us duct.<br />

2) One (1) lot <strong>of</strong> associated equipment.<br />

2.8.3 Unit Auxiliary Trans<strong>for</strong>mer, Station Trans<strong>for</strong>mers and Associated<br />

Equipment<br />

1) Two (2) sets <strong>of</strong> unit auxiliary trans<strong>for</strong>mer (2 x 110% <strong>of</strong> total aux. power<br />

requirement but each capacity not less than 25 MVA) and associated<br />

equipment with the following features:<br />

• Type : Oil immerse, three phase and<br />

two windings, outdoor power<br />

trans<strong>for</strong>mer.<br />

• Rating : 25 MVA<br />

• Rated high voltage :15.75 kV (or as per Generation Voltage)<br />

• Rated low voltage : 6.6 kV<br />

• Connection : DYn 11<br />

• Rated insulation<br />

level : HV Winding LV Winding<br />

• Lighting impulse<br />

Withstand voltage<br />

(1.2/50 micro sec) : 95 kV (Peak) 60 kV(Peak)<br />

• Power frequency<br />

Withstand voltage<br />

(For 1 mm). : 36 kV 22 kV<br />

• Impedance voltage : shall be within the range <strong>of</strong> 5% and 7.5%<br />

• Tap changer : Off-current on high tension winding ±10%<br />

• Neutral grounded : Solidify grounded<br />

2) Four (4) sets <strong>of</strong> station trans<strong>for</strong>mer (4 x 55% <strong>of</strong> total 0.4 kV aux. power<br />

requirement but each capacity not less than 2 MVA) and associated<br />

equipment with the following features:<br />

• Type : Oil immersed, three phase and<br />

two windings, outdoor power<br />

trans<strong>for</strong>mer<br />

• Rating : 2 MVA<br />

• Rated high voltage : 6.6 kV<br />

• Rated low voltage : 415 V<br />

• Connection : Dyn11<br />

• Rated insulation : HV Winding LV Winding<br />

• Lighting impulse : 60 kV(peak)<br />

Withstand voltage<br />

(1.2/50 micro sec.)<br />

<strong>Ghorasal</strong> <strong>300</strong>-<strong>450</strong> <strong>MW</strong> CCPP Project (Vol-2A <strong>of</strong> 2) 16