renewable polyester fibers.<br />

Efficiency class EN 779: G3<br />

Fire resistance: M1<br />

Metallic rigid frame.<br />

Accessible by the air inlet grille assembled on clips.<br />

Standard structure<br />

Galvanised sheet metal.<br />

Thermal and acoustic insulation on air return/discharge in<br />

melamine resin, soft foam with open cells and aluminium film,<br />

fire resistance M1, 15mm thickness.<br />

Pre-cut holes for treated fresh air inlet Ø 100mm or 125mm.<br />

Oblong fixation holes.<br />

Electrical connection box<br />

Hydraulic connection side.<br />

Enclosed box.<br />

Electrical connection terminal On DIN rail as per EN 50022<br />

depth 7.5 mm.<br />

Customer wiring catch.<br />

Note: see installation manual for more details.<br />

COADIS 2<br />

ACCESSORIES<br />

Resilient attachment mounts.<br />

Smooth sleeve, Ø100 mm, for treated fresh air inlet.<br />

Smooth sleeve, Ø100 mm with self-adjusting module for<br />

treated fresh air inlet.<br />

CONTROL DEVICES<br />

Electromechanical wall-mounted thermostat range.<br />

V30 electronic controller range.<br />

V200 electronic controller range.<br />

V2000 ® communicating electronic controller range.<br />

V3000 communicating electronic controller range.<br />

LON control, consult us.<br />

Smooth sleeve, Ø125 mm with or without self-adjusting module<br />

(consult us).<br />

Condensate drain pump fitted to unit or in “ready-to-fit” kit.<br />

230 V thermo valve kit.<br />

OPTIONAL (CONSULT US)<br />

- For specific water and air mode.<br />

- 60 Hz Operation (230V).<br />

- For optimization of suspended ceiling support profile other<br />

than T-piece.<br />

- For dimensions other than standard 600 x 600.<br />

- High Energy Efficiency (HEE) motor.<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

5


GLOBAL VIEW<br />

Cassettes<br />

COADIS 2<br />

Punched steel sheet air inlet<br />

grille clipped without screw with<br />

air filter (possibility to remove<br />

the fan assembly via the grille)<br />

Directional nozzles to adjust air jet<br />

COADIS 2<br />

FIXATION<br />

Fixing holes<br />

Ø12 x 30<br />

Threaded M8 rod<br />

(not supplied)<br />

Pre-cut hole to fit a sleeve of<br />

Ø100mm or Ø125mm with or<br />

without self-adjusting<br />

module (accessory).<br />

If air return sensor used, plan<br />

the fresh air intake at opposite side.<br />

Metallic closed electrical box<br />

with oblong holes to avoid<br />

taking out screws.<br />

. Dry drain pan, without water retention,<br />

avoiding bacteria proliferation.<br />

. Self-extinguishing polymer material<br />

smooth drain pan.<br />

. Reversible connections with<br />

4 diameters : 15, 16, 22 or 28mm.<br />

6<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

DIMENSIONS<br />

Classic model<br />

79<br />

80<br />

17 17<br />

137 A<br />

B<br />

289,5<br />

305<br />

Cooling coil<br />

16 563<br />

595<br />

Heating coil<br />

16<br />

COADIS 2<br />

Holes<br />

12 x 30<br />

2 Pre-cut holes for treated<br />

fresh air (see accessories)<br />

129<br />

16<br />

*<br />

214<br />

176<br />

595<br />

16<br />

500<br />

300<br />

104,5<br />

17<br />

= C<br />

=<br />

E<br />

* Possibility to permutate condensates draining<br />

H: Fixing distance between axis 235/11<br />

F: Fixing distance between axis 235/22 and 235/33<br />

MOUNTING<br />

Hydraulic connections<br />

4<br />

3<br />

1<br />

80 80<br />

102<br />

Classic<br />

COADIS 2<br />

D<br />

17<br />

222<br />

A B C D E<br />

Mass<br />

(kg)<br />

235 / 11 420 595 X 250 309 22<br />

235 / 22 720 895 468 550 X 30<br />

235 / 33 1020 1195 768 850 X 42<br />

IMPORTANT: Drain pan gravity height to<br />

drain condensates = 93 mm<br />

~ 4 to 6 m piping length (lcm/m Slope)<br />

AB<br />

B<br />

A<br />

G1/2"<br />

G3/8"<br />

o<br />

i<br />

5 2<br />

6<br />

G1/2"<br />

G3/8"<br />

<br />

<br />

<br />

<br />

Air vent<br />

Coil drain<br />

One-element connector with 40mm distance between axis<br />

Male/female connector with flat bearing surface<br />

3/8” 1/2”(accessory)<br />

Example of a 2 or 4-way valve with flat bearing surface<br />

(included with the control device loop)<br />

O-ring gasket<br />

i : Water coil inlet<br />

o : Water coil outlet<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

7


DIMENSIONS<br />

Cassettes<br />

COADIS 2<br />

Raised model<br />

Cooling coil<br />

Heating coil<br />

Holes<br />

12 x 30<br />

2 Pre-cut holes for treated<br />

fresh air (see accessories)<br />

*<br />

D<br />

: Possibility to permutate condensates draining<br />

*<br />

H: Fixing distance between axis 235/11<br />

F: Fixing distance between axis 235/22 and 235/33<br />

MOUNTING<br />

Raised<br />

COADIS 2<br />

A B C D E<br />

Mass<br />

(kg)<br />

235 / 11 A 595 X 250 309 24<br />

235 / 22 441 895 468 550 X 33<br />

235 / 33 741 1195 768 850 X 45<br />

Hydraulic connections<br />

1<br />

80 80<br />

IMPORTANT: Drain pan gravity height to<br />

drain condensates = 159 mm<br />

~ 10 to 12 m piping length (lcm/m Slope)<br />

4<br />

3<br />

AB<br />

B<br />

A<br />

G1/2"<br />

G3/8"<br />

o<br />

i<br />

5 2<br />

6<br />

G1/2"<br />

G3/8"<br />

<br />

<br />

<br />

<br />

Air vent<br />

Coil drain<br />

One-element connector with 40mm distance between axis<br />

Male/female connector with flat bearing surface<br />

3/8” 1/2”(accessory)<br />

Example of a 2 or 4-way valve with flat bearing surface<br />

(included with the control device loop)<br />

O-ring gasket<br />

I : Water coil inlet<br />

o : Water coil outlet<br />

8<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

PERFORMANCES FOR CLASSIC AND RAISED MODELS<br />

COADIS 2<br />

235 / 11<br />

235 / 22<br />

235 / 33<br />

Motor<br />

reference<br />

Air flow<br />

m 3 /h<br />

Heating<br />

capacity,<br />

2-pipe<br />

system<br />

coil W<br />

Heating<br />

Mean temperature rise on the air<br />

Cooling capacity W capacity,<br />

in K<br />

Comfort level<br />

4-pipe<br />

Additional electric heater<br />

ISO or NR<br />

system<br />

230/1/50<br />

Total Sensible coil W<br />

1R 1R 2R<br />

600 W 1200 W<br />

R1 420 7090 2 350 1 830 2 530 41 4,2 8,5<br />

R2 390 6710 2 250 1 730 2 450 39 4,6 9,1<br />

R3 345 6130 2 060 1 560 2 320 36 5,2 10,1<br />

R4 295 5420 1 830 1 370 2 150 34 6,0 12,1<br />

R5 225 4340 1 500 1100 1 860 26 7,9 15,8<br />

R6 160 3190 1130 812 1 510 19 11,1 22,3<br />

R7 105 2120 783 565 1 150 < 15 17,0 33,9<br />

900 W 1800 W<br />

R1 685 9 480 3 560 2 790 4 870 44 3,9 7,8<br />

R2 620 8 880 3 330 2 580 4 640 41 4,3 8,5<br />

R3 530 7 990 3 000 2 290 4 280 37 5,0 10,1<br />

R4 450 7 110 2 690 2 020 3 920 34 5,9 11,9<br />

R5 375 6 210 2 360 1 750 3 530 29 7,1 14,3<br />

R6 275 5 170 1 970 1 440 3 060 21 12,4 24,9<br />

R7 215 4 020 1 530 1100 2 500 < 15 3,1 6,3<br />

1200 W 1800 W 2400 W<br />

R1 855 13 400 5 150 3 890 7 230 43 4,2 6,3 8,3<br />

R2 725 11 900 4 630 3 430 6 630 40 4,9 7,4 9,8<br />

R3 600 10 400 4070 2 960 5 970 35 5,9 8,9 11,9<br />

R4 480 8 790 30480 2 470 5 240 29 7,4 11,1 14,9<br />

R5 390 7 440 2 970 2 080 4 590 23 9,1 13,7 18,3<br />

R6 305 6 050 2 440 1 680 3 880 16 11,2 17,5 23,4<br />

R7 205 4 220 1 720 1 170 2 870 < 15 17,4 26,1 34,8<br />

COADIS 2<br />

Standard factory wiring.<br />

Hot water temp.: 90/70 °C, winter air temp.: 19 °C - Cold water temp.: 7/12 °C, summer air temp.: 27 °C 50% RH.<br />

Comfort level: attenuation level of room and installation: 12 dB.<br />

COIL CONTENT (LITRES)<br />

2-pipe system<br />

4-pipe system<br />

COADIS 2 235 / 11 235 / 22 235 / 33<br />

Cold water coil or<br />

Hot water coil<br />

0,48 0,74 1,00<br />

Cold water coil 0,48 0,74 1,00<br />

Hot water coil 0,16 0,23 0,31<br />

ELECTRICAL CHARACTERISTICS 230 V - 1 PH - 50 HZ<br />

COADIS 2 235 / 11 235 / 22 235 / 33<br />

Motor wiring R1 R2 R3 R4 R5 R6 R7 R1 R2 R3 R4 R5 R6 R7 R1 R2 R3 R4 R5 R6 R7<br />

Power input W 73 62 51 43 39 34 30 95 82 69 59 54 48 44 108 90 75 62 56 50 45<br />

Absorbed current A 0,32 0,27 0,22 0,19 0,17 0,15 0,13 0,41 0,37 0,3 0,26 0,23 0,21 0,19 0,47 0,39 0,32 0,27 0,24 0,22 0,2<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

9


Cassettes<br />

COADIS 2<br />

Standard unit (without valve/accessory)<br />

COADIS 2<br />

Connectors on left<br />

2-pipe<br />

system<br />

Water coil only<br />

4-pipe<br />

system<br />

Connectors on right<br />

2-pipe<br />

system<br />

4-pipe<br />

system<br />

Connectors on left<br />

2-pipe system<br />

+ 2 wire system<br />

Water coil + electric element<br />

Connectors on right<br />

2-pipe system<br />

+ 2 wire system<br />

1R 2R 1R 2R<br />

CLASSIC<br />

RAISED<br />

235/11 CLA<br />

600x600<br />

235/22 CLA<br />

600x900<br />

235/33 CLA<br />

600x1200<br />

235/11 REH<br />

600x600<br />

235/22 REH<br />

600x900<br />

235/33 REH<br />

600x1200<br />

600 W 1200 W 600 W 1200 W<br />

Code 7017667 7017669 7017668 7017670 7017671 7017672 7017673 7017674<br />

● ● ● ● ● ● ● ● ●<br />

900 W 1800 W 900 W 1800 W<br />

Code 7017675 7017677 7017676 7017678 7017679 7017687 7017688 7017689<br />

● ● ● ● ● ● ● ● ●<br />

1200 W 1800 W 2400 W 1200 W 1800 W 2400 W<br />

Code 7017691 7017694 7017692 7017695 7017696 7017697 7017698 7017699 7017700 7017701<br />

● ● ● ● ● ● ● ● ● ● ●<br />

600 W 1200 W 600 W 1200 W<br />

Code 7017702 7017704 7017703 7017705 7017706 7017707 7017708 7017709<br />

● ● ● ● ● ● ● ● ●<br />

900 W 1800 W 900 W 1800 W<br />

Code 7017710 7017712 7017711 7017713 7017714 7017715 7017716 7017717<br />

● ● ● ● ● ● ● ● ●<br />

1200 W 1800 W 2400 W 1200 W 1800 W 2400 W<br />

Code 7017719 7017722 7017720 7017723 7017724 7017725 7017726 7017727 7017728 7017730<br />

● ● ● ● ● ● ● v ● ● ●<br />

Units are in stock to meet your requirements at short notice (controls in stock, see chapter on controls)<br />

Option (mounted on the unit, classic model only)<br />

Designation<br />

Code<br />

●<br />

Condensate drain pump mounted on the<br />

unit with overflow safety device.<br />

- 7l/h maximum flow for 1m draining<br />

height and 5m maximal length of piping.<br />

- 6l/h maximum flow for 1m draining<br />

height and 10m maximal length of piping.<br />

Draining: 6mm internal diameter flexible<br />

tube, 8mm diameter nozzle.<br />

For higher drain heights, consult us.<br />

One regulation for each valve must be<br />

added to allow slaving the overflow<br />

safety device to the valve closing<br />

(condensates stopped)***.<br />

Approximate calculation of the<br />

condensed water flow :<br />

P total - P sensible (W)<br />

Qv (l/h) =<br />

680<br />

(View without valve as an indication).<br />

E045004<br />

●<br />

*** For pre-assembly, see accessories<br />

10<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

Units with air control in stock<br />

CONTROL ON AIR Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />

COADIS 2 CLASSIC 2TG Unit code (a) 7173524 7173526 7173528<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

On/Off + 3 speeds + manual dial - heating or<br />

cooling ONLY<br />

RTR-E 7015 5950338<br />

RTR-E 7009 7191518<br />

RTR-E code (1) 5201023<br />

Total price (a+1) ● ● ●<br />

RTR-E code (2) 7124612<br />

Total price (a+2) ● ● ●<br />

COADIS 2<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating/cooling with automatic changeover,<br />

supplied as a kit<br />

A34H 7175611<br />

V30(3) code<br />

+ Co (4) sensor<br />

7166781 + 7163008<br />

Total price (a+3+4) ● ● ●<br />

COADIS 2 CLA or REH 2TG<br />

WALL THERMOSTAT<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating or cooling only<br />

Cooling A32H<br />

Heating A30H<br />

7175609<br />

7175607<br />

V30 (3) code 7166781<br />

Total price (a+3) ● ● ●<br />

Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />

COADIS 2 RAISED 2TG Unit code (a) 7174521 7174523 7174525<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

On/Off + 3 speeds + manual dial - heating or<br />

cooling only<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating/cooling with automatic changeover,<br />

supplied as a kit<br />

RTR-E 7015 5950338<br />

RTR-E 7009 7191518<br />

A34H 7175611<br />

RTR-E code (1) 5201023<br />

Total price (a+1) ● ● ●<br />

RTR-E code (2) 7124612<br />

Total price (a+2) ● ● ●<br />

V30(3) code<br />

+ Co (4) sensor<br />

7166781 + 7163008<br />

Total price (a+3+4) ● ● ●<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating or cooling only<br />

Cooling A32H<br />

Heating A30H<br />

7175609<br />

7175607<br />

V30 (3) code 7166781<br />

Total price (a+3) ● ● ●<br />

Applications<br />

Diagrams<br />

CLA 235/11<br />

2TG+600W<br />

CLA 235/22<br />

2TG+900W<br />

CLA 235/33<br />

2TG+1200W<br />

COADIS 2 CLASSIC 2TG+1R Unit code (a) 7180280 7180284 7180288<br />

COADIS 2 CLA or REH 2TG + elec.<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating/cooling with automatic changeover,<br />

supplied as a kit<br />

A38H 7175630<br />

Applications<br />

Diagrams<br />

V30(3) code<br />

+ Co (4) sensor<br />

7166781 + 7163008<br />

Total price (a+3+4) ● ● ●<br />

REH 235/11<br />

2TG+600W<br />

REH 235/22<br />

2TG+900W<br />

REH 235/33<br />

2TG+1200W<br />

COADIS 2 RAISED 2TG+1R Unit code (a) 7180294 7180298 7180302<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating/cooling with automatic changeover,<br />

supplied as a kit<br />

A38H 7175630<br />

V30(3) code<br />

+ Co (4) sensor<br />

Total price (a+3+4)<br />

7166781 + 7163008<br />

● ● ●<br />

Units in stock to ensure speedy delivery<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

11


Cassettes<br />

COADIS 2<br />

2-pipe water control units in stock<br />

WATER CONTROL Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />

COADIS 2 CLASSIC 2TG<br />

+ 230V 2-way valve kit<br />

Unit code (a)<br />

+ kit (7) code<br />

7173524<br />

+ 7185600<br />

7173526<br />

+ 7185600<br />

7173528<br />

+ 7185600<br />

WALL THERMOSTAT + 230V 2-way valve kit<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

On/Off + 3 speeds + manual dial - heating or<br />

cooling only<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating or cooling only<br />

COADIS 2 RAISED 2TG<br />

+ 230V 2-way valve kit<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

RTR-E 7012 5950384<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

Cooling E32H<br />

Heating E30H<br />

5950268<br />

5950459<br />

7175615<br />

7175613<br />

RTR-E (5) code 5201024<br />

Total price (a+7+5) ● ● ●<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code 7166781<br />

Total price (a+7+3) ● ● ●<br />

Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />

RTR-E 7012 5950384<br />

Unit code (a)<br />

+ kit (7) code<br />

7174521<br />

+ 7185600<br />

7174523<br />

+ 7185600<br />

RTR-E (5) code 5201024<br />

7174525<br />

+ 7185600<br />

Total price (a+7+5) ● ● ●<br />

On/Off + 3 speeds + manual dial - heating or<br />

cooling only<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

5950268<br />

5950459<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

COADIS2 CLA or REH 2TG<br />

WALL THERMOSTAT + 230V 2-way valve kit<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating or cooling only<br />

COADIS 2 CLASSIC 2TG<br />

+ 230V 4-way valve kit<br />

Cooling E32H<br />

Heating E30H<br />

7175615<br />

7175613<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch RTR-E 7012 5950384<br />

On/Off + 3 speeds + manual dial - heating or<br />

cooling only<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating/cooling with automatic changeover,<br />

supplied as a kit<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating or cooling only<br />

COADIS 2 RAISED 2TG<br />

+ 230V 4-way valve kit<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

On/Off + 3 speeds + manual dial - heating or<br />

cooling only<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating/cooling with automatic changeover,<br />

supplied as a kit<br />

V30(3) code 7166781<br />

Total price (a+7+3) ● ● ●<br />

Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

5950268<br />

5950459<br />

E35H 7175618<br />

Cooling E33H<br />

Heating E31H<br />

7175615<br />

7175613<br />

Unit code (a)<br />

+ kit (7) code<br />

7173524<br />

+ 7185601<br />

7173526<br />

+ 7185601<br />

RTR-E (5) code 5201024<br />

7173528<br />

+ 7185601<br />

Total price (a+7+5) ● ● ●<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code<br />

+ Co (4) sensor<br />

7166781 + 7163008<br />

Total price<br />

(a+7+3+4)<br />

● ● ●<br />

V30 (3) code 7166781<br />

Total price (a+7+3) ● ● ●<br />

Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />

RTR-E 7012 5950384<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

5950268<br />

5950459<br />

E35H 7175618<br />

Unit code (a)<br />

+ kit (7) code<br />

7174521<br />

+ 7185601<br />

7174523<br />

+ 7185601<br />

RTR-E (5) code 5201024<br />

7174525<br />

+ 7185601<br />

Total price (a+7+5) ● ● ●<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code<br />

+ Co (4) sensor<br />

Total price<br />

(a+7+3+4)<br />

7166781 + 7163008<br />

● ● ●<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Heating or cooling only<br />

Cooling E33H<br />

Heating E31H<br />

7175615<br />

7175613<br />

V30 (3) code 7166781<br />

Total price<br />

(a+7+3)<br />

● ● ●<br />

Units in stock to ensure speedy delivery<br />

12<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

2-pipe/2-wire water control units in stock<br />

WATER CONTROL Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />

WALL THERMOSTAT + 230V 2-way valve kit<br />

COADIS 2 CLASSIC 2TG<br />

+ 230V 2-way valve kit<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

On/Off + 3 speeds + manual dial - Cooling +<br />

electric heater with deadband<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Cooling + electric heater<br />

with deadband<br />

COADIS 2 RAISED 2TG<br />

+ 230V 2-way valve kit<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

RTR-E 7012 5950384<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

Cooling E32H<br />

Heating E30H<br />

5950268<br />

5950459<br />

7175615<br />

7175613<br />

Unit code (a)<br />

+ kit (7) code<br />

7173524<br />

+ 7185600<br />

7173526<br />

+ 7185600<br />

RTR-E (5) code 5201024<br />

7173528<br />

+ 7185600<br />

Total price (a+7+5) ● ● ●<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code 7166781<br />

Total price (a+7+3) ● ● ●<br />

Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />

RTR-E 7012 5950384<br />

Unit code (a)<br />

+ kit (7) code<br />

7174521<br />

+ 7185600<br />

7174523<br />

+ 7185600<br />

RTR-E (5) code 5201024<br />

7174525<br />

+ 7185600<br />

Total price (a+7+5) ● ● ●<br />

COADIS 2<br />

COADIS 2 CLA or REH 2TG<br />

WALL THERMOSTAT + 230V 2-way valve kit<br />

On/Off + 3 speeds + manual deal - Cooling +<br />

electric heater with deadband<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Cooling + electric heater<br />

with deadband<br />

COADIS 2 CLASSIC 2TG<br />

+ 1R + 230V 4-way valve kit<br />

RTR-E 7011 Froid<br />

RTR-E 7011 Chaud<br />

Cooling E32H<br />

Heating E30H<br />

5950268<br />

5950459<br />

7175615<br />

7175613<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch RTR-E 7012 5950384<br />

On/Off + 3 speeds + manual deal - Cooling +<br />

electric heater with deadband<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Cooling + electric heater<br />

with deadband<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Automatic heating/cooling with electric heater<br />

and automatic changeover, supplied as a kit<br />

COADIS 2 RAISED 2TG<br />

+ 230V 2-way valve kit<br />

On/Off + 3 speeds + manual dial -<br />

heating/cooling with manual toggle switch<br />

On/Off + 3 speeds + manual deal - Cooling +<br />

electric heater with deadband<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Cooling + electric heater with deadband<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code 7166781<br />

Total price (a+7+3) ● ● ●<br />

Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

5950268<br />

5950459<br />

E35H 7175618<br />

Cooling E33H<br />

Heating E31H<br />

7175615<br />

7175613<br />

Unit code (a)<br />

+ kit (7) code<br />

7173524<br />

+ 7185601<br />

7173526<br />

+ 7185601<br />

RTR-E (5) code 5201024<br />

7173528<br />

+ 7185601<br />

Total price (a+7+5) ● ● ●<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code<br />

+ Co (4) sensor<br />

7166781 + 7163008<br />

Total price<br />

(a+7+3+4)<br />

● ● ●<br />

V30 (3) code 7166781<br />

Total price (a+7+3) ● ● ●<br />

Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />

RTR-E 7012 5950384<br />

Cooling RTR-E 7011<br />

Heating RTR-E 7011<br />

5950268<br />

5950459<br />

E35H 7175618<br />

Unit code (a)<br />

+ kit (7) code<br />

7174521<br />

+ 7185601<br />

7174523<br />

+ 7185601<br />

RTR-E (5) code 5201024<br />

7174525<br />

+ 7185601<br />

Total price (a+7+5) ● ● ●<br />

RTR-E (6) code 5201018<br />

Total price (a+7+6) ● ● ●<br />

V30(3) code<br />

+ Co (4) sensor<br />

Total price<br />

(a+7+3+4)<br />

7166781 + 7163008<br />

● ● ●<br />

Wall-mounted V30 with +/- dial, 3 speeds -<br />

Automatic heating/cooling with electric heater<br />

and automatic changeover, supplied as a kit<br />

Cooling E33H<br />

Heating E31H<br />

7175615<br />

7175613<br />

V30 (3) code 7166781<br />

Total price<br />

(a+7+3)<br />

● ● ●<br />

Units in stock to ensure speedy delivery.<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

13


Cassettes<br />

COADIS 2<br />

4-pipe water control units in stock<br />

WATER CONTROL Applications Diagrams CLA 235/11 4TG CLA 235/22 4TG CLA 235/33 4TG<br />

COADIS 2 CLASSIC 4TG<br />

+ two 230V 2-way valve kits<br />

Unit code (a) +<br />

kit (7) code<br />

7173530<br />

+ 2 x 7185600<br />

7173532<br />

+ 2 x 7185600<br />

7173534<br />

+ 2 x 7185600<br />

On/Off + 3 speeds + manual dial -<br />

Heating/cooling with deadband<br />

RTR-E 7203 5950884<br />

RTR-E (6) code 5201021<br />

Total price (a+7+6) ● ● ●<br />

WALL THERMOSTAT + 230V 2-way valve kit<br />

Wall-mounted V30 with +/- dial, 3 speeds<br />

- Heating / cooling<br />

COADIS 2 RAISED 4TG<br />

+ two 230V 2-way valve kits<br />

On/Off + 3 speeds + manual dial -<br />

Heating/cooling with deadband<br />

E40H 7175641<br />

V30 (3) code 7166781<br />

Total price (a+7+3+4) ● ● ●<br />

Applications Diagrams REH 235/11 4TG REH 235/22 4TG REH 235/33 4TG<br />

RTR-E 7203 5950884<br />

Unit code (a) +<br />

kit (7) code<br />

7174527<br />

+ 2 x 7185600<br />

7174529<br />

+ 2 x 7185600<br />

RTR-E (6) code 5201021<br />

7174531<br />

+ 2 x 7185600<br />

Total price (a+7+6) ● ● ●<br />

COADIS 2 CLA or REH 4TG<br />

Wall-mounted V30 with +/- dial,<br />

3 speeds - Heating / cooling<br />

COADIS 2 CLASSIC 4TG<br />

+ two 230V 2-way valve kits<br />

E40H 7175641<br />

V30 (3) code 7166781<br />

Total price (a+7+3+4) ● ● ●<br />

Applications Diagrams CLA 235/11 4TG CLA 235/22 4TG CLA 235/33 4TG<br />

Unit code (a) +<br />

kit (7) code<br />

7173530<br />

+ 2 x 7185601<br />

7173532<br />

+ 2 x 7185601<br />

7173534<br />

+ 2 x 7185601<br />

On/Off + 3 speeds + manual dial -<br />

Heating/cooling with deadband<br />

RTR-E 7203 5950884<br />

RTR-E (6) code 5201021<br />

Total price (a+7+6) ● ● ●<br />

WALL THERMOSTAT + 230V 2-way valve kit<br />

Wall-mounted V30 with +/- dial,<br />

3 speeds - Heating / cooling<br />

COADIS 2 RAISED 4TG<br />

+ two 230V 2-way valve kits<br />

On/Off + 3 speeds + manual dial -<br />

Heating/cooling with deadband<br />

E41H 7175641<br />

V30 (3) code 7166781<br />

Total price (a+7+3+4) ● ● ●<br />

Applications Diagrams REH 235/11 4TG REH 235/22 4TG REH 235/33 4TG<br />

RTR-E 7203 5950884<br />

Unit code (a) +<br />

kit (7) code<br />

7174527<br />

+ 2 x 7185601<br />

7174529<br />

+ 2 x 7185601<br />

RTR-E (6) code 5201021<br />

7174531<br />

+ 2 x 7185601<br />

Total price (a+7+6) ● ● ●<br />

Wall-mounted V30 with +/- dial,<br />

3 speeds - Heating / cooling<br />

E41H 7175641<br />

V30 (3) code 7166781<br />

Total price (a+7+3+4) ● ● ●<br />

Units in stock to ensure speedy delivery.<br />

14<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A


Cassettes<br />

Accessories (supplied separately)<br />

SU1<br />

Designation<br />

Resilient mounts supplied separately<br />

(4 required per unit).<br />

Code<br />

●<br />

0219453 ●<br />

COADIS 2<br />

MO1 Smooth sleeve Ø100 mm with nuts and screws 7013442 ●<br />

MO7<br />

MO4<br />

Smooth spigot ext. Ø 100 mm(1) with self-adjusting<br />

module, fitted with a gasket. Packed with nuts and screws<br />

and drawing.<br />

The air flow rate controller is working to supply a<br />

determined flow(1) with air difference pressure between<br />

50 and 100 Pa.<br />

(1) 3 flow rates are available by use of 3 sets of wedges.<br />

The lower air flow is by default.<br />

(2) Diameter 12 mm, consult us.<br />

15 / 30 / 45 m 3 /h<br />

(1)<br />

60 / 75 / 90 m 3 /h<br />

(1)<br />

7013440 ●<br />

7013544 ●<br />

Kit condensate drain pump for classic model to mount on the unit with overflow safety device.<br />

- 7l/h maximum flow for 1m draining height and 5m maximal length of piping.<br />

- 6l/h maximum flow for 1m draining height and 10m maximal length of piping.<br />

Draining: 6mm internal diameter flexible tube, 8mm diameter nozzle.<br />

For higher drain heights, consult us.<br />

One regulation for each valve must be added to allow slaving the overflow safety device to the valve closing<br />

(condensates stopped).<br />

Fixation assembly supplied with the diagram.<br />

Approximate calculation of the condensed water flow : Qv (l/h) =<br />

P total - P sensible (W)<br />

680<br />

7023316 ●<br />

RA1<br />

2 piece male/female connector 3/8” 1/2”<br />

including gaskets<br />

5202314<br />

+<br />

5200708<br />

●<br />

Accessories are in stock to meet your requirements at short notice<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />

15


Cassettes<br />

COADIS 2<br />

EUROVENT PERFORMANCES - 2-PIPE SYSTEM<br />

CIAT participates in Eurovent's certification programme for fan heaters.<br />

Up-to-date information is available on the Eurovent web site.<br />

www.eurovent-certification.com<br />

Eurovent conditions, 2 tube system:<br />

- Summer: cold water 7/12°C, air 27°C WB 19°C<br />

- Winter: Hot water inlet: 50°C for water flow rate determined in summer conditions, air 20°C<br />

COADIS 2<br />

Motor ref<br />

Sensible cooling<br />

capacity<br />

Total cooling<br />

capacity<br />

Total heating<br />

capacity<br />

Dp cooling<br />

Dp heating<br />

Lw<br />

kW kW kW kPa kPa dB A<br />

R2 1,66 1.91 2,71 28.9 24,5 56<br />

235/11<br />

R4 1.33 1.58 2,2 20.6 17.4 50<br />

R6 0.799 1,00 1,3 9.10 7.84 37<br />

R2 2,46 2,82 3,66 21.0 18,0 57<br />

235/22<br />

R4 1,92 2,26 2,93 14.1 12,2 50<br />

R6 1,36 1,65 2,12 7.84 6,90 39<br />

R2 3,16 3,85 4,93 39.1 33,7 55<br />

235/33<br />

R3 2,73 3,38 4,3 31.0 26,7 51<br />

R6 1,55 2,02 2,49 12.2 10,6 34<br />

Dp: water pressure drop (kPa)<br />

Lw: overall sound power level (dBA)<br />

EUROVENT PERFORMANCES - 4-PIPE SYSTEM<br />

CIAT participates in Eurovent's certification programme for fan heaters.<br />

Up-to-date information is available on the Eurovent web site.<br />

www.eurovent-certification.com<br />

Eurovent conditions, 4 tube system:<br />

- Summer: cold water 7/12°C, air 27°C WB 19°C<br />

- Winter: hot water inlet 70°C/60°C, air 20°C<br />

COADIS 2<br />

Motor ref<br />

Sensible cooling<br />

capacity<br />

Total cooling<br />

capacity<br />

Total heating<br />

capacity<br />

Dp cooling<br />

Dp heating<br />

Lw<br />

235/11<br />

235/22<br />

235/33<br />

Dp: water pressure drop (kPa)<br />

Lw: overall sound power level (dBA)<br />

kW kW kW kPa kPa dB A<br />

R2 1,66 1,91 1,83 28.9 3.26 56<br />

R4 1,33 1,58 1,60 20.6 2.57 50<br />

R6 0,802 1,00 1,12 9.10 1.37 37<br />

R2 2,46 2,82 3,37 21.0 13.3 57<br />

R4 1,92 2,26 2,85 14.1 9.84 50<br />

R6 1,36 1,65 2,21 7.84 6.34 39<br />

R2 3,29 3,95 4,77 41.8 29.1 55<br />

R3 2,83 3,47 4,29 33.1 24.2 51<br />

R6 1,59 2,06 2,77 12.9 11.2 34<br />

This document is non-contractual.As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification.<br />

Head office<br />

Avenue Jean Falconnier - B.P. 14<br />

01350 - Culoz - France<br />

Tel.: +33 (0)4 79 42 42 42 - Fax: +33 (0)4 79 42 42 10<br />

info@ciat.fr - www.ciat.com<br />

CIAT Service<br />

Tel.: +33 (0)4 79 42 42 90 - Fax: +33 (0)4 79 42 42 13<br />

Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26 000 000 € - R.C.S. Belley B 545 620 114<br />

16<br />

AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!