Cassettes<br />
New HEE impeller<br />
included<br />
COADIS 2<br />
COADIS 2 reaches new heights in comfort...<br />
... greater performance, lower energy consumption.<br />
Motor in option<br />
GLOBAL SATISFACTION FOR<br />
.… the end user: optimal air diffusion and the guarantee of global comfort.<br />
.… the architect: discreet integration inside the suspended ceiling.<br />
.… the designer: the proposition of an innovative solution<br />
.… the building occupier: an orientated air jet diffusion.<br />
.… the installer: a complete integrated “All-in-One” air diffusion system.<br />
.… the operator, thanks to real savings: low energy consumption, easy maintenance, ...<br />
USE<br />
COADIS 2 is a non-independent terminal air conditioning unit<br />
installed in suspended ceilings which combines low cost<br />
installation and operating advantages of central hot/chilled<br />
water production with individual temperature control for each<br />
room. Hydraulic connections can be installed in the suspended<br />
ceiling of the corridor adjacent to the room, and condensates<br />
can be drained by gravity (water pump not required).<br />
OPERATING PRINCIPLE<br />
The centrifugal fan uses a high-efficiency impeller to draw in air<br />
through a perforated return air register. The air is filtered then<br />
warmed or cooled as it passes through a high-efficiency heat<br />
exchanger containing hot or chilled water and/or an electric<br />
heater. Air is then pulsed horizontally into the room by<br />
COANDA effect through several directional diffusion nozzles<br />
with a high induction rate.<br />
RANGE<br />
COADIS 2 is particuarly adapted to office configurations up to<br />
3 panels wide (3 x 1.35 m) and 6 m long max.<br />
The 3 sizes of the COADIS 2 cover a range of air flows from<br />
130 to 800 m3/h, meeting the most stringent sound level<br />
requirements.<br />
Type 235/11 fits into 600 × 600 mm panels<br />
Type 235/22 fits into 600 × 900 mm panels<br />
Type 235/33 fits into 600 × 1200 mm panels<br />
Two models, Classic and Raised, are available, and in most<br />
cases there is no need for a draining pump (and therefore<br />
maintenance is reduced).<br />
The white RAL 9010 panel integrates perfectly into suspended<br />
ceilings.<br />
Consult us for special panel sizes: 650 × 650, 650 × 1300,<br />
675 × 675, 675 × 1350, etc.<br />
CIAT takes part in the EUROVENT fan coil unit certification programme, see performances in Eurovent mode, on last page of the range.<br />
The list of products and certified characteristics is given in the EUROVENT directory and on the web site www.eurovent-certification.com .<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
1
Cassettes<br />
COADIS 2<br />
COADIS 2 integrated<br />
inside the suspended ceiling<br />
Hydraulical<br />
pipings<br />
Condensates<br />
evacuation<br />
COADIS 2 are non-independent terminal air conditioning units<br />
installed at the end of a room. Their dimensions are suitable for<br />
integration into standard 600 × 600 suspended ceiling panels.<br />
The units are easy to install on four threaded rods, preferably<br />
with resilient mounts. The unit is designed so as to avoid the<br />
installation of a draining pump in most cases. The hydraulic<br />
connections can be made from pipes in the suspended ceiling<br />
of the corridor adjacent to the room, and condensates can be<br />
drained by gravity directly into the main evacuation pipe.<br />
Figure A<br />
COADIS 2 solves indoor air quality problems by a comfort-type<br />
approach, optimising air diffusion and minimising power<br />
consumption. The entire air diffusion system is included in the<br />
intake/outlet panel, with no additional ducts or grilles.<br />
To optimise air diffusion, we use nozzles with a high induction<br />
coefficient, causing the ambient air to be drawn along by the<br />
discharge air. This enables the air stream to stick to the ceiling<br />
by Coanda effect, avoiding draughts in the occupied area of the<br />
room. The units are designed for offices up to 5 or 6 metres<br />
long.<br />
The directional nozzles enable the range of the air jet and the<br />
lateral component to be adjusted (see Figure A).<br />
Similarly, the air jet can be directed at a chosen angle, allowing<br />
the COADIS 2 to be installed in a corner and still maintain good<br />
air distribution.<br />
2<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
COADIS 2 “GLOBAL COMFORT IS A REALITY”<br />
● Isovelocity curves at medium speed<br />
Room height (m)<br />
2.2<br />
0.16<br />
1.6<br />
1.4<br />
0.2<br />
0.16<br />
0.6<br />
0.11<br />
1.4<br />
1.0<br />
0.2<br />
1.4<br />
1.0<br />
0.6<br />
1.0<br />
0.6 0.6<br />
0.2<br />
0,16<br />
0.11<br />
0.2<br />
2.5<br />
2.1<br />
1.7<br />
1.3<br />
0.9<br />
COADIS 2<br />
0.16<br />
0.11<br />
0.16<br />
0.21<br />
0.21<br />
0.5<br />
0.1<br />
● Isotemperatures curve at medium speed<br />
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0<br />
Room length (m)<br />
18<br />
18<br />
20 20<br />
20<br />
22<br />
22<br />
24 24<br />
24<br />
22<br />
24<br />
24<br />
2.5<br />
2.1<br />
Room height (m)<br />
25.5 25.5<br />
26.0 26.0<br />
25.0<br />
25.0<br />
24.5<br />
24.5<br />
24.5<br />
24.5<br />
25.0<br />
25.0<br />
25.0<br />
24.5<br />
25.0<br />
25.0<br />
24.5<br />
1.7<br />
1.3<br />
0.9<br />
0.5<br />
24.5<br />
25.0<br />
24<br />
0.1<br />
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0<br />
Room length (m)<br />
Note: Cooling test drawings: cold water 7/12°C<br />
- inlet air 27°C<br />
- room air 25°C<br />
The COADIS 2 is designed in accordance with the<br />
requirements of the ISO 7730 standard: “Determination of the<br />
PMV and PPD indexes and specification of the conditions for<br />
thermal comfort conditions”.<br />
In short, the COADIS 2 is designed for optimal reduction of<br />
local discomfort factors in the occupied volume, as shown on<br />
the graphs above:<br />
● Recommended vertical temperature gradient with max.<br />
difference of 3°C.<br />
● Asymmetric radiation minimised by effective air mixing (cold<br />
wall phenomenon).<br />
● Recommended floor temperature between 23 and 25°C for a<br />
seated person.<br />
● No draught felt by the user, with air speeds not exceeding<br />
0.25 m/s in normal operating conditions.<br />
Acoustic comfort has not been overlooked, as shown by the<br />
comfort levels on next pages.<br />
We have defined the occupied zone in accordance with the<br />
CEN TC 156 WG6 European working group “Design criteria for<br />
the indoor environment”, that is:<br />
■ Distance from external window: 1.0 m<br />
■ Distance from external wall: 0.5 m<br />
■ Distance from entrance door: 1.0 m<br />
■ Distance from internal wall: 0.5 m<br />
■ Distance from floor: 1.8 m<br />
Obstacles in the air stream (beams, light fittings, etc.) should<br />
be avoided as the air jet can behave in one of three ways:<br />
■ Breaks away from the ceiling and drops, disturbing comfort.<br />
■ Breaks away from the ceiling then rises again downstream<br />
from the obstacle.<br />
■ Ignores the obstacle.<br />
It is clear that various construction trades must work together<br />
to ensure thermal and acoustic comfort and high quality air<br />
diffusion for users. On site tests should be carried out in order<br />
to optimise air diffusion and other parameters to obtain the<br />
desired comfort level.<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
3
Cassettes<br />
THE ADVANTAGES OF COADIS 2<br />
THIRD GENERATION CASSETTE<br />
COADIS 2<br />
The reference<br />
on the market<br />
Top-of-the-range polymer diffuser allowing<br />
an operation with high temperature hot<br />
water conditions of traditional boiler<br />
(90/70°C).<br />
Internal insulation with film for<br />
easy cleaning, avoids eroding<br />
the insulation and prevents dust<br />
build-up, greater exchange<br />
surface for higher power.<br />
4 lines of circular nozzles<br />
allowing air induction of<br />
over 40%.<br />
Nozzles flush to the panel<br />
Electrical box adapted to<br />
accommodate most of the<br />
existing control devices.<br />
1 motor per unit to minimise<br />
breakdowns and maintenance<br />
costs<br />
The high-efficiency, wide<br />
diameter (160 mm) impellers<br />
developed by CIAT maintain<br />
performance at suitable levels<br />
even when the filters are<br />
clogged.<br />
Hydraulic coils optimized to<br />
limit the latent power:<br />
energy saving, more<br />
exchange surface for<br />
more capacity.<br />
Condensates drain pan in<br />
polymer without water<br />
retention:<br />
→ No internal corrosion<br />
→ No proliferation of bacteria.<br />
New panel lined with<br />
protective, non-hazardous<br />
and environmentally-friendly<br />
acoustic and thermal<br />
insulation.<br />
Electric battery sheathed without resistive<br />
wire:<br />
→ Smooth stainless pipe inserted in the<br />
finned coil, for safety and optimal comfort<br />
→ Electric battery placed after the hydraulic<br />
coil (energy saving in heating/cooling +<br />
electric operation)<br />
Protected use:<br />
→ access to the fan motor<br />
assembly thanks to a CIAT<br />
tool delivered with the unit<br />
→ An exterior front panel<br />
screwed and not clipped.<br />
11 years’ experience for optimum quality.<br />
4<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
TECHNICAL DESCRIPTION<br />
Air return/discharge lower panel<br />
Perfectly adaptable to the dimensions of 600 x 600 panels to<br />
be integrated inside or outside the suspended ceiling.<br />
Uniform colour of all components White Ral 9010.<br />
Punched aluminium air inlet grille, quick dismantling by clips.<br />
Air discharge by directional circular nozzles with a high<br />
induction rate allowing the air jet adhesion to the ceiling<br />
by “Coanda effect”, avoiding cold air falling into the comfort<br />
zone. Clipped nozzles in thermoplastic material, V0 RAL 9010<br />
fire rating.<br />
One-piece sheet of protective, non-hazardous and<br />
environmentally-friendly insulation. M1 fire rating.<br />
Water coil (2-pipe or 4-pipe system)<br />
Galvanised sheet metal, copper tubes, aluminium fins.<br />
One-element connector with 40 mm between axis for direct<br />
control valve mounting.<br />
Air vent and draining.<br />
Working pressure 16 Bar (20°C).<br />
Test pressure 24 Bar.<br />
Max water temperature: 110°C (PN10).<br />
Water coil connectors on the left or right side of the unit when<br />
facing the discharge (to be mentioned on the order).<br />
Electrical battery (2-pipe system +<br />
electric)<br />
230/1/50 shrouded mono-tube electric heating element(s)<br />
set inside the water coil finned block ensuring an excellent<br />
distribution of the heating energy.<br />
2 capillary tube temperature limiters, with manual and<br />
automatic reset, inserted in the aluminium housing.<br />
Condensates recovery tray<br />
Self-extinguishing polymer material, fire resistance M1<br />
Without water retention, condensates drain at the same level<br />
as inside the sloping drain pan.<br />
Manually reversible connectors at the front or the rear of the<br />
drain pan.<br />
4 evacuation diameters: Ø 15, 16, 22 or 28 mm<br />
Mounted on slide together with the coil for easy dismantling.<br />
Ancillary pan<br />
Pan delivered separately. Clips onto pan made of<br />
self-extinguishing polymer,<br />
M1 fire rating.<br />
Fan motor assembly<br />
■ Motor<br />
7 speeds, 3 of them pre-wired in factory (possibility of<br />
modifying this wiring on site).<br />
Closed type, tropicalised, with protected shaft and ballbearings.<br />
Automatic thermal protector with standard opening on the winding<br />
Resilient mounts.<br />
Supply 230/1/50.<br />
Reduced consumption.<br />
■ Fan(s)<br />
Galvanised sheet metal casing(s).<br />
CIAT dia. 160 mm dynamically balanced ABS impeller(s) with<br />
forwared-curved blades and dual inlets.<br />
V0 Fire rating.<br />
Air filter<br />
Installed before the fan assembly.<br />
Flexible filtering media in renewable polyester fibers.<br />
Efficiency class EN 779: G3<br />
Fire resistance: M1<br />
Metallic rigid frame.<br />
Accessible by the air inlet grille assembled on clips.<br />
Standard structure<br />
Galvanised sheet metal.<br />
Thermal and acoustic insulation on air return/discharge in<br />
melamine resin, soft foam with open cells and aluminium film,<br />
fire resistance M1, 15mm thickness.<br />
Pre-cut holes for treated fresh air inlet Ø 100mm or 125mm.<br />
Oblong fixation holes.<br />
Electrical connection box<br />
Hydraulic connection side.<br />
Enclosed box.<br />
Electrical connection terminal On DIN rail as per EN 50022<br />
depth 7.5 mm.<br />
Customer wiring catch.<br />
Note: see installation manual for more details.<br />
COADIS 2<br />
ACCESSORIES<br />
Resilient attachment mounts.<br />
Smooth sleeve, Ø100 mm, for treated fresh air inlet.<br />
Smooth sleeve, Ø100 mm with self-adjusting module for<br />
treated fresh air inlet.<br />
CONTROL DEVICES<br />
Electromechanical wall-mounted thermostat range.<br />
V30 electronic controller range.<br />
V200 electronic controller range.<br />
V2000 ® communicating electronic controller range.<br />
V3000 communicating electronic controller range.<br />
LON control, consult us.<br />
Smooth sleeve, Ø125 mm with or without self-adjusting module<br />
(consult us).<br />
Condensate drain pump fitted to unit or in “ready-to-fit” kit.<br />
230 V thermo valve kit.<br />
OPTIONAL (CONSULT US)<br />
- For specific water and air mode.<br />
- 60 Hz Operation (230V).<br />
- For optimization of suspended ceiling support profile other<br />
than T-piece.<br />
- For dimensions other than standard 600 x 600.<br />
- High Energy Efficiency (HEE) motor.<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
5
GLOBAL VIEW<br />
Cassettes<br />
COADIS 2<br />
Punched steel sheet air inlet<br />
grille clipped without screw with<br />
air filter (possibility to remove<br />
the fan assembly via the grille)<br />
Directional nozzles to adjust air jet<br />
COADIS 2<br />
FIXATION<br />
Fixing holes<br />
Ø12 x 30<br />
Threaded M8 rod<br />
(not supplied)<br />
Pre-cut hole to fit a sleeve of<br />
Ø100mm or Ø125mm with or<br />
without self-adjusting<br />
module (accessory).<br />
If air return sensor used, plan<br />
the fresh air intake at opposite side.<br />
Metallic closed electrical box<br />
with oblong holes to avoid<br />
taking out screws.<br />
. Dry drain pan, without water retention,<br />
avoiding bacteria proliferation.<br />
. Self-extinguishing polymer material<br />
smooth drain pan.<br />
. Reversible connections with<br />
4 diameters : 15, 16, 22 or 28mm.<br />
6<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
DIMENSIONS<br />
Classic model<br />
79<br />
80<br />
17 17<br />
137 A<br />
B<br />
289,5<br />
305<br />
Cooling coil<br />
16 563<br />
595<br />
Heating coil<br />
16<br />
COADIS 2<br />
Holes<br />
12 x 30<br />
2 Pre-cut holes for treated<br />
fresh air (see accessories)<br />
129<br />
16<br />
*<br />
214<br />
176<br />
595<br />
16<br />
500<br />
300<br />
104,5<br />
17<br />
= C<br />
=<br />
E<br />
* Possibility to permutate condensates draining<br />
H: Fixing distance between axis 235/11<br />
F: Fixing distance between axis 235/22 and 235/33<br />
MOUNTING<br />
Hydraulic connections<br />
4<br />
3<br />
1<br />
80 80<br />
102<br />
Classic<br />
COADIS 2<br />
D<br />
17<br />
222<br />
A B C D E<br />
Mass<br />
(kg)<br />
235 / 11 420 595 X 250 309 22<br />
235 / 22 720 895 468 550 X 30<br />
235 / 33 1020 1195 768 850 X 42<br />
IMPORTANT: Drain pan gravity height to<br />
drain condensates = 93 mm<br />
~ 4 to 6 m piping length (lcm/m Slope)<br />
AB<br />
B<br />
A<br />
G1/2"<br />
G3/8"<br />
o<br />
i<br />
5 2<br />
6<br />
G1/2"<br />
G3/8"<br />
<br />
<br />
<br />
<br />
Air vent<br />
Coil drain<br />
One-element connector with 40mm distance between axis<br />
Male/female connector with flat bearing surface<br />
3/8” 1/2”(accessory)<br />
Example of a 2 or 4-way valve with flat bearing surface<br />
(included with the control device loop)<br />
O-ring gasket<br />
i : Water coil inlet<br />
o : Water coil outlet<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
7
DIMENSIONS<br />
Cassettes<br />
COADIS 2<br />
Raised model<br />
Cooling coil<br />
Heating coil<br />
Holes<br />
12 x 30<br />
2 Pre-cut holes for treated<br />
fresh air (see accessories)<br />
*<br />
D<br />
: Possibility to permutate condensates draining<br />
*<br />
H: Fixing distance between axis 235/11<br />
F: Fixing distance between axis 235/22 and 235/33<br />
MOUNTING<br />
Raised<br />
COADIS 2<br />
A B C D E<br />
Mass<br />
(kg)<br />
235 / 11 A 595 X 250 309 24<br />
235 / 22 441 895 468 550 X 33<br />
235 / 33 741 1195 768 850 X 45<br />
Hydraulic connections<br />
1<br />
80 80<br />
IMPORTANT: Drain pan gravity height to<br />
drain condensates = 159 mm<br />
~ 10 to 12 m piping length (lcm/m Slope)<br />
4<br />
3<br />
AB<br />
B<br />
A<br />
G1/2"<br />
G3/8"<br />
o<br />
i<br />
5 2<br />
6<br />
G1/2"<br />
G3/8"<br />
<br />
<br />
<br />
<br />
Air vent<br />
Coil drain<br />
One-element connector with 40mm distance between axis<br />
Male/female connector with flat bearing surface<br />
3/8” 1/2”(accessory)<br />
Example of a 2 or 4-way valve with flat bearing surface<br />
(included with the control device loop)<br />
O-ring gasket<br />
I : Water coil inlet<br />
o : Water coil outlet<br />
8<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
PERFORMANCES FOR CLASSIC AND RAISED MODELS<br />
COADIS 2<br />
235 / 11<br />
235 / 22<br />
235 / 33<br />
Motor<br />
reference<br />
Air flow<br />
m 3 /h<br />
Heating<br />
capacity,<br />
2-pipe<br />
system<br />
coil W<br />
Heating<br />
Mean temperature rise on the air<br />
Cooling capacity W capacity,<br />
in K<br />
Comfort level<br />
4-pipe<br />
Additional electric heater<br />
ISO or NR<br />
system<br />
230/1/50<br />
Total Sensible coil W<br />
1R 1R 2R<br />
600 W 1200 W<br />
R1 420 7090 2 350 1 830 2 530 41 4,2 8,5<br />
R2 390 6710 2 250 1 730 2 450 39 4,6 9,1<br />
R3 345 6130 2 060 1 560 2 320 36 5,2 10,1<br />
R4 295 5420 1 830 1 370 2 150 34 6,0 12,1<br />
R5 225 4340 1 500 1100 1 860 26 7,9 15,8<br />
R6 160 3190 1130 812 1 510 19 11,1 22,3<br />
R7 105 2120 783 565 1 150 < 15 17,0 33,9<br />
900 W 1800 W<br />
R1 685 9 480 3 560 2 790 4 870 44 3,9 7,8<br />
R2 620 8 880 3 330 2 580 4 640 41 4,3 8,5<br />
R3 530 7 990 3 000 2 290 4 280 37 5,0 10,1<br />
R4 450 7 110 2 690 2 020 3 920 34 5,9 11,9<br />
R5 375 6 210 2 360 1 750 3 530 29 7,1 14,3<br />
R6 275 5 170 1 970 1 440 3 060 21 12,4 24,9<br />
R7 215 4 020 1 530 1100 2 500 < 15 3,1 6,3<br />
1200 W 1800 W 2400 W<br />
R1 855 13 400 5 150 3 890 7 230 43 4,2 6,3 8,3<br />
R2 725 11 900 4 630 3 430 6 630 40 4,9 7,4 9,8<br />
R3 600 10 400 4070 2 960 5 970 35 5,9 8,9 11,9<br />
R4 480 8 790 30480 2 470 5 240 29 7,4 11,1 14,9<br />
R5 390 7 440 2 970 2 080 4 590 23 9,1 13,7 18,3<br />
R6 305 6 050 2 440 1 680 3 880 16 11,2 17,5 23,4<br />
R7 205 4 220 1 720 1 170 2 870 < 15 17,4 26,1 34,8<br />
COADIS 2<br />
Standard factory wiring.<br />
Hot water temp.: 90/70 °C, winter air temp.: 19 °C - Cold water temp.: 7/12 °C, summer air temp.: 27 °C 50% RH.<br />
Comfort level: attenuation level of room and installation: 12 dB.<br />
COIL CONTENT (LITRES)<br />
2-pipe system<br />
4-pipe system<br />
COADIS 2 235 / 11 235 / 22 235 / 33<br />
Cold water coil or<br />
Hot water coil<br />
0,48 0,74 1,00<br />
Cold water coil 0,48 0,74 1,00<br />
Hot water coil 0,16 0,23 0,31<br />
ELECTRICAL CHARACTERISTICS 230 V - 1 PH - 50 HZ<br />
COADIS 2 235 / 11 235 / 22 235 / 33<br />
Motor wiring R1 R2 R3 R4 R5 R6 R7 R1 R2 R3 R4 R5 R6 R7 R1 R2 R3 R4 R5 R6 R7<br />
Power input W 73 62 51 43 39 34 30 95 82 69 59 54 48 44 108 90 75 62 56 50 45<br />
Absorbed current A 0,32 0,27 0,22 0,19 0,17 0,15 0,13 0,41 0,37 0,3 0,26 0,23 0,21 0,19 0,47 0,39 0,32 0,27 0,24 0,22 0,2<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
9
Cassettes<br />
COADIS 2<br />
Standard unit (without valve/accessory)<br />
COADIS 2<br />
Connectors on left<br />
2-pipe<br />
system<br />
Water coil only<br />
4-pipe<br />
system<br />
Connectors on right<br />
2-pipe<br />
system<br />
4-pipe<br />
system<br />
Connectors on left<br />
2-pipe system<br />
+ 2 wire system<br />
Water coil + electric element<br />
Connectors on right<br />
2-pipe system<br />
+ 2 wire system<br />
1R 2R 1R 2R<br />
CLASSIC<br />
RAISED<br />
235/11 CLA<br />
600x600<br />
235/22 CLA<br />
600x900<br />
235/33 CLA<br />
600x1200<br />
235/11 REH<br />
600x600<br />
235/22 REH<br />
600x900<br />
235/33 REH<br />
600x1200<br />
600 W 1200 W 600 W 1200 W<br />
Code 7017667 7017669 7017668 7017670 7017671 7017672 7017673 7017674<br />
● ● ● ● ● ● ● ● ●<br />
900 W 1800 W 900 W 1800 W<br />
Code 7017675 7017677 7017676 7017678 7017679 7017687 7017688 7017689<br />
● ● ● ● ● ● ● ● ●<br />
1200 W 1800 W 2400 W 1200 W 1800 W 2400 W<br />
Code 7017691 7017694 7017692 7017695 7017696 7017697 7017698 7017699 7017700 7017701<br />
● ● ● ● ● ● ● ● ● ● ●<br />
600 W 1200 W 600 W 1200 W<br />
Code 7017702 7017704 7017703 7017705 7017706 7017707 7017708 7017709<br />
● ● ● ● ● ● ● ● ●<br />
900 W 1800 W 900 W 1800 W<br />
Code 7017710 7017712 7017711 7017713 7017714 7017715 7017716 7017717<br />
● ● ● ● ● ● ● ● ●<br />
1200 W 1800 W 2400 W 1200 W 1800 W 2400 W<br />
Code 7017719 7017722 7017720 7017723 7017724 7017725 7017726 7017727 7017728 7017730<br />
● ● ● ● ● ● ● v ● ● ●<br />
Units are in stock to meet your requirements at short notice (controls in stock, see chapter on controls)<br />
Option (mounted on the unit, classic model only)<br />
Designation<br />
Code<br />
●<br />
Condensate drain pump mounted on the<br />
unit with overflow safety device.<br />
- 7l/h maximum flow for 1m draining<br />
height and 5m maximal length of piping.<br />
- 6l/h maximum flow for 1m draining<br />
height and 10m maximal length of piping.<br />
Draining: 6mm internal diameter flexible<br />
tube, 8mm diameter nozzle.<br />
For higher drain heights, consult us.<br />
One regulation for each valve must be<br />
added to allow slaving the overflow<br />
safety device to the valve closing<br />
(condensates stopped)***.<br />
Approximate calculation of the<br />
condensed water flow :<br />
P total - P sensible (W)<br />
Qv (l/h) =<br />
680<br />
(View without valve as an indication).<br />
E045004<br />
●<br />
*** For pre-assembly, see accessories<br />
10<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
Units with air control in stock<br />
CONTROL ON AIR Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />
COADIS 2 CLASSIC 2TG Unit code (a) 7173524 7173526 7173528<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
On/Off + 3 speeds + manual dial - heating or<br />
cooling ONLY<br />
RTR-E 7015 5950338<br />
RTR-E 7009 7191518<br />
RTR-E code (1) 5201023<br />
Total price (a+1) ● ● ●<br />
RTR-E code (2) 7124612<br />
Total price (a+2) ● ● ●<br />
COADIS 2<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating/cooling with automatic changeover,<br />
supplied as a kit<br />
A34H 7175611<br />
V30(3) code<br />
+ Co (4) sensor<br />
7166781 + 7163008<br />
Total price (a+3+4) ● ● ●<br />
COADIS 2 CLA or REH 2TG<br />
WALL THERMOSTAT<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating or cooling only<br />
Cooling A32H<br />
Heating A30H<br />
7175609<br />
7175607<br />
V30 (3) code 7166781<br />
Total price (a+3) ● ● ●<br />
Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />
COADIS 2 RAISED 2TG Unit code (a) 7174521 7174523 7174525<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
On/Off + 3 speeds + manual dial - heating or<br />
cooling only<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating/cooling with automatic changeover,<br />
supplied as a kit<br />
RTR-E 7015 5950338<br />
RTR-E 7009 7191518<br />
A34H 7175611<br />
RTR-E code (1) 5201023<br />
Total price (a+1) ● ● ●<br />
RTR-E code (2) 7124612<br />
Total price (a+2) ● ● ●<br />
V30(3) code<br />
+ Co (4) sensor<br />
7166781 + 7163008<br />
Total price (a+3+4) ● ● ●<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating or cooling only<br />
Cooling A32H<br />
Heating A30H<br />
7175609<br />
7175607<br />
V30 (3) code 7166781<br />
Total price (a+3) ● ● ●<br />
Applications<br />
Diagrams<br />
CLA 235/11<br />
2TG+600W<br />
CLA 235/22<br />
2TG+900W<br />
CLA 235/33<br />
2TG+1200W<br />
COADIS 2 CLASSIC 2TG+1R Unit code (a) 7180280 7180284 7180288<br />
COADIS 2 CLA or REH 2TG + elec.<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating/cooling with automatic changeover,<br />
supplied as a kit<br />
A38H 7175630<br />
Applications<br />
Diagrams<br />
V30(3) code<br />
+ Co (4) sensor<br />
7166781 + 7163008<br />
Total price (a+3+4) ● ● ●<br />
REH 235/11<br />
2TG+600W<br />
REH 235/22<br />
2TG+900W<br />
REH 235/33<br />
2TG+1200W<br />
COADIS 2 RAISED 2TG+1R Unit code (a) 7180294 7180298 7180302<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating/cooling with automatic changeover,<br />
supplied as a kit<br />
A38H 7175630<br />
V30(3) code<br />
+ Co (4) sensor<br />
Total price (a+3+4)<br />
7166781 + 7163008<br />
● ● ●<br />
Units in stock to ensure speedy delivery<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
11
Cassettes<br />
COADIS 2<br />
2-pipe water control units in stock<br />
WATER CONTROL Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />
COADIS 2 CLASSIC 2TG<br />
+ 230V 2-way valve kit<br />
Unit code (a)<br />
+ kit (7) code<br />
7173524<br />
+ 7185600<br />
7173526<br />
+ 7185600<br />
7173528<br />
+ 7185600<br />
WALL THERMOSTAT + 230V 2-way valve kit<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
On/Off + 3 speeds + manual dial - heating or<br />
cooling only<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating or cooling only<br />
COADIS 2 RAISED 2TG<br />
+ 230V 2-way valve kit<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
RTR-E 7012 5950384<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
Cooling E32H<br />
Heating E30H<br />
5950268<br />
5950459<br />
7175615<br />
7175613<br />
RTR-E (5) code 5201024<br />
Total price (a+7+5) ● ● ●<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code 7166781<br />
Total price (a+7+3) ● ● ●<br />
Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />
RTR-E 7012 5950384<br />
Unit code (a)<br />
+ kit (7) code<br />
7174521<br />
+ 7185600<br />
7174523<br />
+ 7185600<br />
RTR-E (5) code 5201024<br />
7174525<br />
+ 7185600<br />
Total price (a+7+5) ● ● ●<br />
On/Off + 3 speeds + manual dial - heating or<br />
cooling only<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
5950268<br />
5950459<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
COADIS2 CLA or REH 2TG<br />
WALL THERMOSTAT + 230V 2-way valve kit<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating or cooling only<br />
COADIS 2 CLASSIC 2TG<br />
+ 230V 4-way valve kit<br />
Cooling E32H<br />
Heating E30H<br />
7175615<br />
7175613<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch RTR-E 7012 5950384<br />
On/Off + 3 speeds + manual dial - heating or<br />
cooling only<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating/cooling with automatic changeover,<br />
supplied as a kit<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating or cooling only<br />
COADIS 2 RAISED 2TG<br />
+ 230V 4-way valve kit<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
On/Off + 3 speeds + manual dial - heating or<br />
cooling only<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating/cooling with automatic changeover,<br />
supplied as a kit<br />
V30(3) code 7166781<br />
Total price (a+7+3) ● ● ●<br />
Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
5950268<br />
5950459<br />
E35H 7175618<br />
Cooling E33H<br />
Heating E31H<br />
7175615<br />
7175613<br />
Unit code (a)<br />
+ kit (7) code<br />
7173524<br />
+ 7185601<br />
7173526<br />
+ 7185601<br />
RTR-E (5) code 5201024<br />
7173528<br />
+ 7185601<br />
Total price (a+7+5) ● ● ●<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code<br />
+ Co (4) sensor<br />
7166781 + 7163008<br />
Total price<br />
(a+7+3+4)<br />
● ● ●<br />
V30 (3) code 7166781<br />
Total price (a+7+3) ● ● ●<br />
Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />
RTR-E 7012 5950384<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
5950268<br />
5950459<br />
E35H 7175618<br />
Unit code (a)<br />
+ kit (7) code<br />
7174521<br />
+ 7185601<br />
7174523<br />
+ 7185601<br />
RTR-E (5) code 5201024<br />
7174525<br />
+ 7185601<br />
Total price (a+7+5) ● ● ●<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code<br />
+ Co (4) sensor<br />
Total price<br />
(a+7+3+4)<br />
7166781 + 7163008<br />
● ● ●<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Heating or cooling only<br />
Cooling E33H<br />
Heating E31H<br />
7175615<br />
7175613<br />
V30 (3) code 7166781<br />
Total price<br />
(a+7+3)<br />
● ● ●<br />
Units in stock to ensure speedy delivery<br />
12<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
2-pipe/2-wire water control units in stock<br />
WATER CONTROL Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />
WALL THERMOSTAT + 230V 2-way valve kit<br />
COADIS 2 CLASSIC 2TG<br />
+ 230V 2-way valve kit<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
On/Off + 3 speeds + manual dial - Cooling +<br />
electric heater with deadband<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Cooling + electric heater<br />
with deadband<br />
COADIS 2 RAISED 2TG<br />
+ 230V 2-way valve kit<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
RTR-E 7012 5950384<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
Cooling E32H<br />
Heating E30H<br />
5950268<br />
5950459<br />
7175615<br />
7175613<br />
Unit code (a)<br />
+ kit (7) code<br />
7173524<br />
+ 7185600<br />
7173526<br />
+ 7185600<br />
RTR-E (5) code 5201024<br />
7173528<br />
+ 7185600<br />
Total price (a+7+5) ● ● ●<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code 7166781<br />
Total price (a+7+3) ● ● ●<br />
Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />
RTR-E 7012 5950384<br />
Unit code (a)<br />
+ kit (7) code<br />
7174521<br />
+ 7185600<br />
7174523<br />
+ 7185600<br />
RTR-E (5) code 5201024<br />
7174525<br />
+ 7185600<br />
Total price (a+7+5) ● ● ●<br />
COADIS 2<br />
COADIS 2 CLA or REH 2TG<br />
WALL THERMOSTAT + 230V 2-way valve kit<br />
On/Off + 3 speeds + manual deal - Cooling +<br />
electric heater with deadband<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Cooling + electric heater<br />
with deadband<br />
COADIS 2 CLASSIC 2TG<br />
+ 1R + 230V 4-way valve kit<br />
RTR-E 7011 Froid<br />
RTR-E 7011 Chaud<br />
Cooling E32H<br />
Heating E30H<br />
5950268<br />
5950459<br />
7175615<br />
7175613<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch RTR-E 7012 5950384<br />
On/Off + 3 speeds + manual deal - Cooling +<br />
electric heater with deadband<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Cooling + electric heater<br />
with deadband<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Automatic heating/cooling with electric heater<br />
and automatic changeover, supplied as a kit<br />
COADIS 2 RAISED 2TG<br />
+ 230V 2-way valve kit<br />
On/Off + 3 speeds + manual dial -<br />
heating/cooling with manual toggle switch<br />
On/Off + 3 speeds + manual deal - Cooling +<br />
electric heater with deadband<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Cooling + electric heater with deadband<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code 7166781<br />
Total price (a+7+3) ● ● ●<br />
Applications Diagrams CLA 235/11 CLA 235/22 CLA 235/33<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
5950268<br />
5950459<br />
E35H 7175618<br />
Cooling E33H<br />
Heating E31H<br />
7175615<br />
7175613<br />
Unit code (a)<br />
+ kit (7) code<br />
7173524<br />
+ 7185601<br />
7173526<br />
+ 7185601<br />
RTR-E (5) code 5201024<br />
7173528<br />
+ 7185601<br />
Total price (a+7+5) ● ● ●<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code<br />
+ Co (4) sensor<br />
7166781 + 7163008<br />
Total price<br />
(a+7+3+4)<br />
● ● ●<br />
V30 (3) code 7166781<br />
Total price (a+7+3) ● ● ●<br />
Applications Diagrams REH 235/11 REH 235/22 REH 235/33<br />
RTR-E 7012 5950384<br />
Cooling RTR-E 7011<br />
Heating RTR-E 7011<br />
5950268<br />
5950459<br />
E35H 7175618<br />
Unit code (a)<br />
+ kit (7) code<br />
7174521<br />
+ 7185601<br />
7174523<br />
+ 7185601<br />
RTR-E (5) code 5201024<br />
7174525<br />
+ 7185601<br />
Total price (a+7+5) ● ● ●<br />
RTR-E (6) code 5201018<br />
Total price (a+7+6) ● ● ●<br />
V30(3) code<br />
+ Co (4) sensor<br />
Total price<br />
(a+7+3+4)<br />
7166781 + 7163008<br />
● ● ●<br />
Wall-mounted V30 with +/- dial, 3 speeds -<br />
Automatic heating/cooling with electric heater<br />
and automatic changeover, supplied as a kit<br />
Cooling E33H<br />
Heating E31H<br />
7175615<br />
7175613<br />
V30 (3) code 7166781<br />
Total price<br />
(a+7+3)<br />
● ● ●<br />
Units in stock to ensure speedy delivery.<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
13
Cassettes<br />
COADIS 2<br />
4-pipe water control units in stock<br />
WATER CONTROL Applications Diagrams CLA 235/11 4TG CLA 235/22 4TG CLA 235/33 4TG<br />
COADIS 2 CLASSIC 4TG<br />
+ two 230V 2-way valve kits<br />
Unit code (a) +<br />
kit (7) code<br />
7173530<br />
+ 2 x 7185600<br />
7173532<br />
+ 2 x 7185600<br />
7173534<br />
+ 2 x 7185600<br />
On/Off + 3 speeds + manual dial -<br />
Heating/cooling with deadband<br />
RTR-E 7203 5950884<br />
RTR-E (6) code 5201021<br />
Total price (a+7+6) ● ● ●<br />
WALL THERMOSTAT + 230V 2-way valve kit<br />
Wall-mounted V30 with +/- dial, 3 speeds<br />
- Heating / cooling<br />
COADIS 2 RAISED 4TG<br />
+ two 230V 2-way valve kits<br />
On/Off + 3 speeds + manual dial -<br />
Heating/cooling with deadband<br />
E40H 7175641<br />
V30 (3) code 7166781<br />
Total price (a+7+3+4) ● ● ●<br />
Applications Diagrams REH 235/11 4TG REH 235/22 4TG REH 235/33 4TG<br />
RTR-E 7203 5950884<br />
Unit code (a) +<br />
kit (7) code<br />
7174527<br />
+ 2 x 7185600<br />
7174529<br />
+ 2 x 7185600<br />
RTR-E (6) code 5201021<br />
7174531<br />
+ 2 x 7185600<br />
Total price (a+7+6) ● ● ●<br />
COADIS 2 CLA or REH 4TG<br />
Wall-mounted V30 with +/- dial,<br />
3 speeds - Heating / cooling<br />
COADIS 2 CLASSIC 4TG<br />
+ two 230V 2-way valve kits<br />
E40H 7175641<br />
V30 (3) code 7166781<br />
Total price (a+7+3+4) ● ● ●<br />
Applications Diagrams CLA 235/11 4TG CLA 235/22 4TG CLA 235/33 4TG<br />
Unit code (a) +<br />
kit (7) code<br />
7173530<br />
+ 2 x 7185601<br />
7173532<br />
+ 2 x 7185601<br />
7173534<br />
+ 2 x 7185601<br />
On/Off + 3 speeds + manual dial -<br />
Heating/cooling with deadband<br />
RTR-E 7203 5950884<br />
RTR-E (6) code 5201021<br />
Total price (a+7+6) ● ● ●<br />
WALL THERMOSTAT + 230V 2-way valve kit<br />
Wall-mounted V30 with +/- dial,<br />
3 speeds - Heating / cooling<br />
COADIS 2 RAISED 4TG<br />
+ two 230V 2-way valve kits<br />
On/Off + 3 speeds + manual dial -<br />
Heating/cooling with deadband<br />
E41H 7175641<br />
V30 (3) code 7166781<br />
Total price (a+7+3+4) ● ● ●<br />
Applications Diagrams REH 235/11 4TG REH 235/22 4TG REH 235/33 4TG<br />
RTR-E 7203 5950884<br />
Unit code (a) +<br />
kit (7) code<br />
7174527<br />
+ 2 x 7185601<br />
7174529<br />
+ 2 x 7185601<br />
RTR-E (6) code 5201021<br />
7174531<br />
+ 2 x 7185601<br />
Total price (a+7+6) ● ● ●<br />
Wall-mounted V30 with +/- dial,<br />
3 speeds - Heating / cooling<br />
E41H 7175641<br />
V30 (3) code 7166781<br />
Total price (a+7+3+4) ● ● ●<br />
Units in stock to ensure speedy delivery.<br />
14<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A
Cassettes<br />
Accessories (supplied separately)<br />
SU1<br />
Designation<br />
Resilient mounts supplied separately<br />
(4 required per unit).<br />
Code<br />
●<br />
0219453 ●<br />
COADIS 2<br />
MO1 Smooth sleeve Ø100 mm with nuts and screws 7013442 ●<br />
MO7<br />
MO4<br />
Smooth spigot ext. Ø 100 mm(1) with self-adjusting<br />
module, fitted with a gasket. Packed with nuts and screws<br />
and drawing.<br />
The air flow rate controller is working to supply a<br />
determined flow(1) with air difference pressure between<br />
50 and 100 Pa.<br />
(1) 3 flow rates are available by use of 3 sets of wedges.<br />
The lower air flow is by default.<br />
(2) Diameter 12 mm, consult us.<br />
15 / 30 / 45 m 3 /h<br />
(1)<br />
60 / 75 / 90 m 3 /h<br />
(1)<br />
7013440 ●<br />
7013544 ●<br />
Kit condensate drain pump for classic model to mount on the unit with overflow safety device.<br />
- 7l/h maximum flow for 1m draining height and 5m maximal length of piping.<br />
- 6l/h maximum flow for 1m draining height and 10m maximal length of piping.<br />
Draining: 6mm internal diameter flexible tube, 8mm diameter nozzle.<br />
For higher drain heights, consult us.<br />
One regulation for each valve must be added to allow slaving the overflow safety device to the valve closing<br />
(condensates stopped).<br />
Fixation assembly supplied with the diagram.<br />
Approximate calculation of the condensed water flow : Qv (l/h) =<br />
P total - P sensible (W)<br />
680<br />
7023316 ●<br />
RA1<br />
2 piece male/female connector 3/8” 1/2”<br />
including gaskets<br />
5202314<br />
+<br />
5200708<br />
●<br />
Accessories are in stock to meet your requirements at short notice<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A<br />
15
Cassettes<br />
COADIS 2<br />
EUROVENT PERFORMANCES - 2-PIPE SYSTEM<br />
CIAT participates in Eurovent's certification programme for fan heaters.<br />
Up-to-date information is available on the Eurovent web site.<br />
www.eurovent-certification.com<br />
Eurovent conditions, 2 tube system:<br />
- Summer: cold water 7/12°C, air 27°C WB 19°C<br />
- Winter: Hot water inlet: 50°C for water flow rate determined in summer conditions, air 20°C<br />
COADIS 2<br />
Motor ref<br />
Sensible cooling<br />
capacity<br />
Total cooling<br />
capacity<br />
Total heating<br />
capacity<br />
Dp cooling<br />
Dp heating<br />
Lw<br />
kW kW kW kPa kPa dB A<br />
R2 1,66 1.91 2,71 28.9 24,5 56<br />
235/11<br />
R4 1.33 1.58 2,2 20.6 17.4 50<br />
R6 0.799 1,00 1,3 9.10 7.84 37<br />
R2 2,46 2,82 3,66 21.0 18,0 57<br />
235/22<br />
R4 1,92 2,26 2,93 14.1 12,2 50<br />
R6 1,36 1,65 2,12 7.84 6,90 39<br />
R2 3,16 3,85 4,93 39.1 33,7 55<br />
235/33<br />
R3 2,73 3,38 4,3 31.0 26,7 51<br />
R6 1,55 2,02 2,49 12.2 10,6 34<br />
Dp: water pressure drop (kPa)<br />
Lw: overall sound power level (dBA)<br />
EUROVENT PERFORMANCES - 4-PIPE SYSTEM<br />
CIAT participates in Eurovent's certification programme for fan heaters.<br />
Up-to-date information is available on the Eurovent web site.<br />
www.eurovent-certification.com<br />
Eurovent conditions, 4 tube system:<br />
- Summer: cold water 7/12°C, air 27°C WB 19°C<br />
- Winter: hot water inlet 70°C/60°C, air 20°C<br />
COADIS 2<br />
Motor ref<br />
Sensible cooling<br />
capacity<br />
Total cooling<br />
capacity<br />
Total heating<br />
capacity<br />
Dp cooling<br />
Dp heating<br />
Lw<br />
235/11<br />
235/22<br />
235/33<br />
Dp: water pressure drop (kPa)<br />
Lw: overall sound power level (dBA)<br />
kW kW kW kPa kPa dB A<br />
R2 1,66 1,91 1,83 28.9 3.26 56<br />
R4 1,33 1,58 1,60 20.6 2.57 50<br />
R6 0,802 1,00 1,12 9.10 1.37 37<br />
R2 2,46 2,82 3,37 21.0 13.3 57<br />
R4 1,92 2,26 2,85 14.1 9.84 50<br />
R6 1,36 1,65 2,21 7.84 6.34 39<br />
R2 3,29 3,95 4,77 41.8 29.1 55<br />
R3 2,83 3,47 4,29 33.1 24.2 51<br />
R6 1,59 2,06 2,77 12.9 11.2 34<br />
This document is non-contractual.As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification.<br />
Head office<br />
Avenue Jean Falconnier - B.P. 14<br />
01350 - Culoz - France<br />
Tel.: +33 (0)4 79 42 42 42 - Fax: +33 (0)4 79 42 42 10<br />
info@ciat.fr - www.ciat.com<br />
CIAT Service<br />
Tel.: +33 (0)4 79 42 42 90 - Fax: +33 (0)4 79 42 42 13<br />
Compagnie Industrielle d’Applications Thermiques - S.A. with a registered capital of 26 000 000 € - R.C.S. Belley B 545 620 114<br />
16<br />
AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.640 A