BST 14i3 - Wieland Electric
BST 14i3 - Wieland Electric
BST 14i3 - Wieland Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>BST</strong> 14i2<br />
Technical data<br />
<strong>BST</strong> 14i2<br />
General:<br />
Poles: 2<br />
Rated voltage:<br />
Rated current:<br />
Wire colors:<br />
Rated cross-sections:<br />
Connection type:<br />
Coding:<br />
Locking device:<br />
Strain relief.<br />
50 V<br />
3 A<br />
Degree of protection: IP 20<br />
Wire stripping length:<br />
Feed through resistance:<br />
Materials:<br />
Continuous temperature:<br />
1 (+) red, 2 (-) black<br />
0.25 – 0.75 mm²<br />
Spring-loaded<br />
Mechanical coding, identifi ed by color<br />
Integrated<br />
Integrated in connector housing<br />
8 mm<br />
Approx. 5 mΩ per female-male connection<br />
Thermoplastic PE compound, halogen-free<br />
Contacts: plated brass<br />
70° C<br />
Green (KNX):<br />
Coding:<br />
Approvals:<br />
Cables:<br />
Accord. to KNX standard<br />
Connectors as per KNX manual<br />
Accord. to KNX guidelines<br />
Blue (dimming applications):<br />
Coding:<br />
Cables:<br />
Individual coding<br />
Designed for 230 V<br />
When using <strong>BST</strong> 14i2 for dimming applications (DALI/1-10 V), the following must be observed:<br />
The given voltage is not Safety Extra Low Voltage (SELV) but Functional Extra Low Voltage (FELV).<br />
Thus, when laying supply and signal cables together, the installation material must comply with the highest occurring<br />
supply voltage in order to ensure safe separation of the circuits.<br />
<strong>BST</strong> 14i2 pastel blue is suitable for this application when the following is observed according to the<br />
general installation guidelines:<br />
– fixed installation (e.g. suspended ceilings)<br />
– all components are plugged<br />
– unused connectors have to be closed with covers<br />
(female: 05.563.7753.0, male: 05.563.7853.0)<br />
– installation in areas only accessible for authorized personnel<br />
– <strong>BST</strong> 14 cables with blue and black connectors made by WIELAND are designed for mains voltage<br />
– no “TouchDIM“ application<br />
40