4400 & 4800 SERIES WET NICHE INSTALLATION INSTRUCTIONS
4400 & 4800 SERIES WET NICHE INSTALLATION INSTRUCTIONS
4400 & 4800 SERIES WET NICHE INSTALLATION INSTRUCTIONS
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>4400</strong> & <strong>4800</strong> <strong>SERIES</strong> <strong>WET</strong> <strong>NICHE</strong><br />
<strong>INSTALLATION</strong> <strong>INSTRUCTIONS</strong><br />
SAFETY WARNING:<br />
THE INSTALLER IS RESPONSIBLE FOR PROPER<br />
INSTALLA<br />
ALLATION.<br />
THESE FIXTURES MUST BE INSTALLED BY A<br />
QUALIFIED PERSON IN ACCORD<br />
CCORDANCE<br />
WITH<br />
NATIONAL ELECTRIC CODE AND RELEVANT<br />
LOCAL CODES.<br />
READ 1990 NATIONAL ELECTRIC CODE<br />
ARTICLE 680-20 THRU 680-22 PRIOR TO<br />
INSTALLING.<br />
ATTACH WIRE TIES TO MOUNTING<br />
EARS AND SECURE TO RE-BAR<br />
<strong>NICHE</strong><br />
1. INSTALL <strong>NICHE</strong> IN PLACE AND SECURE<br />
TO RE-BAR BY WIRING TO EARS ON<br />
<strong>NICHE</strong>.<br />
2. MAKE SURE <strong>NICHE</strong> FLANGE WILL BE<br />
COMPLETELY COVERED IN PLASTER<br />
FOR A WATER-TIGHT SEAL. BE SURE<br />
THE <strong>NICHE</strong> IS LEVEL.<br />
3. ATT<br />
TTACH<br />
THE CONDUIT TO THE <strong>NICHE</strong><br />
HOUSING.<br />
NOTE:<br />
THE CONDUIT HUB MUST BE ORIENTED AT<br />
THE TOP. WHEN LOW VOLTAGE FIXTURES<br />
OR PLASTIC CONDUIT IS USED IT IS<br />
RECONNENDED THAT 1" CONDUIT<br />
BE USED.<br />
4. IF PLASTIC CONDUIT IS USED, A #8<br />
STRANDED COPPER BOND WIRE MUST<br />
BE POSITIVELY ATT<br />
TTACHED IN THE<br />
JUNCTION BOX,<br />
PULLED THROUGH<br />
THE CONDUIT, AND SECURED TO THE<br />
BONDING LUG INSIDE THE <strong>NICHE</strong>.<br />
5. TO O MEET NATIONAL ELECTRIC CODE<br />
REQUIREMENTS:<br />
"THE TERMINATION<br />
TION<br />
OF THE #8 CONDUCTOR OR IN THE FORM<br />
ING SHELL SHALL BE COVERED<br />
WITH,<br />
OR ENCAPSULATED IN, A LISTED<br />
POTTING COMPOUND TO O PROTECT<br />
SUCH CONNECTION FROM<br />
THE POS<br />
SIBLE DETERIORATING TING EFFECT OF<br />
POOL WATER."<br />
6. COVER <strong>NICHE</strong>, SHOOT T GUNITE, AND<br />
PRIME TRIM PLASTER TO FLANGE<br />
EDGE.<br />
7. INSTALL FIXTURE.<br />
POOL FINISH SURFACE (PLASTER)<br />
MUST BE CUT BACK BEHIND THE<br />
STAINLESS STEEL <strong>NICHE</strong>-CAN<br />
FLANGES, FOR A WATERTIGHT SEAL.<br />
POOL FINISH SURFACE (PLASTER)<br />
MUST BE CUT BACK BEHIND THE<br />
STAINLESS STEEL <strong>NICHE</strong>-CAN<br />
FLANGES, FOR A WATERTIGHT SEAL.<br />
Swimming pools 18" min. per NEC.<br />
Recommend 2" for Fountain<br />
WATER<br />
#8 BONDING WIRE<br />
(FOR PVC CONDUIT USES ONLY)<br />
LIGHT<br />
POOL FINISH SURFACE (PLASTER)<br />
MUST BE CUT BACK BEHIND THE<br />
STAINLESS STEEL <strong>NICHE</strong>-CAN<br />
FLANGES, FOR A WATERTIGHT SEAL.<br />
<strong>NICHE</strong><br />
<strong>NICHE</strong><br />
HYDREL is a registered trademark of Lithonia Lighting<br />
12881 BRADLEY AVENUE, SYLMAR, CALIFORNIA 91342 • PHONE: 818/362-9465 • FAX: 818/362-6548<br />
HYDREL INS'S\INS-UWL-3 10/99
<strong>4400</strong> & <strong>4800</strong> <strong>SERIES</strong> <strong>WET</strong> <strong>NICHE</strong><br />
<strong>INSTALLATION</strong> <strong>INSTRUCTIONS</strong><br />
JUNCTION BOX<br />
CONDUIT<br />
Hydrel fixtures are designed to meet 1990 National Electric Code, Article<br />
680 requirements. The N.E.C. requires that fixtures must be installed so<br />
that the fixture lens is at least 18" below normal water level. The junction<br />
box shall be located at least 8" above maximum water level, pool deck or<br />
ground, whichever is greater. The junction box shall be located not less<br />
than 4 feet from the perimeter of the pool, unless separated from the pool<br />
by a fence, wall or other permanent barrier. Junction boxes mounted<br />
above grade in the walkway around the pool shall be afforded additional<br />
protection by locating them in such places as under a diving board,<br />
adjacent to fixed structures, etc. Check local codes to assure acceptance.<br />
<strong>4400</strong> <strong>SERIES</strong><br />
TWIST AND LOCK MOUNTING<br />
<strong>4800</strong> <strong>SERIES</strong><br />
CONCRETE <strong>NICHE</strong>S, EXTENDED<br />
#8 STRANDED<br />
EQUIP. GROUND<br />
BONDING<br />
Mounting the fixture into the niche is simple and positive with the Twist and<br />
Lock feature. Fixture may be inserted directly into the niche. (No hooking a<br />
lower lug or slipping over a pin.) Fixture is inserted and given a slight<br />
clockwise twist. The retaining screw then provides a positive fixture lock.<br />
NOTE: Screw should be located at top of fixture.<br />
SOLID<br />
WIRE<br />
JUNCTION BOX AND FIXTURE <strong>INSTALLATION</strong> <strong>NICHE</strong> MOUNT<br />
(FOUNTAINS ONLY)<br />
TILE OR CONCRETE<br />
FOUNTAIN FLOOR<br />
FIXTURE<br />
JUNCTION BOX<br />
PC-21<br />
POTTING COMPOUND<br />
PER NEC680<br />
USR<br />
STRAIN RELIEF<br />
<strong>NICHE</strong><br />
EXCESS<br />
CORD COILED<br />
SO LAMP CAN<br />
BE REMOVED<br />
1" SERVOCE<br />
ENTRANCE<br />
CONDUIT<br />
HYDREL is a registered trademark of Lithonia Lighting<br />
#8 SOLID COPPER<br />
BOND WIRE<br />
CORD<br />
CONDUIT<br />
(3-90° BENDS MAX.)<br />
12881 BRADLEY AVENUE, SYLMAR, CALIFORNIA 91342 • PHONE: 818/362-9465 • FAX: 818/362-6548<br />
HYDREL INS'S\INS-UWL-3 10/99