4.3.f Water Flow (Pressure) Switch Adjustment<br />

WARNING<br />

- Failure to heed the following may result in injury or death.<br />

Water Pressure Switch adjustment procedure to be performed by experienced<br />

service personnel only; procedure must not be attempted by individuals lacking<br />

adequate electrical and mechanical experience.<br />

CAUTION<br />

- Failure to heed the following may result in equipment damage.<br />

If, after water pressure switch adjustment, the heat pump continues to operate with<br />

water pump off, readjust water pressure switch to ensure heat pump will not run<br />

without water flow.<br />

A water pressure switch adjustment may be required if heat pump operates without sufficient water flow.<br />

Confirm the following before attempting a water pressure switch adjustment:<br />

Water circulator pump is operating.<br />

<br />

<br />

<br />

Filter is clean.<br />

Water valves are set to flow water through the heat pump.<br />

“FLO” code is displayed (or displays intermittently).<br />

Locate Water Pressure Switch:<br />

<br />

<br />

<br />

<br />

Remove heat pump access plate (lower panel - below the control panel access plate)<br />

Locate water pressure switch. The switch will be found attached outside of the electrical enclosure,<br />

at lower edge; exact location will vary by heat pump model.<br />

Identify type of switch to adjust (“Len Gordon” or “TecMark”). To determine which brand pressure<br />

switch is installed compare water pressure switch in heat pump to Figure 22 and Figure 23. Follow<br />

the adjustment procedure for the appropriate switch.<br />

Should adjustment of water pressure switch prove unsuccessful, contact <strong>AquaCal</strong> AutoPilot<br />

Technical Support; site-specific factors may<br />

require the installation of an external flow<br />

switch.<br />

“Len Gordon” Switch:<br />

1) Locate black rectangular plastic tab,<br />

located on forward-facing side of the<br />

switch. See Figure 22. The black<br />

rectangle is a wheel lock tab.<br />

2) Slide tab left to unlock the adjustment<br />

wheel.<br />

3) With water pump operating and<br />

electrical power supplied to the heat<br />

pump, slowly rotate top of adjustment<br />

wheel to the left or right until “FLO” code<br />

(just) disappears.<br />

Rotate top of adjustment wheel to decrease water<br />

pressure required to start heat pump<br />

Tab shown in<br />

un-locked<br />

position<br />

Figure 22<br />

4) Once adjustment has been completed, slide wheel locking tab fully back to right-hand locked<br />

position.<br />

5) With electrical power remaining “ON” and heat pump operating, shut off power to circulating<br />

pump. If switch has been correctly adjusted, heat pump will shut off and “FLO” code will display<br />

when water pump stops.<br />

6) Reinstall heat pump front cover.