24.11.2014 Views

FIRE ALARM REPORTING SYSTEM, RADIO TYPE Design ... - WPC

FIRE ALARM REPORTING SYSTEM, RADIO TYPE Design ... - WPC

FIRE ALARM REPORTING SYSTEM, RADIO TYPE Design ... - WPC

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

JBLM DESIGN STANDARDS<br />

SECTION 28 31 33.00 10 - <strong>FIRE</strong> <strong>ALARM</strong> <strong>REPORTING</strong> <strong>SYSTEM</strong>, <strong>RADIO</strong> <strong>TYPE</strong><br />

<strong>Design</strong> Requirements<br />

a. The transceiver number and the transceiver zones to be used for each project shall be<br />

designated by the Ft. Lewis Fire Inspectors / DPW Fire Alarm Maintenance personnel.<br />

The Ft. Lewis Fire Alarm Transceiver frequency is 139.6750 MHz.<br />

b. The following initiating events or troubles shall require their own transmitted zone<br />

-deluge sprinkler system<br />

-water flow (sprinkler)<br />

-low air pressure (dry sprinkler)<br />

-separate buildings or quads<br />

-FACP common trouble<br />

c. No conduit in the top or bottom of transmitter enclosures<br />

d. All threaded connections on the antenna mast shall have silicone seal added for water<br />

proofing the joint.<br />

e. All fire alarm transceivers must be listed or approved for use with the existing Monaco<br />

D-21M base reporting system and meet the following minimum requirements:<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

FM approved<br />

Narrowband radio communications with the Monaco D-21 base reporting system.<br />

• FCC certified for narrowband operation and meets the requirements of the<br />

NTIA<br />

• Manual of Regulations and Procedures for Federal frequency<br />

Management.<br />

Fallback communications to hardwire connection if wired (phone line backup).<br />

Transmits live-voice and pre-recorded messages from the D-21 Mass Notification<br />

System to within-building mass notification panels or wide-area speaker stations.<br />

Receives live voice from radio, telephone, and microphone.<br />

Pre-recorded messages can be triggered via relay contact closure.<br />

Security features prevents unauthorized take over of live-voice transmissions.<br />

Supervised connection to mass notification panel.<br />

Status LEDs reflect the status of the transciever: general trouble, system fault,<br />

in-communication, carrier detect, transmit, primary power, battery boost charge,<br />

and battery float charge.<br />

Communication LEDs indicate the method of communication used: radio or<br />

hardwire and whether or not a live-voice message is being sent.<br />

Full-duplex RS-232 port used to program the transciever via connection to a<br />

laptop computer.<br />

115 or 230 Vac power is monitored with automatic switchover to backup battery<br />

power that provides standby power.<br />

Self test, stuck transmitter disconnect, reset, acknowledge, and battery reconnect<br />

switches.<br />

Local audible alert.<br />

Real time clock and calendar.<br />

At least 1/2 Mb of program memory.<br />

SECTION 28 31 33 Page 1


o<br />

o<br />

At least 1/2 Mb of non-volatile data storage.<br />

One selectable RS-422/RS-485 port for communication with peripheral<br />

equipment or hardwire connection to multiple units connected together for<br />

communication with the D-21.<br />

Notes to <strong>Design</strong>ers on Drawing Content<br />

a. All as-builts shall be required to show the exact run of conduit, quantity of wires, wire<br />

color code, location of every initiating device, signaling device, module, and any major<br />

junction boxes or power supplies. The plans will also show loop number and the address<br />

of each device, or module, if system is addressable.<br />

SECTION 28 31 33.00 10<br />

<strong>FIRE</strong> <strong>ALARM</strong> <strong>REPORTING</strong> <strong>SYSTEM</strong>, <strong>RADIO</strong> <strong>TYPE</strong><br />

11/08<br />

PART 1<br />

GENERAL<br />

1.1 REFERENCES<br />

The publications listed below form a part of this specification to the<br />

extent referenced. The publications are referred to within the text by the<br />

basic designation only.<br />

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)<br />

IEEE C135.30<br />

IEEE C62.41.1<br />

IEEE C62.41.2<br />

(1988) Zinc-Coated Ferrous Ground Rods for<br />

Overhead or Underground Line Construction<br />

(2002) IEEE Guide on the Surges Environment<br />

in Low-Voltage (1000 V and Less) AC Power<br />

Circuits<br />

(2002) IEEE Recommended Practice on<br />

Characterization of Surges in Low-Voltage<br />

(1000 V and Less) AC Power Circuits<br />

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)<br />

NEMA ICS 1<br />

(2000; R 2005; R 2008) Standard for<br />

Industrial Control and Systems General<br />

Requirements<br />

NATIONAL <strong>FIRE</strong> PROTECTION ASSOCIATION (NFPA)<br />

SECTION 28 31 33 Page 2


NFPA 70 (2007; AMD 1 2008) National Electrical Code -<br />

2008 Edition<br />

NFPA 72<br />

NFPA 780<br />

(2006) National Fire Alarm Code<br />

(2007) Standard for the Installation of<br />

Lightning Protection Systems<br />

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)<br />

TIA-222-G<br />

(2005) Structural Standards for Antenna<br />

Supporting Structures and Antennas<br />

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)<br />

47 CFR 15 Radio Frequency Devices<br />

UNDERWRITERS LABORATORIES (UL)<br />

UL 1242<br />

UL 467<br />

UL 6<br />

UL 797<br />

(2006; Rev thru Jul 2007) Standard for<br />

Electrical Intermediate Metal Conduit --<br />

Steel<br />

(2007) Standard for Grounding and Bonding<br />

Equipment<br />

(2007) Standard for Electrical Rigid Metal<br />

Conduit-Steel<br />

(2007) Standard for Electrical Metallic<br />

Tubing -- Steel<br />

1.2 <strong>SYSTEM</strong> DESCRIPTION<br />

Provide a central reporting system complying with NFPA 72. The equipment<br />

furnished shall be listed by Underwriters Laboratories, or Factory Mutual<br />

Engineering and Research, or be approved or listed by a nationally<br />

recognized testing laboratory. Furnish tags with stamped identification<br />

numbers for keys and locks. Locks shall be keyed alike. On JBLM, all locks<br />

required for fire alarm system components shall use 211 keys (panels,<br />

subpanels, pull stations, excluding Monaco BTX). The radio system shall<br />

report alarms to the radio fire alarm monitoring base station. The system<br />

shall be a completely supervised radio type fire alarm reporting system.<br />

The system shall indicate the area of alarm. The radio communication link<br />

shall be supervised and operated in accordance with NFPA 72. Electrical<br />

supervision shall be provided for all circuits and for all positions of<br />

interface panel control switches.<br />

1.2.1 Operational Features<br />

The JBLM Fire Alarm Maintenance Shop prefers the following characteristics<br />

be designed into fire alarm systems:<br />

a. All devices in new addressable fire alarm systems to be rotary<br />

decade switch addressable.<br />

b. All new fire alarm systems to have Windows based programming.<br />

SECTION 28 31 33 Page 3


c. All new fire alarm systems to have drift compensation and<br />

maintenance alert. The maintenance alert shall be included as a zone in<br />

the fire alarm transmitter.<br />

Fire alarm panels, transceivers and other sensitive electrical or electronic<br />

equipment shall be installed in dedicated electrical equipment rooms readily<br />

accessible to maintenance personnel and independent of building occupants<br />

whenever possible (i.e., space accessible from the exterior of the<br />

facility), not in mechanical spaces or other areas subject to to excessive<br />

temperature or moisture. To protect control equipment in areas that are not<br />

continuously occupied, smoke/heat detection or a suppression system nozzle<br />

shall be provided. Each control unit location shall provide notification of<br />

fire at that location. A suppression system nozzle is preferred over a<br />

heat/smoke detector.<br />

Addressable fire alarm panels shall display a history of events on the panel<br />

display without additional software/hardware.<br />

Annunciators are not a desired fire alarm system component. Do not include<br />

or install an annunciator in the fire alarm system unless specifically<br />

required by code.<br />

1.3 SUBMITTALS<br />

Government approval is required for submittals with a "G" designation;<br />

submittals not having a "G" designation are for information only. When<br />

used, a designation following the "G" designation identifies the office that<br />

will review the submittal for the Government. Submit the following in<br />

accordance with Section 01 33 00 SUBMITTAL PROCEDURES:<br />

SD-02 Shop Drawings<br />

Fire Alarm Reporting System; G<br />

Detail drawings, signed by the Registered Professional Engineer,<br />

consisting of a complete list of equipment and material, including<br />

manufacturer's descriptive and technical literature, catalog cuts,<br />

and installation instructions. Note that the contract drawings<br />

show layouts based on typical detectors. Check the layout based on<br />

the actual detectors to be installed and make any necessary<br />

revisions in the detail drawings. Detail drawings shall also<br />

contain complete wiring and schematic diagrams for the equipment<br />

furnished, equipment layout, and any other details required to<br />

demonstrate that the system has been coordinated and will properly<br />

function as a unit.<br />

Wiring for Systems; G<br />

Detail point-to-point wiring diagram, signed by the Registered<br />

Professional Engineer, showing all points of connection. Diagram<br />

shall include connections between system devices, appliances,<br />

control panels, supervised devices, an all equipment that is<br />

activated or controlled by the panel.<br />

Record Drawings; G<br />

SECTION 28 31 33 Page 4


Two copies of as-built drawings showing the exact run of conduit,<br />

quantity of wires, wire color code, location of every initiating<br />

device, signaling device, module, and any major junction boxes or<br />

power supplies. The plans shall also show Loop number and the<br />

address of each device, or module, if the system is addressable.<br />

Provide electronic copy on CD in AutoCAD.<br />

SD-03 Product Data<br />

Battery<br />

Substantiating battery calculations for supervisory and alarm<br />

power requirements. Ampere-hour requirements for each system<br />

component, each panel component and the battery recharging period<br />

shall be included.<br />

Spare Parts<br />

Spare parts data for each different item of material and<br />

equipment specified, after approval of detail drawings, and not<br />

later than 1 month prior to the date of beneficial occupancy. Data<br />

shall include a complete list of parts and supplies with the<br />

current unit prices and source of supply and a list of the parts<br />

recommended by the manufacturer to be replaced after 1 year of<br />

service.<br />

Training<br />

Provide training courses for the operations and maintenance<br />

staff. Conduct the system operation training in the building where<br />

the system is installed after the system is functionally complete.<br />

The system maintenance, expansion, and modification training shall<br />

consist of on site and/or off site class room training as necessary<br />

to fully qualify the government operations and maintenance<br />

technicians to perform all levels of maintenance, expansions, and<br />

modifications to the fire alarm system, hardware, software, and<br />

components. This training will include (and turn over to the<br />

government) all proprietary licenses, software, and tools to<br />

perform the required tasks. All specialized equipment and/or<br />

training to program, edit existing program, add or delete devices,<br />

shall be provided as a part of the fire alarm system training.<br />

Test Procedures<br />

Detailed test procedures for the fire alarm reporting system 60<br />

days prior to performing system tests. The test procedures shall<br />

be signed by the Registered Professional Engineer.<br />

SD-06 Test Reports<br />

Testing<br />

Test reports in booklet form showing field tests performed to<br />

prove compliance with the specified performance criteria, upon<br />

completion and testing of the installed system. Each test report<br />

shall document all readings, test results, and indicate the final<br />

position of controls.<br />

SECTION 28 31 33 Page 5


SD-07 Certificates<br />

Equipment<br />

Certified copies of current applicable approvals or listings<br />

issued by UL, FM or other nationally recognized testing laboratory<br />

showing compliance with applicable NFPA standards.<br />

Certificate of Fitness<br />

Provide Certificate of Fitness for any individual,<br />

business, or firm engaged in the inspecting, designing, testing,<br />

maintaining or servicing of fire and life safety systems.<br />

Registered Professional Engineer<br />

Verification of experience and license number for Registered<br />

Professional Engineer, as specified.<br />

Installers<br />

Verification of experience and license number for Installer, as<br />

specified.<br />

SD-10 Operation and Maintenance Data<br />

Fire Alarm Reporting System; G<br />

Two complete hard copies and one electronic copy in Adobe Acrobat<br />

(.pdf) format on CD or DVD of operating instructions outlining<br />

step-by-step procedures required for system startup, operation, and<br />

shutdown. The instructions shall include the manufacturer's name,<br />

model number, service manual, parts list, and brief description of<br />

all equipment and their basic operating features.<br />

Two complete hard copies and one electronic copy in Adobe Acrobat<br />

(.pdf) format on CD or DVD of maintenance instructions listing<br />

routine maintenance procedures, possible breakdowns and repairs,<br />

and troubleshooting guide. The instructions shall include conduit<br />

layout, equipment layout and simplified wiring, and control<br />

diagrams of the system as installed. Instructions shall be<br />

approved prior to training.<br />

1.4 QUALITY ASSURANCE<br />

Provide the services of a Registered Professional Engineer with at least 4<br />

years of current experience in the design of fire protection and detection<br />

systems. Submit the qualifications, with verification of experience and<br />

license number, for Engineers, Technicians, Installers and contractors as<br />

specified in UFC 3-600-01. Any individual, business, or firm engaged in the<br />

inspecting, testing, maintaining, designing or servicing of fire and life<br />

safety systems and equipment shall be certified to perform these activities<br />

in accordance with Appendix G of FL REG 420-30. A certificate of fitness<br />

can be obtained by completing the Employee Application for Certification of<br />

Fitness with supporting credentials to the JBLM Fire Prevention branch.<br />

Allow five working days for processing of application for Certificate of<br />

SECTION 28 31 33 Page 6


Fitness. Contact the JBLM Fire Prevention Branch at 253-966-7155 or 253-<br />

966-1764 for additional information. Submit a copy of certificate of<br />

fitness to the Contracting Officer or the Contracting Officer's<br />

Representative prior to starting work on life safety system and equipment.<br />

1.5 DELIVERY, STORAGE, AND HANDLING<br />

Protect all equipment delivered and placed in storage from the weather,<br />

humidity and temperature variations, dirt, dust, and other contaminants.<br />

1.6 SPECIAL TOOLS AND SPARE PARTS<br />

Furnish to the Contracting Officer software (including proprietary software,<br />

codes, and passwords), connecting cables, proprietary equipment necessary<br />

for the maintenance, testing, and reprogramming of the equipment. Furnish<br />

special tools necessary for the maintenance of the equipment. Provide one<br />

spare set of fuses of each type and size required and 5 spare lamps of each<br />

type.<br />

PART 2<br />

PRODUCTS<br />

2.1 STANDARD PRODUCTS<br />

Provide material and equipment which are the standard products of a<br />

manufacturer regularly engaged in the manufacture of the products and that<br />

essentially duplicate items that have been in satisfactory use for at least<br />

2 years prior to bid opening. Equipment shall be supported by a service<br />

organization that can provide service within 24 hours.<br />

2.2 NAMEPLATES<br />

Major components of equipment shall have the manufacturer's name, address,<br />

type or style, voltage and current rating, and catalog number on a<br />

noncorrosive and nonheat-sensitive plate which is securely attached to the<br />

equipment.<br />

2.3 <strong>RADIO</strong> <strong>FIRE</strong> <strong>ALARM</strong> TRANSMITTER (TRANSCEIVER)<br />

Radio Fire Alarm Transmitter (Transceiver) shall be compatible with the<br />

Radio Fire Alarm Monitoring Base Station. The transmitter shall be all<br />

solid state and comply with applicable portions of 47 CFR 15 governing type<br />

acceptance. All transmitters of a common configuration shall be<br />

interchangeable with the other devices furnished by the manufacturer. Each<br />

transmitter and interface device shall be the manufacturer's current<br />

commercial product completely assembled, wired, tested at the factory, and<br />

delivered ready for installation and operation.<br />

2.3.1 Frequency Allocation<br />

The transmitters shall operate on a frequency of 139.6750 MHz.<br />

2.3.2 Power Requirements<br />

Transmitters shall be powered by a combination of locally available 120 Vac,<br />

and sealed lead-acid type batteries requiring no additional water. In the<br />

event of loss of 120 Vac power, the transmitter shall automatically switch<br />

to battery operation. The switchover shall be accomplished with no<br />

SECTION 28 31 33 Page 7


interruption of protective service, without adversely affecting the batterypowered<br />

capabilities, and shall cause the transmission of a trouble message<br />

in no less than 5 seconds. Upon restoration of ac power, transfer back to<br />

normal ac power supply shall be automatic and the battery shall be<br />

recharged. The converter/battery charger shall be installed within the<br />

transmitter housing. Power supply transient filtering shall be provided.<br />

2.3.2.1 Battery Power<br />

The battery package shall be capable of supplying all the power requirements<br />

for a given transmitter.<br />

2.3.2.2 Battery Duration<br />

Radio fire alarm transmitter standby battery capacity shall provide<br />

sufficient power to operate the transmitter in a normal standby status for a<br />

minimum of 72 hours and shall be capable of transmitting alarms during that<br />

period. The capacity for battery-only powered transmitters shall be 6<br />

months before recharging is necessary.<br />

2.3.2.3 Battery Supervision<br />

Each radio fire alarm transmitter shall constantly monitor and supervise its<br />

own battery powered supply. A low-battery condition shall be reported when<br />

battery voltage falls below 85 percent of the rated voltage.<br />

2.3.3 Functional Requirements<br />

2.3.3.1 Interfacing Indicators and Controls<br />

Transmitters shall incorporate the provisions for auxiliary interconnection<br />

to existing interior alarm systems.<br />

2.3.3.2 Generation of Signals<br />

Each transmitter shall be a standard design which allows the immediate<br />

transmission of all initiated signals.<br />

2.3.3.3 Power Output<br />

The radio frequency (RF) power output of each transmitter shall be<br />

sufficient for reliable alarm reporting. The minimum RF power output shall<br />

be 1 watt.<br />

2.3.3.4 Memory<br />

Transmitters shall have memory capability. Multiple, simultaneous alarms<br />

shall not result in the loss of any messages. Messages shall be stored<br />

until they are transmitted.<br />

2.3.3.5 Transmission Confirmation<br />

When a signal is initiated at a public box (push button or pull lever), the<br />

transmitter shall produce an audible or visual indication that the<br />

transmitter is operating and that a signal is being sent.<br />

SECTION 28 31 33 Page 8


2.3.3.6 Transmitter Identity Code<br />

Each transmitter shall transmit a distinct identity code number as part of<br />

all signals emanating from the transmitter. The identity code shall allow<br />

for no less than a 3 digit code selection and be transmitted not less than<br />

three complete rounds (cycles). The transceiver number and the transceiver<br />

zones to be used for each project shall be designated by the JBLM Fire<br />

Inspectors/DPW Fire Alarm Maintenance personnel. The following initiating<br />

events or troubles shall require their own transmitted zone:<br />

a. Deluge sprinkler system.<br />

b. Water flow (sprinklers).<br />

c. Low air pressure (dry sprinklers).<br />

d. Separate buildings or quads.<br />

d. FACP common trouble.<br />

2.3.3.7 Message <strong>Design</strong>ations<br />

Each transmitter shall allow as a minimum no less than 10 distinct and<br />

individually identifiable message designations as to the types or causes of<br />

transmitter actuation.<br />

a. Master Message: Master messages shall be transmitted upon<br />

automatic actuation of the transmitter. The building and zone causing<br />

actuation shall be individually identified as part of this<br />

transmission. The transmitter shall be capable of identifying and<br />

transmitting a minimum of 3 master (zone) messages.<br />

b. Test Message: Test message shall be capable of both manual and<br />

automatic actuation. When a transceiver method is employed, it shall<br />

provide for automatic interrogation at preselected periods or<br />

continuous automatic interrogation in accordance with the governing<br />

standard. Additionally, transceiver systems shall provide for<br />

selective interrogation at times determined by the user. Testing the<br />

automatic test actuation shall occur a minimum of once in each 24-hour<br />

period, at an optionally preselected time. Stability of the electronic<br />

actuating device shall be plus or minus 1 minute per month within the<br />

temperature range stipulated for system operation. Actuation of the<br />

"Test" message designation, regardless of initiating means, shall cause<br />

no less than 1 complete message to be sent.<br />

c. Tamper Message <strong>Design</strong>ation: The tamper message shall be<br />

automatically transmitted when a tamper switch is tripped in the<br />

transmitter housing.<br />

d. Trouble Message <strong>Design</strong>ation: Trouble message shall be<br />

automatically transmitted in the event of a failure in excess of 1<br />

minute of the main operating power source of the transmitter.<br />

2.3.4 Transmitter Housings<br />

The housings on transmitters shall be fabricated from corrosion-resistant<br />

cast metal or suitable substitute which has the physical strength sufficient<br />

SECTION 28 31 33 Page 9


to ward off physical damage normally expected to be received by vandalism.<br />

The housing shall be sealed against the entry of moisture, dust, dirt,<br />

insects, and other foreign objects. Exterior housings shall be NEMA 4X.<br />

2.3.4.1 Lock<br />

Internal components shall be protected from vandalism by a tamper-proof lock<br />

on the transmitter housing. The housing shall allow access to all internal<br />

components for testing, servicing, and replacement at the installation site.<br />

2.3.4.2 Mounting<br />

Transmitter housings shall be designed for universal mounting on walls,<br />

poles, or pedestals. Mounting shall utilize either lag bolts, anchor bolts,<br />

stainless steel banding, mounting brackets, or a shackle/bolt combination,<br />

as applicable to the specific installation.<br />

2.3.4.3 Operating Panel<br />

Each publicly accessible transmitter shall have an operating panel that<br />

incorporates a dedicated signal initiating device (pull hook or push button)<br />

clearly identified for the initiation of "<strong>FIRE</strong>" signals. The device shall<br />

be protected with a conventional spring-loaded, "fast-action" break-glass,<br />

or similar pull-type door that allows observation of the actuation device<br />

when in the closed position. The door shall be fabricated and finished in a<br />

manner consistent with that required of the main housing.<br />

2.3.4.4 Labeling<br />

Each publicly accessible transmitter shall be labeled on both sides and on<br />

the front surface with the word "<strong>FIRE</strong>." The label shall be white with red<br />

lettering.<br />

2.3.5 Environmental Operating Requirements<br />

The transmitter shall be designed for reliable outside operation in an<br />

ambient temperature range of -22 to 140 degrees F. Transmitters shall be<br />

corrosion-resistant and designed for reliable operation under adverse<br />

climatic conditions including 100 mph winds, ice, rain, and snow storms.<br />

2.3.6 Painting<br />

Radio fire alarm transmitter and interface housings shall be factory<br />

painted. The finish color shall be fire engine red. Painted surfaces<br />

damaged during installation shall be repainted to match existing paint.<br />

2.4 <strong>RADIO</strong> TRANSMITTER INTERFACE DEVICE<br />

The interface device shall provide a means of converting the signals that<br />

are available from the local control equipment into a form that is<br />

compatible with the transmitter inputs, while still maintaining electrical<br />

supervision of the entire system. Interface devices shall be utilized when<br />

direct connection between local control equipment and the transmitter is not<br />

possible. Interface devices shall be completely assembled, wired, tested at<br />

the factory, and delivered ready for installation and operation.<br />

SECTION 28 31 33 Page 10


2.4.1 Enclosure<br />

When furnished as an independent self-contained device, the interface device<br />

shall be incorporated into an enclosure conforming to NEMA ICS 1 or other<br />

national standard as required by its location.<br />

2.4.2 Indicators<br />

Indicators shall be provided to indicate alarm and trouble conditions and<br />

shall consist of a red fire alarm and an amber trouble light. The<br />

indicators shall be designed to ensure visibility during daylight hours and<br />

to indicate the reporting zone.<br />

2.4.3 Access<br />

Switches and other controls shall not be accessible without the use of a<br />

key. Access to controls shall be by unlocking and opening a panel or door.<br />

2.4.4 Mounting<br />

Interface housings shall be designed for universal mounting on walls, poles,<br />

or pedestals. Mounting shall utilize either lag bolts, anchor bolts,<br />

stainless steel banding, mounting brackets, or a shackle/bolt combination,<br />

as applicable to the specific installation.<br />

2.4.5 Inputs/Outputs<br />

Each interface panel shall provide, as a minimum, the number of alarm<br />

circuit inputs and outputs indicated. Each input circuit shall be arranged<br />

so that the alarm signals shall override the trouble signals.<br />

2.5 <strong>RADIO</strong> <strong>FIRE</strong> <strong>ALARM</strong> MONITORING BASE STATION<br />

2.5.1 Receiver (Transceiver) System<br />

One master radio fire alarm receiving (transceiver) system compatible with<br />

transmitter frequency shall be provided. The system shall be completely<br />

assembled, wired, tested at the factory, and delivered ready for<br />

installation and operation. Transceivers shall be solid-state design and<br />

shall use frequency modulation. The transceiver can be a single integrated<br />

unit, or it may consist of separate transmitter and receiver modules with a<br />

common power supply, amplifier, and control unit. All fire alarm<br />

transceivers must be listed or approved for use with Monaco D-21M base<br />

reporting system and meet the following minimum requirements:<br />

a. FM approved, narrowband radio communications with Monaco D-21 base<br />

reporting system.<br />

b. FCC certified for narrowband operation and meets the requirements<br />

of the NTIA Manual of Regulations and Procedures for Federal Frequency<br />

Management.<br />

c. Fallback communications to hardwire connections if wired (phone<br />

line backup).<br />

SECTION 28 31 33 Page 11


d. Transmit live voice and pre-recorded messages from the D-21 mass<br />

notification system to within building mass notification panels or<br />

wide-area speaker stations.<br />

e. Receive live voice from radio, telephone, and microphone.<br />

f. Pre-recorded messages can be triggered via relay contact closure.<br />

g. Security features prevents unauthorized take over of live voice<br />

transmissions.<br />

h. Supervised connection to mass notification panel.<br />

i. Status LED's reflect the status of the transceiver general trouble,<br />

system fault, in-communication, carrier detect, transmit, primary<br />

power, battery boost charge, and battery float charge.<br />

j. Communication LED's indicate the method of communication used:<br />

radio or hardwire, and whether or not a live voice message is being<br />

sent.<br />

k. Full-duplex RS-232 port used to program the transceiver via<br />

connection to a laptop computer.<br />

l. 115 or 230 Vac power is monitored with automatic swithchover to<br />

backup battery power that provides standby power.<br />

m. Self test, stuck transmitter disconnect, reset, acknowledge, and<br />

battery reconnect switches.<br />

n. Local audible alert.<br />

o. Real time clock and calendar.<br />

p. At least 1/2 Mb of program memory.<br />

q. At least 1/2 Mb of non-volatile data storage.<br />

r. One selectable RS-422/RS-485 port for communication with peripheral<br />

equipment or hardwire connection to multiple units connected together<br />

for communication with the D-21.<br />

2.5.1.1 Transmitter Section<br />

Transmitter shall operate on a frequency of 139.6750 MHz. Frequency<br />

stability shall be within 0.00025 percent over the operating temperature<br />

range. Transmitter shall be designed to work into a 50-ohm load. Frequency<br />

deviation shall be less than or equal to 5 kHz. Audio response shall be<br />

within plus 1 dB and minus 3 dB over the 300 Hz to 3,000 Hz range.<br />

2.5.1.2 Receiver Section<br />

Receiver antenna input impedance shall be 50 ohms. Receiver shall be tuned<br />

to a frequency assignment of 139.6750 MHz. Receiver shall have no more than<br />

5 percent audio distortion measured at 1,000 Hz. Receiver shall have a<br />

noise level not greater than minus 50 dB below the signal level. Receiver<br />

output shall be compatible with the associated device.<br />

SECTION 28 31 33 Page 12


2.5.2 Fire Alarm Console<br />

Console shall contain a complete and independent fire alarm receiving<br />

system, consisting of, as a minimum, a radio receiver/transmitter, signal to<br />

message decoder, audio alarm signaling devices, audio alarm silence switch,<br />

visual display, alarm reset switch(es), alarm recording printer, primary and<br />

emergency power supplies, power supply monitors, memory devices, and all<br />

necessary interconnecting cables.<br />

2.5.2.1 Audible Fire Alarm<br />

The audible alarm signaling devices used to indicate the receipt of fire<br />

alarm messages shall produce a unique sound. The device shall be internally<br />

mounted in the console and shall be activated upon receipt of all fire alarm<br />

signals. The audible devices used to indicate the receipt of<br />

transmitter/interface trouble messages, including tamper and low-battery<br />

voltage, shall be separate and distinct from the device used to denote<br />

receipt of fire alarm messages.<br />

2.5.2.2 Visual Display<br />

Console display shall indicate, as a minimum, the originating transmitter<br />

identity code number and shall include the following message designations:<br />

a. Fire<br />

b. Trouble<br />

c. Battery<br />

d. Test<br />

e. Tamper<br />

f. Master Zone 1 thru 3<br />

2.5.2.3 Console Memory<br />

Console shall have a memory buffer capable of retaining a minimum of 500<br />

transmitter codes, together with the specific message designations<br />

associated with each transmitter. The system shall reject any received<br />

message not matching the programmed transmitter codes where such message<br />

identification code is not stored in the system. Upon command, the console<br />

shall display and print a summary of transmitters which have transmitted a<br />

low-battery or trouble message, or failed to transmit a message during the<br />

previous 24-hour test period. Any incoming transmitter signal shall preempt<br />

the command display and printout function, and be processed, displayed,<br />

and printed. The 24-hour memory shall not be purged and shall always be<br />

current and available. Transmitter memory data shall not be lost in the<br />

event of a total loss of operating or emergency power supplies.<br />

2.5.2.4 Console Supervision<br />

The supervisory system shall provide constant supervision of the operating<br />

conditions of the console. Indicators shall be provided for each major<br />

component, and an audible signal shall be produced in the event of failure<br />

of any major component. A switch shall be provided to silence the audible<br />

trouble signal.<br />

2.5.2.5 Receiver Supervision<br />

SECTION 28 31 33 Page 13


The supervisory system shall provide constant supervision and display of the<br />

operating condition of the radio receivers, and shall indicate an abnormal<br />

condition when a radio fire alarm transmitter carrier lasting more than 15<br />

seconds is detected. The receiver's ability to properly receive and decode<br />

an incoming signal shall be tested at least once every 24 hours.<br />

2.5.2.6 Manual Battery Test<br />

Console shall have a switch to manually place the console on emergency<br />

battery power for test purposes.<br />

2.5.2.7 Electrical Connections<br />

Console shall be designed with modular components to allow interchange of<br />

components for maintenance purposes. Primary power cables shall incorporate<br />

positive twist-lock connections. Interconnecting cables and connectors<br />

shall be compatible with computer quality signal data transmission.<br />

2.5.3 Antenna System<br />

The antenna system shall utilize vertical polarization antennas,<br />

communication links between transmitters/receivers and antennas, and<br />

matching networks as needed for the proper coverage. The antenna system<br />

shall be either omni-directional or shaped-coverage as selected by the<br />

Contractor based on the topography. The antenna system and cabling shall be<br />

furnished to provide adequate system gain. The antennas shall be capable of<br />

withstanding the environmental conditions of 125 mph wind and 1/2 inch<br />

radial ice without failure. Lightning protection shall comply with NFPA<br />

780. Antenna supporting structures shall comply with TIA-222-G. Apply<br />

silicone sealant at all threaded connections on the antenna mast to<br />

waterproof the joint.<br />

2.5.3.1 Grounding Conductors<br />

Antenna grounding conductors shall be minimum 32-strand, No. 17 AWG copper.<br />

2.5.3.2 Communication Links<br />

Transmission line between the transmitter/receiver and the antenna shall be<br />

50-ohm impedance rated for the transmitter output power. As a minimum,<br />

cable shall exhibit an attenuation not exceeding 1.1 dB per 100 feet at 200<br />

mHz.<br />

2.6 <strong>FIRE</strong> <strong>ALARM</strong> <strong>SYSTEM</strong> PERIPHERAL EQUIPMENT<br />

2.6.1 Repeaters<br />

Repeaters shall be provided where indicated or required to meet system<br />

requirements. The repeater shall receive and transmit on the assigned<br />

frequencies. The receiver and transmitter sections shall conform to the<br />

requirements specified for transceivers. Two-way data transmission shall be<br />

relayed between the base station and remote stations. Repeater shall<br />

utilize a bandpass-type duplexer and one antenna, or multiple-bandpass<br />

cavity filters and multiple antennas. The duplexer or filter cavities shall<br />

isolate the receiver from transmitter spurious noise and prevent receiver<br />

desensitization. The duplexer or filter cavities shall be rated to handle<br />

the output power of the transmitter. Repeater shall be keyed with tone-<br />

SECTION 28 31 33 Page 14


encoded control circuit. A transmitter time-out circuit shall be provided<br />

to prevent system lockup.<br />

2.6.2 Radio Fire Alarm Transmitter Box Location Light<br />

Each indicated transmitter providing publicly accessible actuating functions<br />

shall be provided with a vapor-tight, incandescent type light fixture<br />

constructed of a flame retardant, nonplastic, polycarbonate material with a<br />

threaded ruby globe. The light shall be supported with 1/2 inch galvanized<br />

steel conduit and located approximately 1 foot above the box. The light<br />

shall be provided with an incandescent, 50-watt, 120-volt extended service<br />

lamp. Transmitters which are powered by battery only shall not be equipped<br />

with location lights.<br />

2.6.3 Conduit<br />

Conduit and fittings shall comply with UL 6, UL 1242, and UL 797.<br />

2.6.4 Ground Rods<br />

Ground rods shall be of copper-clad steel conforming to UL 467 zinc-coated<br />

steel conforming to IEEE C135.30 solid stainless steel not less than 3/4<br />

inch in diameter by 10 feet in length.<br />

2.6.5 Power Supply<br />

The operating power for the system shall be single phase taken from the<br />

building electric service as specified in paragraph Power Supply for the<br />

System. Emergency backup power shall be provided by sealed lead-acid type<br />

batteries requiring no additional water. The charging system shall recharge<br />

fully discharged batteries within 12 hours and maintain the batteries in the<br />

fully charged state. The battery shall have the capacity to operate the<br />

system for not less than 72 hours under maximum normal load with the power<br />

supply to the charger disconnected.<br />

2.6.6 Wiring<br />

Wiring shall be in accordance with NFPA 70 and as indicated. Station wiring<br />

shall be color coded.<br />

PART 3<br />

EXECUTION<br />

3.1 EXAMINATION<br />

After becoming familiar with all details of the work, verify all dimensions<br />

in the field, and advise the Contracting Officer of any discrepancy before<br />

performing the work.<br />

3.2 INSTALLATION<br />

Perform installation as shown and in accordance with the manufacturer's<br />

recommendations, unless otherwise specified. Provide all necessary<br />

interconnections, services, and adjustments required for a complete and<br />

operational system. Electrical work shall be in accordance with NFPA 70.<br />

No conduit penetrations are allowed in the top or bottom of transmitter<br />

enclosures. Threaded connections on the antenna mast shall have silicone<br />

seal added for waterproofing the joint.<br />

SECTION 28 31 33 Page 15


3.2.1 Power Supply for the System<br />

Provide a single dedicated branch-circuit connection for supplying power to<br />

the fire alarm system. The backup power supply shall be automatically<br />

energized upon failure of the normal power supply.<br />

3.2.2 Wiring for Systems<br />

Wiring for systems shall be installed in rigid conduit, intermediate<br />

metallic conduit, or electric metallic tubing. The conductors for the fire<br />

alarm system shall not be installed in conduits, junction boxes, or outlet<br />

boxes with conductors of lighting and power systems. The sum of the crosssectional<br />

areas of individual conductors shall not exceed 40 percent of the<br />

interior cross-sectional area of the conduit. Conduit shall comply with<br />

NFPA 70. Provide ample gutter space to accommodate necessary wiring.<br />

Submit wiring diagrams as specified in the Submittals paragraph.<br />

3.3 OVERVOLTAGE AND SURGE PROTECTION<br />

Equipment connected to alternating current circuits shall be protected from<br />

surges in accordance with IEEE C62.41.1, IEEE C62.41.2 and NFPA 70. Cables<br />

and conductors which serve as communications links, except fiber optics,<br />

shall have surge protection circuits installed at each end. Fuses shall not<br />

be used for surge protection.<br />

3.4 GROUNDING<br />

Ground rods shall not protrude more than 6 inches above grade. Noncurrentcarrying<br />

metallic parts associated with radio fire alarm equipment shall<br />

have a maximum resistance to solid "earth" ground not to exceed 25 ohms.<br />

3.5 TRAINING<br />

Provide training courses for operations and maintenance staff. Conduct the<br />

system operation training in the building where the system is installed.<br />

The training period shall consist of 3 training days (8 hours per day) and<br />

shall start after the system is functionally complete but prior to final<br />

acceptance tests. The instructions shall cover all of the items contained in<br />

the operating and maintenance instructions. Additional system training<br />

shall provide the designated government personnel adequate knowledge, tools<br />

and equipment that will be required to diagnose, repair, maintain and expand<br />

functions inherent to the system and shall be conducted on site and/or off<br />

site as necessary to fully qualify the government operations and maintenance<br />

technicians to perform all levels of maintenance, expansions and<br />

modifications to the fire alarm system, hardware, software and components.<br />

This training will include submittal to the government of all proprietary<br />

licenses, software and tools to perform the required tasks. All specialized<br />

equipment and/or training to program, edit existing program, add or delete<br />

devices, etc. shall be provided as part of the fire alarm system.<br />

3.6 TESTING<br />

Notify the Contracting Officer 30 days before the performance and acceptance<br />

tests are to be conducted and submit the test procedures to be used.<br />

Perform the tests in the presence of the Contracting Officer under the<br />

supervision of the fire alarm system manufacturer's qualified<br />

SECTION 28 31 33 Page 16


epresentative. Furnish all instruments and personnel required for the<br />

tests.<br />

a. Coordinate all testing with Public Works, Fire Department, Physical<br />

Security and the Contracting officer. The ring down test proving<br />

battery capacity shall be done the morning of the final acceptance<br />

test. The pre-test form shall be on hand at the time of the acceptance<br />

test. The contractor shall obtain the transmitter number from the JBLM<br />

Emergency Control Center (Building 4101). Forward and reflective power<br />

reading of the transmitter and transmitter zones shall be written<br />

inside the transmitter cabinet. The contractor shall ensure that a set<br />

of Record Drawings are on hand during the final acceptance test.<br />

3.6.1 Performance Testing<br />

Upon completion of the installation, the system shall be subjected to a<br />

complete functional and operational performance test. Test shall determine<br />

that the system is free from grounded, shorted, or open circuits. When all<br />

corrections have been made, the system shall be retested to assure that it<br />

is functional. Copies of performance test reports shall be submitted in<br />

accordance with paragraph SUBMITTALS.<br />

3.6.2 Acceptance Test<br />

The testing shall be in accordance with NFPA 72. The recommended tests in<br />

NFPA 72 shall be considered mandatory and shall verify that all previous<br />

deficiencies have been corrected. The tests shall include the following:<br />

a. Tests to indicate there are no grounded, shorted, or open circuits.<br />

b. Tests of each radio fire alarm transmitter/receiver/transceiver/<br />

repeater.<br />

c. Tests of radio fire alarm monitoring base station for all required<br />

functions.<br />

d. Tests of normal and emergency power supplies.<br />

e. The 72 hour - 15 minute ring down test shall be done the morning of<br />

the final acceptance test. The pre-test form shall be on hand at the<br />

time of the acceptance test. The contractor shall obtain the<br />

transmitter number from the JBLM Emergency Control Center. Forward and<br />

reflective power reading of the transmitter and transmitter zones shall<br />

be written inside the transmitter. The contractor shall ensure a set of<br />

as-built drawings are on hand during the final acceptance test.<br />

-- End of Section --<br />

SECTION 28 31 33 Page 17


JBLM DESIGN STANDARDS<br />

SECTION 28 31 64.00 10 - <strong>FIRE</strong> DETECTION AND <strong>ALARM</strong> <strong>SYSTEM</strong>, ADDRESSABLE<br />

<strong>Design</strong> Requirements<br />

a. Fire alarm panels, transceivers, and other sensitive electrical or electronic equipment<br />

shall be installed in dedicated electrical equipment rooms readily accessible to<br />

maintenance personnel independent of building occupants (i.e., space accessible from<br />

exterior of facility), not in mechanical spaces or other areas subject to excessive<br />

temperature and moisture.<br />

b. To protect control equipment in areas that are not continuously occupied, smoke/heat<br />

detection or a suppression system nozzle shall be provided. Each control unit location to<br />

provide notification of fire at that location. A suppression system nozzle is preferred over<br />

a heat/smoke detector.<br />

c. Smoke detectors shall be of the photo-electric type wherever possible, ionization type<br />

detectors will only be used where alternative detectors are not available or unsuitable for<br />

specific applications. Manufacturers of ionization detectors specified must provide for no<br />

cost disposal of their detectors.<br />

d. Addressable fire alarm panels shall display history of events on the panel display without<br />

additional software/hardware.<br />

e. Notification appliances in individual sleeping rooms of dormitories that sound with the<br />

general alarm shall silence with the general alarm silence function from the fire alarm<br />

panel. When device is mounted externally on brick or exterior surface, a rubber gasket<br />

shall be used (to reduce electrolysis and grounds).<br />

f. Spare parts, manuals for fire alarm system, documentation showing mapping/tree of<br />

devices (showing the polling sequence), and all software/hardware required for<br />

programming/editing shall be turned over to Public Works personnel at the time of<br />

acceptance testing. Spare parts will include 2% or a minimum of 2 each type of device<br />

used in the system (bases, sounder bases, modules, detectors, pull stations, horn-strobes,<br />

magnetic door holders, etc.). For software-based systems, a record copy of the sitespecific<br />

software will be delivered DPW Fire Alarm Technicians after all changes have<br />

been made for acceptance test. NFPA 72 4.5.2.3 (3).<br />

g. When warranty is in effect, the Fire Alarm Contractor shall be required to respond<br />

(physically go to building in Alarm or Trouble), within 48 hours to an <strong>ALARM</strong><br />

CONDITION and 72 hours to a TROUBLE CONDITION.<br />

h. Per AR 420-1 Army unaccompanied personnel housing, hotels, and transient quarters<br />

used for Federal personnel on official travel require single station hard wired smoke<br />

detectors in each guest room. Four or more stories requires fire suppression system.<br />

i. Fire alarm annunciators are not desired as part of the fire alarm system on JBLM. Unless<br />

specifically required by code, do not include annunciators in fire alarm system designs.<br />

Notes to <strong>Design</strong>ers on Drawing Content<br />

a. All as-builts shall be required to show the sequence of operation table, details of the<br />

different devices and the external wiring connections, exact run of conduit, quantity of<br />

SECTION 28 31 64 Page 1


wires, wire color code, location of every initiating device, signaling device, module, and<br />

any major junction boxes or power supplies. The plans will also show Loop number and<br />

the address of each device, or module, if system is addressable.<br />

b. A copy of the record drawings (as-builts) shall be delivered to the DPW Fire Alarm<br />

Techs at the initial fire alarm acceptance test.<br />

SECTION 28 31 64.00 10<br />

<strong>FIRE</strong> DETECTION AND <strong>ALARM</strong> <strong>SYSTEM</strong>, ADDRESSABLE<br />

11/08<br />

PART 1<br />

GENERAL<br />

1.1 REFERENCES<br />

The publications listed below form a part of this specification to the<br />

extent referenced. The publications are referred to within the text by the<br />

basic designation only. Criteria and requirements appearing in bold apply<br />

to work on JBLM only.<br />

ACOUSTICAL SOCIETY OF AMERICA (ASA)<br />

ASA S3.41<br />

(1990; R 2001) Audible Emergency Evacuation<br />

Signal (ASA 96)<br />

FM GLOBAL (FM)<br />

FM P7825a<br />

(2005) Approval Guide Fire Protection<br />

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)<br />

IEEE C62.41.1<br />

IEEE C62.41.2<br />

(2002) IEEE Guide on the Surges Environment<br />

in Low-Voltage (1000 V and Less) AC Power<br />

Circuits<br />

(2002) IEEE Recommended Practice on<br />

Characterization of Surges in Low-Voltage<br />

(1000 V and Less) AC Power Circuits<br />

NATIONAL <strong>FIRE</strong> PROTECTION ASSOCIATION (NFPA)<br />

NFPA 1221<br />

(2006; Errata 2006) Installation, Maintenance<br />

and Use of Emergency Services Communications<br />

Systems<br />

NFPA 70 (2007; AMD 1 2008) National Electrical Code -<br />

2008 Edition<br />

NFPA 72<br />

NFPA 90A<br />

(2006) National Fire Alarm Code<br />

(2008) Standard for the Installation of Air<br />

Conditioning and Ventilating Systems<br />

SECTION 28 31 64 Page 2


U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)<br />

47 CFR 15 Radio Frequency Devices<br />

UNDERWRITERS LABORATORIES (UL)<br />

UL 1242<br />

UL 1971<br />

UL 228<br />

UL 268<br />

UL 268A<br />

UL 38<br />

UL 464<br />

UL 521<br />

UL 6<br />

UL 632<br />

UL 797<br />

UL 864<br />

(2006; Rev thru Jul 2007) Standard for<br />

Electrical Intermediate Metal Conduit --<br />

Steel<br />

(2002; Rev thru May 2006) Signaling Devices<br />

for the Hearing Impaired<br />

(2006) Door Closers-Holders, With or Without<br />

Integral Smoke Detectors<br />

(2006) Standard for Smoke Detectors for Fire<br />

Alarm Signaling Systems<br />

(2008) Smoke Detectors for Duct Application<br />

(1999; Rev thru Feb 2005) Standard for<br />

Signaling Boxes for Fire Alarm Systems<br />

(2003; Rev thru Feb 2008) Standard for<br />

Audible Signal Appliances<br />

(1999; Rev thru Jul 2005) Heat Detectors for<br />

Fire Protective Signaling Systems<br />

(2007) Standard for Electrical Rigid Metal<br />

Conduit-Steel<br />

(2000) Electrically-Actuated Transmitters<br />

(2007) Standard for Electrical Metallic<br />

Tubing -- Steel<br />

(2003; Rev thru May 2007) Control Units and<br />

Accessories for Fire Alarm Systems<br />

1.2 <strong>SYSTEM</strong> DESCRIPTION<br />

The fire detection and alarm system and the central reporting system shall<br />

be a complete, supervised fire alarm reporting system configured in<br />

accordance with NFPA 72; exceptions are acceptable as directed by the<br />

Contracting Officer. Fire alarm systems with 4 or more devices per alarm<br />

initiating device zone shall be of the addressable type, except in troop<br />

housing where all systems shall be the addressable type. Furnish equipment<br />

compatible and UL listed, FM approved, or approved or listed by a nationally<br />

recognized testing laboratory in accordance with the applicable NFPA<br />

standards. All locks shall be keyed alike with 211 keys. Provide four keys<br />

for the system. On JBLM, all locks required for fire alarm system<br />

components shall use 211 keys (panels, subpanels, pull stations, excluding<br />

Monaco BTX). Furnish tags with stamped identification number for keys and<br />

locks.<br />

SECTION 28 31 64 Page 3


1.2.1 Operational Features<br />

The JBLM Fire Alarm Maintenance Shop prefers the following characteristics<br />

be designed into fire alarm systems:<br />

a. All devices in new addressable fire alarm systems to be rotary<br />

decade switch addressable.<br />

b. All new fire alarm systems to have Windows based programming.<br />

c. All new fire alarm systems to have drift compensation and<br />

maintenance alert. The maintenance alert shall be included as a zone in<br />

the fire alarm transmitter.<br />

1.2.2 Operation<br />

Activate the system into the alarm mode by actuation of any alarm initiating<br />

device. The system will remain in the alarm mode until the initiating<br />

device is reset and the fire alarm control panel is reset and restored to<br />

normal. Alarm initiating devices shall be connected to Class A initiating<br />

device circuits (IDC), , to class A signal line circuits (SLC), Style 7 , in<br />

accordance with NFPA 72. Connect alarm notification appliances to Class A<br />

notification appliance circuits (NAC), Style Z in accordance with NFPA 72.<br />

Provide a looped conduit system so that if the conduit and all conductors<br />

within are severed at any point, all IDC, NAC and SLC will remain<br />

functional. The conduit loop requirement is not applicable to the signal<br />

transmission link from the local panels (at the protected premises) to the<br />

Supervising Station (fire station, fire alarm central communication center).<br />

Textual, audible, and visual appliances and systems shall comply with NFPA<br />

72. Fire alarm system components requiring power, except for the control<br />

panel power supply, shall operate on 24 Volts dc. Addressable system shall<br />

be microcomputer (microprocessor or microcontroller) based with a minimum<br />

word size of eight bits and shall provide the following features:<br />

a. Sufficient memory to perform as specified and as shown for<br />

addressable system.<br />

b. Individual identity of each addressable device for the following<br />

conditions: alarm; trouble; open; short; and appliances missing/failed<br />

remote detector - sensitivity adjustment from the panel for smoke<br />

detectors.<br />

c. Capability of each addressable device being individually disabled<br />

or enabled from the panel.<br />

d. Size each SLC to provide 40 percent addressable expansion without<br />

hardware modifications to the panel.<br />

1.2.3 Operational Features<br />

The system shall have the following operating features:<br />

a. Monitor electrical supervision of SLC and NAC. Smoke detectors<br />

shall have combined alarm initiating and power circuits.<br />

SECTION 28 31 64 Page 4


. Monitor electrical supervision of the primary power (ac) supply,<br />

battery voltage, placement of alarm zone module (card, PC board) within<br />

the control panel, and transmitter tripping circuit integrity.<br />

c. A trouble buzzer and trouble LED/LCD (light emitting diode/liquid<br />

crystal diode) to activate upon a single break, open, or ground fault<br />

condition which prevents the required normal operation of the system.<br />

The trouble signal shall also operate upon loss of primary power (ac)<br />

supply, low battery voltage, removal of alarm zone module (card, PC<br />

board), and disconnection of the circuit used for transmitting alarm<br />

signals off-premises. A trouble alarm silence switch shall be provided<br />

which will silence the trouble buzzer, but will not extinguish the<br />

trouble indicator LED/LCD. Subsequent trouble and supervisory alarms<br />

shall sound the trouble signal until silenced. After the system<br />

returns to normal operating conditions, the trouble buzzer shall again<br />

sound until the silencing switch returns to normal position, unless<br />

automatic trouble reset is provided.<br />

d. A one person test mode. Activating an initiating device in this<br />

mode will activate an alarm for a short period of time, then<br />

automatically reset the alarm, without activating the transmitter<br />

during the entire process.<br />

e. A transmitter disconnect switch to allow testing and maintenance of<br />

the system without activating the transmitter but providing a trouble<br />

signal when disconnected and a restoration signal when reconnected.<br />

f. Evacuation alarm silencing switch which, when activated, will<br />

silence alarm devices, but will not affect the zone indicating LED/LCD<br />

nor the operation of the transmitter. This switch shall be over-ridden<br />

upon activation of a subsequent alarm from an unalarmed device and the<br />

NAC devices will be activated.<br />

g. Electrical supervision for circuits used for supervisory signal<br />

services (i.e., sprinkler systems, valves, etc.). Supervision shall<br />

detect any open, short, or ground.<br />

h. Confirmation or verification of all smoke detectors. The control<br />

panel shall interrupt the transmission of an alarm signal to the system<br />

control panel for a factory preset period. This interruption period<br />

shall be adjustable from 1 to 60 seconds and be factory set at 20<br />

seconds. Immediately following the interruption period, a confirmation<br />

period shall be in effect during which time an alarm signal, if<br />

present, will be sent immediately to the control panel. Fire alarm<br />

devices other than smoke detectors shall be programmed without<br />

confirmation or verification.<br />

i. The fire alarm control panel shall provide supervised addressable<br />

relays for HVAC shutdown. An override at the HVAC panel shall not be<br />

provided.<br />

j. Provide one person test mode - Activating an initiating device in<br />

this mode will activate an alarm for a short period of time, then<br />

automatically reset the alarm, without activating the transmitter<br />

during the entire process.<br />

SECTION 28 31 64 Page 5


k. The fire alarm control panel shall provide the required monitoring<br />

and supervised control outputs needed to accomplish elevator recall.<br />

l. The fire alarm control panel shall monitor and control the fire<br />

sprinkler system, or other fire protection extinguishing system.<br />

m. The control panel and field panels shall be software reprogrammable<br />

to enable expansion or modification of the system without replacement<br />

of hardware or firmware. Examples of required changes are: adding or<br />

deleting devices or zones; changing system responses to particular<br />

input signals; programming certain input signals to activate auxiliary<br />

devices.<br />

n. Zones shall be arranged as indicated on the contract drawings. The<br />

following initiating events or troubles shall require their own<br />

transmitted zone: deluge sprinkler system, water flow (sprinkler), low<br />

air pressure (dry sprinkler), separate buildings or quads, FACP common<br />

trouble.<br />

o. The JBLM Fire Alarm Maintenance Shop prefers the following<br />

characteristics be designed into fire alarm systems for the purpose of<br />

keeping maintenance simple:<br />

1. All devices in new addressable fire alarm systems to be rotary<br />

decade switch addressable.<br />

2. All new fire alarm systems to have windows based programming.<br />

3. All new fire alarm systems to have drift compensation and<br />

maintenance alert. The maintenance alert shall be included as a<br />

zone in the fire alarm transmitter.<br />

1.2.4 Alarm Functions<br />

An alarm condition on a circuit shall automatically initiate the following<br />

functions:<br />

a. Transmission of a signal over the station fire reporting system.<br />

The signal shall be common for all zones.<br />

b. Visual indications of the alarmed devices on the fire alarm control<br />

panel display and on the remote audible/visual display.<br />

c. Continuous sounding or operation of alarm notification appliances<br />

throughout the building as required by ASA S3.41.<br />

d. Closure of doors held open by electromagnetic devices.<br />

e. Operation of the smoke control system.<br />

f. Deactivation of the air handling units serving the alarmed area.<br />

g. Shutdown of power to the data processing equipment in the alarmed<br />

area.<br />

h. Automatic discharge of the designated fire suppression systems. A<br />

15 second maximum delay shall be provided for the deluge system, a 30<br />

SECTION 28 31 64 Page 6


second delay for the wet pipe system with the exception of aircraft<br />

hangars in which two alarm devices should be required to trigger before<br />

a deluge system is activated.It is not desirable in every situation to<br />

have the alarm system automatically discharge the fire suppression<br />

system. For example, in aircraft hangars, two heat/smoke detectors or a<br />

single manual initiating device are required to trigger before the<br />

deluge system is deployed.<br />

i. Smoke detectors in sleeping rooms shall be fully addressable and<br />

self-resetting (no manual reset required at the fire alarm panel) with<br />

a sounder base operated from the fire alarm controls panel and having<br />

reverse polarity sounding capability for local and general alarms.<br />

Activation of the sleeping room smoke detector will only set off its<br />

sounder base for a local audible alarm. A general alarm will also<br />

activate the sounder base. Upon an alarm condition, detector shall be<br />

non-latching, shall not require reset at the fire alarm panel after a<br />

local alarm, and shall not cause the transmitter to send an alarm or<br />

trouble signal.<br />

1.2.5 Primary Power<br />

Operating power shall be provided as required by paragraph Power Supply for<br />

the System. Transfer from normal to emergency power or restoration from<br />

emergency to normal power shall be fully automatic and not cause<br />

transmission of a false alarm. Loss of ac power shall not prevent<br />

transmission of a signal via the fire reporting system upon operation of any<br />

initiating circuit.<br />

1.2.6 Battery Backup Power<br />

Battery backup power shall be through use of rechargeable, sealed-type<br />

storage batteries and battery charger.<br />

1.2.7 Interface With Existing Fire Alarm Equipment (where this occurs)<br />

The equipment specified herein shall operate as an extension to an existing<br />

configuration. The new equipment shall be connected to existing monitoring<br />

equipment as indicated. Existing equipment shall be expanded, modified, or<br />

supplemented as necessary to extend the existing control and/or monitoring<br />

functions to the new points or zones. New components shall be capable of<br />

merging with the existing configuration without degrading the performance of<br />

either system. The scope of the acceptance tests of paragraph Testing shall<br />

include aspects of operation that involve combined use of both new and<br />

existing portions of the final configuration.<br />

1.2.8 Interface With other Equipment<br />

Interfacing components shall be furnished as required to connect to<br />

subsystems or devices which interact with the fire alarm system, such as<br />

supervisory or alarm contacts in suppression systems, operating interfaces<br />

for smoke control systems, door releases, etc.<br />

1.3 SUBMITTALS<br />

Government approval is required for submittals with a "G" designation;<br />

submittals not having a "G" designation are for information only. When<br />

used, a designation following the "G" designation identifies the office that<br />

SECTION 28 31 64 Page 7


will review the submittal for the Government. Submit the following in<br />

accordance with Section 01 33 00 SUBMITTAL PROCEDURES:<br />

SD-02 Shop Drawings<br />

Detail Drawings; G<br />

Two complete hard copies and one electronic copy in Adobe Acrobat<br />

(.pdf) and AutoCAD (.dwg) format on CD or DVD of detail drawings,<br />

prepared and signed by a Registered Professional Engineer who meets<br />

the qualifications identified in UFC 3-600-01.<br />

SD-03 Product Data<br />

Storage Batteries; G<br />

Substantiating battery calculations for supervisory and alarm<br />

power requirements. Ampere-hour requirements for each system<br />

component and each panel component, and the battery recharging<br />

period shall be included.<br />

Low Battery Voltage; G<br />

Voltage drop calculations for notification appliance circuits to<br />

indicate that sufficient voltage is available for proper appliance<br />

operation.<br />

Special Tools and Spare Parts; G<br />

Spare parts data for each different item of material and<br />

equipment specified, not later than 3 months prior to the date of<br />

beneficial occupancy. Data shall include a complete list of parts<br />

and supplies with the current unit prices and source of supply and<br />

a list of the parts recommended by the manufacturer to be replaced<br />

after 1 year of service.<br />

Technical Data and Computer Software; G<br />

Technical data which relates to computer software.<br />

Training<br />

Lesson plans, operating instructions, maintenance procedures, and<br />

training data, furnished in manual format, for the training<br />

courses. The operations training shall familiarize designated<br />

government personnel with proper operation of the fire alarm<br />

system. The maintenance training course shall provide the<br />

designated government personnel adequate knowledge required to<br />

diagnose, repair, maintain, and expand functions inherent to the<br />

system.<br />

Testing<br />

Detailed test procedures, prepared and signed by a Registered<br />

Professional Engineer or a NICET Level 3 Fire Alarm Technician, for<br />

the fire detection and alarm system 60 days prior to performing<br />

system tests.<br />

SECTION 28 31 64 Page 8


SD-06 Test Reports<br />

Testing; G<br />

Test reports, in booklet form, showing field tests performed to<br />

prove compliance with the specified performance criteria, upon<br />

completion and testing of the installed system. Each test report<br />

shall document readings, test results and indicate the final<br />

position of controls. Include the NFPA 72 Certificate of<br />

Completion and NFPA 72 Inspection and Testing Form, with the<br />

appropriate test reports.<br />

SD-07 Certificates<br />

Equipment<br />

Certified copies of current approvals or listings issued by an<br />

independent test lab if not listed by UL, FM or other nationally<br />

recognized testing laboratory, showing compliance with specified<br />

NFPA standards.<br />

Qualifications<br />

Proof of qualifications for required personnel. The installer<br />

shall submit proof of experience for the Professional Engineer,<br />

fire alarm technician, and the installing company. Proof of<br />

qualifications for required personnel per UFC 3-600-01.<br />

Certificate of Fitness; G<br />

Provide Certificate of Fitness for any individual, business, or<br />

firm engaged in the inspecting, designing, testing, maintaining or<br />

servicing of fire and life safety systems.<br />

SD-10 Operation and Maintenance Data<br />

Operating and Maintenance Instructions; G<br />

One set of as-built drawings, two complete hard copies and one<br />

electronic copy in Adobe Acrobat (.pdf) format on CD or DVD of<br />

theoperating manual outlining step-by-step procedures required for<br />

system startup, operation, and shutdown. The manual shall include<br />

the manufacturer's name, model number, service manual, parts list,<br />

and complete description of equipment and their basic operating<br />

features. Six copies of maintenance manual listing routine<br />

maintenance procedures, possible breakdowns and repairs, and<br />

troubleshooting guide. The manuals shall include conduit layout,<br />

equipment layout and simplified wiring, and control diagrams of the<br />

system as installed. The manuals shall include complete procedures<br />

for system revision and expansion, detailing both equipment and<br />

software requirements. Original and backup copies of all software<br />

delivered for this project shall be provided, on each type of media<br />

utilized. Manuals shall be approved prior to training. Provide two<br />

copies of the fire alarm system database and all software/hardware<br />

required for programming/editing to the Department of Public Works<br />

at the time of acceptance testing.<br />

SECTION 28 31 64 Page 9


As-Built Drawings; G<br />

As-built drawings shall show the sequence of operation table,<br />

details of the different devices and the external wiring<br />

connections, exact run of conduit, quanity of wires, wire color<br />

code, location of every initiating device, signaling device,<br />

module, and any major junction boxes or power supplies. Plans shall<br />

show Loop numbers and the address of each device or module.<br />

1.4 QUALITY ASSURANCE<br />

1.4.1 Qualifications<br />

1.4.2 Engineer and Technician<br />

a. Qualifications per UFC 3-600-01. Any individual, business, or firm<br />

engaged in the inspecting, testing, maintaining, designing or servicing<br />

of fire and life safety systems and equipment shall be certified to<br />

perform these activities in accordance with Appendix G of FL REG 420-<br />

30. A certificate of fitness can be obtained by completing the<br />

Employee Application for Certification of Fitness with supporting<br />

credentials to the JBLM Fire Prevention branch. Allow five working<br />

days for processing of application for Certificate of Fitness. Contact<br />

the JBLM Fire Prevention Branch at 253-966-7155 or 253-966-1764 for<br />

additional information. Submit a copy of certificate of fitness to the<br />

Contracting Officer or the Contracting Officer's Representative prior<br />

to starting work on life safety system and equipment.<br />

1.4.3 Installer<br />

The installing Contractor shall provide the following: NICET Fire Alarm<br />

Technicians to perform the installation of the system. A NICET Level 3 Fire<br />

Alarm Technician shall supervise the installation of the fire alarm system.<br />

NICET Level 2 or higher Fire Alarm Technician shall install and terminate<br />

fire alarm devices, cabinets and panels. An electrician or NICET Level 1<br />

Fire Alarm Technician shall install conduit for the fire alarm system. The<br />

Fire Alarm technicians installing the equipment shall be factory trained in<br />

the installation, adjustment, testing, and operation of the equipment<br />

specified herein and on the drawings. Any individual, business, or firm<br />

engaged in the inspecting, testing, maintaining, designing or servicing of<br />

fire and life safety systems and equipment shall be certified to perform<br />

these activities in accordance with Appendix G of FL REG 420-30. A<br />

certificate of fitness can be obtained by completing the Employee<br />

Application for Certification of Fitness with supporting credentials to the<br />

JBLM Fire Prevention branch. Allow five working days for processing of<br />

application for Certificate of Fitness. Contact the JBLM Fire Prevention<br />

Branch at 253-966-7155 or 253-966-1764 for additional information. Submit a<br />

copy of certificate of fitness to the Contracting Officer or the Contracting<br />

Officer's Representative prior to starting work on life safety system and<br />

equipment.<br />

1.4.4 Fire Protection Engineer<br />

Qualifications per UFC 3-600-01. Any individual, business, or firm engaged<br />

in the inspecting, testing, maintaining, designing or servicing of fire and<br />

life safety systems and equipment shall be certified to perform these<br />

SECTION 28 31 64 Page 10


activities in accordance with Appendix G of FL REG 420-30. A certificate of<br />

fitness can be obtained by completing the Employee Application for<br />

Certification of Fitness with supporting credentials to the JBLM Fire<br />

Prevention branch. Allow five working days for processing of application<br />

for Certificate of Fitness. Contact the JBLM Fire Prevention Branch at 253-<br />

966-7155 or 253-966-1764 for additional information. Submit a copy of<br />

certificate of fitness to the Contracting Officer or the Contracting<br />

Officer's Representative prior to starting work on life safety system and<br />

equipment.<br />

1.4.5 Detail Drawings<br />

Submit detail drawings consisting of a complete list of equipment and<br />

material, including manufacturer's descriptive and technical literature,<br />

catalog cuts, and installation instructions. Note that the contract<br />

drawings show layouts based on typical detectors. Check the layout based on<br />

the actual detectors to be installed and make any necessary revisions in the<br />

detail drawings. The detail drawings shall also contain complete wiring and<br />

schematic diagrams for the equipment furnished, equipment layout, and any<br />

other details required to demonstrate that the system has been coordinated<br />

and will properly function as a unit. Detailed point-to-point wiring<br />

diagram shall be prepared and signed by a Registered Professional Engineer<br />

or a NICET Level 3 Fire Alarm Technician showing points of connection.<br />

Diagram shall include connections between system devices, appliances,<br />

control panels, supervised devices, and equipment that is activated or<br />

controlled by the panel. As-builts shall show the sequence of operation<br />

table, details of the different devices and the external wiring connections,<br />

exact run of conduit, quanity of wires, wire color code, location of every<br />

initiating device, signaling device, module, and any major junction boxes or<br />

power supplies. Plans shall show Loop numbers and the address of each device<br />

or module if the system is addressable.<br />

1.5 TECHNICAL DATA AND COMPUTER SOFTWARE<br />

Technical data and computer software (meaning technical data which relates<br />

to computer software) which is specifically identified in this project, and<br />

which may be defined/required in other specifications, shall be delivered,<br />

strictly in accordance with the CONTRACT CLAUSES, and in accordance with the<br />

Contract Data Requirements List, DD Form 1423. For software based systems,<br />

a record copy of the site specific software will be delivered to DPW fire<br />

alarm technicians after all changes have been made for acceptance test.<br />

Data delivered shall be identified by reference to the particular<br />

specification paragraph against which it is furnished. Data to be submitted<br />

shall include complete system, equipment, and software descriptions.<br />

Descriptions shall show how the equipment will operate as a system to meet<br />

the performance requirements of this contract. The data package shall also<br />

include the following:<br />

a. Identification of programmable portions of system equipment and<br />

capabilities.<br />

b. Description of system revision and expansion capabilities and<br />

methods of implementation detailing both equipment and software<br />

requirements.<br />

c. Provision of operational software data on all modes of programmable<br />

portions of the fire alarm and detection system.<br />

SECTION 28 31 64 Page 11


d. Description of Fire Alarm Control Panel equipment operation.<br />

e. Description of auxiliary and remote equipment operations.<br />

f. Library of application software.<br />

g. Operation and maintenance manuals as specified in SD-19 of the<br />

Submittals paragraph.<br />

1.6 DELIVERY, STORAGE, AND HANDLING<br />

Protect equipment delivered and placed in storage from the weather, humidity<br />

and temperature variation, dirt, dust, and any other contaminants.<br />

1.7 SPECIAL TOOLS AND SPARE PARTS<br />

Furnish to the Contracting Officer software (including proprietary software,<br />

codes, and passwords), connecting cables, proprietary equipment and two<br />

spare fuses of each type and size required, necessary for the maintenance,<br />

testing, and reprogramming of the equipment. Two percent of the total<br />

number of each different type of base, sounder base, module, detector, pull<br />

station, hornstrobe, magnetic door holders, etc., but no less than two each,<br />

shall be furnished. Mount spare fuses in the fire alarm panel.<br />

PART 2<br />

PRODUCTS<br />

2.1 STANDARD PRODUCTS<br />

Provide material and equipment which are the standard products of a<br />

manufacturer regularly engaged in the manufacture of the products for at<br />

least 2 years prior to bid opening. Equipment shall be supported by a<br />

service organization that can provide service within 24 hours of<br />

notification. Preferred Materials/Manufacturers: Silent Knight, EST,<br />

Simplex, Notifier. Fire alarm transmitters shall be equal in all aspects to<br />

Monaco transmitter.<br />

2.2 NAMEPLATES<br />

Major components of equipment shall have the manufacturer's name, address,<br />

type or style, voltage and current rating, and catalog number on a<br />

noncorrosive and nonheat-sensitive plate which is securely attached to the<br />

equipment.<br />

2.3 CONTROL PANEL<br />

Control Panel shall comply with the applicable requirements of UL 864.<br />

Panel shall be modular, installed in a steel cabinet with hinged door and<br />

cylinder lock. Control panel shall be a clean, uncluttered, and orderly<br />

assembled panel containing components and equipment required to provide the<br />

specified operating and supervisory functions of the system. The panel<br />

shall have prominent rigid plastic, phenolic or metal identification plates<br />

for LED/LCDs, zones, SLC, controls, meters, fuses, and switches.<br />

a. Nameplates for fuses shall also include ampere rating. The LED/LCD<br />

displays shall be located on the exterior of the cabinet door or be<br />

visible through the cabinet door. Control panel switches shall be<br />

SECTION 28 31 64 Page 12


within the locked cabinet. A suitable means (single operation) shall<br />

be provided for testing the control panel visual indicating devices<br />

(meters or LEDs/LCDs). Meters and LEDs shall be plainly visible when<br />

the cabinet door is closed. Signals and LEDs/LCDs shall be provided to<br />

indicate by zone any alarm, supervisory or trouble condition on the<br />

system.<br />

b. Each IDC shall be powered and supervised so that a signal on one<br />

zone does not prevent the receipt of signals from other devices. Loss<br />

of power, including batteries, shall not require the manual reloading<br />

of a program. Upon restoration of power, startup shall be automatic,<br />

and shall not require any manual operation. The loss of primary power<br />

or the sequence of applying primary or emergency power shall not affect<br />

the transmission of alarm, supervisory or trouble signals.<br />

c. Visual annunciation shall be provided for LED/LCD visual display as<br />

an integral part of the control panel and shall identify with a word<br />

description and id number each device. Cabinets shall be provided with<br />

ample gutter space to allow proper clearance between the cabinet and<br />

live parts of the panel equipment. If more than one modular unit is<br />

required to form a control panel, the units shall be installed in a<br />

single cabinet large enough to accommodate units. Cabinets shall be<br />

painted red.<br />

2.3.1 Remote System Audible/Visual Display<br />

Audible appliance shall have a minimum sound level output rating of 85 dBA<br />

at 10 feet and operate in conjunction with the panel integral display. The<br />

audible device shall be silenced by a system silence switch on the remote<br />

system. The audible device shall be silenced by the system silence switch<br />

located at the remote location, but shall not extinguish the visual<br />

indication. The remote LED/LCD visual display shall provide identification,<br />

consisting of the word description and id number for each device as<br />

displayed on the control panel. A rigid plastic, phenolic or metal<br />

identification sign which reads "Fire Alarm System Remote Display" shall be<br />

provided at the remote audible/visual display. The remote visual appliance<br />

located with the audible appliance shall not be extinguished until the<br />

trouble or alarm has been cleared.<br />

2.3.2 Circuit Connections<br />

Connect circuit conductors entering or leaving the panel to screw-type<br />

terminals with each conductor and terminal marked for identification.<br />

2.3.3 System Expansion and Modification Capabilities<br />

Provide as part of this contract, any equipment, software, and training<br />

needed by Public Works Fire Alarm Technicians to implement future changes to<br />

the fire alarm system.<br />

2.3.4 Addressable Control Module<br />

The control module shall be capable of operating as a relay (dry contact<br />

form C) for interfacing the control panel with other systems, and to control<br />

door holders or initiate elevator fire service. The module shall be UL<br />

listed as compatible with the control panel. The indicating device or the<br />

external load being controlled shall be configured as a Style Y notification<br />

SECTION 28 31 64 Page 13


appliance circuits. The system shall be capable of supervising, audible,<br />

visual and dry contact circuits. The control module shall have both an<br />

input and output address. The supervision shall detect a short on the<br />

supervised circuit and shall prevent power from being applied to the<br />

circuit. The control model shall provide address setting means compatible<br />

with the control panel's SLC supervision and store an internal identifying<br />

code. The control module shall contain an integral LED that flashes each<br />

time the control module is polled. Existing fire alarm system notification<br />

appliance circuits shall be connected to a single module to power and<br />

supervise the circuit.<br />

2.3.5 Addressable Initiating Device Circuits Module<br />

Configure the initiating device being monitored as a Style D initiating<br />

device circuits. The system shall be capable of defining any module as an<br />

alarm module and report alarm trouble, loss of polling, or as a supervisory<br />

module, and reporting supervisory short, supervisory open or loss of<br />

polling. The module shall be UL listed as compatible with the control<br />

panel. The monitor module shall provide address setting means compatible<br />

with the control panel's SLC supervision and store an internal identifying<br />

code. Monitor module shall contain an integral LED that flashes each time<br />

the monitor module is polled. Pull stations with a monitor module in a<br />

common backbox are not required to have an LED. Existing fire alarm system<br />

initiating device circuits shall be connected to a single module to power<br />

and supervise the circuit.<br />

2.4 STORAGE BATTERIES<br />

Provide storage batteries which are 24 Vdc sealed, lead-acid type requiring<br />

no additional water with ample capacity, with primary power disconnected, to<br />

operate the fire alarm system for a period of 72 hours. Following this<br />

period of battery operation, the batteries shall have ample capacity to<br />

operate all components of the system, including all alarm signaling devices<br />

in the total alarm mode for a minimum period of 15 minutes. Locate<br />

batteries at the bottom of the panel or in a separate battery cabinet.<br />

Provide batteries with overcurrent protection in accordance with NFPA 72.<br />

Separate battery cabinets shall have a lockable, hinged cover similar to the<br />

fire alarm panel. The lock shall be keyed the same as the fire alarm<br />

control panel. Paint the cabinets to match the fire alarm control panel.<br />

2.5 BATTERY CHARGER<br />

Battery charger shall be completely automatic, 24 Vdc with high/low charging<br />

rate, capable of restoring the batteries from full discharge (18 Volts dc)<br />

to full charge within 48 hours. A pilot light indicating when batteries are<br />

manually placed on a high rate of charge shall be provided as part of the<br />

unit assembly, if a high rate switch is provided. Locate charger in control<br />

panel cabinet or in a separate battery cabinet.<br />

2.6 ADDRESSABLE MANUAL <strong>FIRE</strong> <strong>ALARM</strong> STATIONS<br />

Addressable manual fire alarm stations shall conform to the applicable<br />

requirements of UL 38. Manual stations shall be connected into signal line<br />

circuits. Stations shall be installed on surface, semi-flush or flush<br />

mounted outlet boxes as stated in the Delivery or Task Order. Manual<br />

stations shall be mounted at 54 inches. Stations shall be double action<br />

type. Stations shall be finished in red, with raised letter operating<br />

SECTION 28 31 64 Page 14


instructions of contrasting color. Stations requiring the breaking of glass<br />

or plastic panels for operation are not acceptable. Stations employing<br />

glass rods are not acceptable. The use of a 211 key shall be required to<br />

reset the station. Gravity or mercury switches are not acceptable.<br />

Switches and contacts shall be rated for the voltage and current upon which<br />

they operate. Addressable pull stations shall be capable of being field<br />

programmed, shall latch upon operation and remain latched until manually<br />

reset. Stations shall have a separate screw terminal for each conductor.<br />

Surface mounted boxes shall be matched and painted the same color as the<br />

fire alarm manual stations.<br />

2.7 <strong>FIRE</strong> DETECTING DEVICES<br />

Fire detecting devices shall comply with the applicable requirements of NFPA<br />

72, NFPA 90A, UL 268, UL 268A, and UL 521. The detectors shall be provided<br />

as indicated. Provide smoke/heat detection or fire suppression nozzle to<br />

protect control equipment per NFPA 72; 4.4.5 in areas that are not<br />

continuously occupied. Fire suppression nozzle is preferred to smoke/heat<br />

detector. Detector base shall have screw terminals for making connections.<br />

No solder connections will be allowed. Detectors located in concealed<br />

locations (above ceiling, raised floors, etc.) shall have a remote visible<br />

indicator LED/LCD. Addressable fire detecting devices, except flame<br />

detectors, shall be dynamically supervised and uniquely identified in the<br />

control panel. All fire alarm initiating devices shall be individually<br />

addressable, except where indicated. Installed devices shall conform to<br />

NFPA 70 hazard classification of the area where devices are to be installed.<br />

2.7.1 Heat Detectors<br />

<strong>Design</strong> heat detectors for detection of fire by fixed temperature,<br />

combination fixed temperature and rate-of-rise principle as stated in the<br />

Delivery or Task Order. Heat detector spacing shall be rated in accordance<br />

with UL 521. Detectors located in areas subject to moisture, exterior<br />

atmospheric conditions, or hazardous locations as defined by NFPA 70, shall<br />

be types approved for such locations. Heat detectors located in attic<br />

spaces or similar concealed spaces below the roof shall be intermediate<br />

temperature rated.<br />

2.7.1.1 Combination Fixed-Temperature and Rate-of-Rise Detectors<br />

Detectors shall be designed for outlet box mounting and supported<br />

independently of wiring connections. Contacts shall be self-resetting after<br />

response to rate-of-rise principle. Under fixed temperature actuation, the<br />

detector shall have a permanent external indication which is readily<br />

visible. Detector units located in boiler rooms, showers, or other areas<br />

subject to abnormal temperature changes shall operate on fixed temperature<br />

principle only. The UL 521 test rating for the fixed temperature portion<br />

shall be 135 degrees F or as shown. The UL 521 test rating for the Rate-of-<br />

Rise detectors shall be rated for 50 by 50 ft.<br />

2.7.1.2 Rate Compensating Detectors<br />

Detector mounting type shall be as stated in the Delivery or Task Order,<br />

with outlet box supported independently of wiring connections. Detectors<br />

shall be hermetically sealed and automatically resetting. Rate Compensated<br />

detectors shall be rated for 50 by 50 ft.<br />

SECTION 28 31 64 Page 15


2.7.1.3 Fixed Temperature Detectors<br />

Detectors shall be designed for outlet box mounting and supported<br />

independently of wiring connections. Detectors shall be designed to detect<br />

high heat. The detectors shall have a specific temperature setting of 135<br />

degrees F or as shown. The UL 521 test rating for the fixed temperature<br />

detectors shall be rated for 15 by 15 ft.<br />

2.7.2 Smoke Detectors<br />

<strong>Design</strong> smoke detectors for detection of abnormal smoke densities. Smoke<br />

detectors shall be ionization, photoelectric or projected beam type as<br />

stated in the Delivery or Task Order. Detectors shall contain a visible<br />

indicator LED/LCD that shows when the unit is in alarm condition. Detectors<br />

shall not be adversely affected by vibration or pressure. Detectors shall<br />

be the plug-in type in which the detector base contains terminals for making<br />

wiring connections. Detectors that are to be installed in concealed (above<br />

false ceilings, etc.) locations shall be provided with a remote indicator<br />

LED/LCD suitable for mounting in a finished, visible location.<br />

2.7.2.1 Ionization Detectors<br />

Ionization detectors with a dual chamber shall be responsive to both<br />

invisible and visible particles of combustion. One chamber shall be a<br />

reference chamber and the second a sampling chamber. Detectors containing<br />

radium shall not be provided. Detectors shall not cause an alarm condition<br />

due to anticipated fluctuations in relative humidity. The sensitivity of<br />

the detector shall be field adjustable to compensate for operating<br />

conditions. Detector shall require no replacement or readjustment to<br />

restore it to normal operation after an alarm condition. Each detector<br />

shall be capable of withstanding ambient air velocity up to 300 fpm in<br />

accordance with UL 268. Addressable smoke detectors shall be capable of<br />

having the sensitivity being remotely adjusted by the control panel.<br />

Manufacturers of ionization detectors shall provide for no cost disposal of<br />

their detectors.<br />

2.7.2.2 Photoelectric Detectors<br />

Detectors shall operate on a light scattering concept using an LED light<br />

source. Failure of the LED shall not cause an alarm condition. Detectors<br />

shall be factory set for sensitivity and shall require no field adjustments<br />

of any kind. Detectors shall have an obscuration rating in accordance with<br />

UL 268. Addressable smoke detectors shall be capable of having the<br />

sensitivity being remotely adjusted by the control panel.<br />

2.7.2.3 Projected Beam Smoke Detectors<br />

Detectors shall be designed for detection of abnormal smoke densities.<br />

Detectors shall consist of separate transmitter and receiver units. The<br />

transmitter unit shall emit an infrared beam to the receiver unit. When the<br />

signal at the receiver falls below a preset sensitivity, the detector shall<br />

initiate an alarm. The receiver shall contain an LED which is powered upon<br />

an alarm condition. Long-term changes to the received signal caused by<br />

environmental variations shall be automatically compensated. Detectors<br />

shall incorporate features to assure that they are operational; a trouble<br />

signal shall be initiated if the beam is obstructed, the limits of the<br />

compensation circuit are reached, or the housing cover is removed.<br />

SECTION 28 31 64 Page 16


Detectors shall have multiple sensitivity settings in order to meet UL<br />

listings for the different distances covered by the beam. In the event of<br />

beam interference for more than three seconds a trouble alarm shall be<br />

transmitted.<br />

2.7.2.4 Duct Detectors<br />

Duct-mounted photoelectric smoke detectors shall be furnished and installed<br />

where indicated and in accordance with NFPA 90A. Units shall consist of a<br />

smoke detector as specified in paragraph Photoelectric Detectors, mounted in<br />

a special housing fitted with duct sampling tubes. Detector circuitry shall<br />

be mounted in a metallic enclosure exterior to the duct. Detectors shall<br />

have a manual reset. Detectors shall be rated for air velocities that<br />

include air flows between 500 and 4000 fpm. Detectors shall be powered from<br />

the fire alarm panel. Sampling tubes shall run the full width of the duct.<br />

The duct detector package shall conform to the requirements of NFPA 90A, UL<br />

268A, and shall be UL listed for use in air-handling systems. The control<br />

functions, operation, reset, and bypass shall be controlled from the fire<br />

alarm control panel. Lights to indicate the operation and alarm condition;<br />

and the test and reset buttons shall be visible and accessible with the unit<br />

installed and the cover in place. Detectors mounted above 6 feet and those<br />

mounted below 6 feet that cannot be easily accessed while standing on the<br />

floor, shall be provided with a remote detector indicator panel containing<br />

test and reset switches. Remote lamps and switches as well as the affected<br />

fan units shall be properly identified in etched plastic placards.<br />

Detectors shall have auxiliary contacts to provide control, interlock, and<br />

shutdown functions specified in Section 23 09 23 DIRECT DIGITAL CONTROL FOR<br />

HVAC AND OTHER LOCAL BUILDING <strong>SYSTEM</strong>S. The detectors shall be supplied by<br />

the fire alarm system manufacturer to ensure complete system compatibility.<br />

2.7.3 Combination Smoke and Heat Detectors<br />

Combination smoke and heat detectors shall have an audible device (selfcontained)<br />

and be designed for detection of abnormal smoke densities by the<br />

photoelectric principle and abnormal heat by a fixed temperature sensor.<br />

Smoke detectors shall be provided with an LED light source. Failure of the<br />

LED shall not cause an alarm condition and the sensitivity shall be factory<br />

set at a nominal 3 percent and require no field adjustments of any kind.<br />

Heat detector portion shall be fixed temperature sensor rated at 135 degrees<br />

F. The audible appliances shall have a minimum sound output of at least 85<br />

dBA at 10 feet. Detectors shall contain a visible indicator LED that shows<br />

when the unit is in alarm condition. Detectors shall not be adversely<br />

affected by vibration or pressure. Heat detectors shall connect to a<br />

control panel and shall be self restorable.<br />

2.7.4 Flame Detectors<br />

The detectors shall comply with FM P7825a. The detectors shall be sensitive<br />

to the micron range best suited for their intended use. The detectors shall<br />

operate over electrically supervised wiring circuits and the loss of power<br />

to the detector shall result in a trouble signal. A self-test feature shall<br />

be provided for each detector to be individually tested.<br />

2.7.4.1 Infrared (IR) Single Frequency Flame Detector<br />

The detector shall be sensitive in the range best suited for the intended<br />

service.<br />

SECTION 28 31 64 Page 17


2.7.4.2 Infrared (IR) Dual Frequency Flame Detector<br />

The IR detector shall consist of two or more IR sensors, each selected for a<br />

different IR frequency. The primary sensor shall be sensitive in the range<br />

best suited for the intended service. Secondary sensors are tuned to<br />

different IR wavelengths to null out the effect of black body radiation to<br />

the primary sensor.<br />

2.7.4.3 Ultraviolet (UV) Flame Detectors<br />

UV flame detector shall be of the narrow band response type which operates<br />

on radiated ultraviolet energy and shall be sensitive in the range best<br />

suited for the intended service. The cone of vision shall be 80 degrees or<br />

greater. Each detector shall be completely insensitive to light sources in<br />

the visible frequency range.<br />

2.7.4.4 Combination UV/IR Flame Detector<br />

The UV/IR detector shall provide discrimination against false alarms by<br />

requiring both UV and IR flame detection before an alarm is sent. The UV<br />

sensor shall be sensitive in the range of 0.185 to 0.265 micrometers only.<br />

The IR sensor shall be sensitive in the range best suited for the intended<br />

service. Detectors shall be completely insensitive to light sources in the<br />

visible frequency range.<br />

2.8 NOTIFICATION APPLIANCES<br />

Audible appliances shall conform to the applicable requirements of UL 464.<br />

Devices shall be connected into notification appliance circuits. Devices<br />

shall have a separate screw terminal for each conductor. Audible appliances<br />

shall generate a unique audible sound from other devices provided in the<br />

building and surrounding area. Surface mounted audible appliances shall be<br />

painted red. Recessed audible appliances shall be installed with a grill<br />

that is painted red with a factory finish to match the surface to which it<br />

is mounted.<br />

2.8.1 Alarm Bells<br />

Bells shall be surface mounted with matching mounting back box. Bells shall<br />

be suitable for use in an electrically supervised circuit. Bells shall be<br />

the underdome type producing a minimum output rating of 85 dBA at 10 feet.<br />

Bells used in exterior locations shall be specifically listed or approved<br />

for outdoor use and be provided with metal housing and protective grilles.<br />

Single stroke, electrically operated, supervised, solenoid bells shall be<br />

used for coded applications.<br />

2.8.2 Alarm Horns<br />

Horns shall be surface mounted, with matching mounting back box, grille and<br />

vibrating type suitable for use in an electrically supervised circuit.<br />

Horns shall produce a sound rating of at least 85 dBA at 10 feet. Horns<br />

used in exterior locations shall be specifically listed or approved for<br />

outdoor use and be provided with metal housing and protective grilles.<br />

2.8.3 Chimes<br />

SECTION 28 31 64 Page 18


Chimes shall be electrically operated, supervised, electronic type, with an<br />

adjustable frequency of 800 to 1200 Hertz. Chimes shall have a minimum<br />

sound rating of 80 dBA at 10 feet. Chimes shall ring the bell codes, as<br />

indicated.<br />

2.8.4 Visual Notification Appliances<br />

Visual notification appliances shall conform to the applicable requirements<br />

of UL 1971 and the contract drawings. Appliances shall have clear high<br />

intensity optic lens, xenon flash tubes, and output white light. Strobe<br />

flash rate shall be between 1 to 3 flashes per second and a minimum of 75<br />

candela.<br />

2.8.5 Combination Audible/Visual Notification Appliances<br />

Combination audible/visual notification appliances shall provide the same<br />

requirements as individual units except they shall mount as a unit in<br />

standard backboxes. Units shall be factory assembled. Any other audible<br />

notification appliance employed in the fire alarm systems shall be approved<br />

by the Contracting Officer.<br />

2.8.6 Voice Evacuation System<br />

The voice evacuation system shall provide for one-way voice communications,<br />

routing and pre-amplification of digital alarm tones and voice (digital and<br />

analog) messages. The system shall be zoned for messages (Custom and<br />

prerecorded) and tones as indicated on the drawings. The following<br />

electronic tones shall be available from the amplifier: Slow Whoop,<br />

High/Low, Horn, Chime, Beep, Stutter, Wail and Bell. The system shall have<br />

a microphone and allow for general paging within the space. Operation shall<br />

be either manually from a control switch or automatically from the fire<br />

alarm control panel. Reset shall be accomplished by the fire alarm control<br />

panel during panel reset.<br />

2.9 <strong>FIRE</strong> DETECTION AND <strong>ALARM</strong> <strong>SYSTEM</strong> PERIPHERAL EQUIPMENT<br />

2.9.1 Electromagnetic Door Hold-Open Devices<br />

Devices shall be attached to the walls unless otherwise indicated. Devices<br />

shall comply with the appropriate requirements of UL 228. Devices shall<br />

operate on 24 Volt dc power. Compatible magnetic component shall be<br />

attached to the door. Under normal conditions, the magnets shall attract<br />

and hold the doors open. When magnets are de-energized, they shall release<br />

the doors. Magnets shall have a holding force of 25 pounds. Devices shall<br />

be UL or FM approved. Housing for devices shall be brushed aluminum or<br />

stainless steel. Operation shall be fail safe with no moving parts.<br />

Electromagnetic door hold-open devices shall not be required to be held open<br />

during building power failure.<br />

2.9.2 Conduit<br />

Conduit and fittings shall comply with NFPA 70, UL 6, UL 1242, and UL 797.<br />

2.9.3 Wiring<br />

Wiring shall conform to NFPA 70. Wiring for 120 Vac power shall be No. 12<br />

AWG minimum. The SLC wiring shall be copper cable in accordance with the<br />

SECTION 28 31 64 Page 19


manufacturers requirements. Wiring for fire alarm dc circuits shall be No.<br />

16 AWG minimum. Voltages shall not be mixed in any junction box, housing,<br />

or device, except those containing power supplies and control relays.<br />

Wiring shall conform to NFPA 70. System field wiring shall be solid copper<br />

and installed in metallic conduit or electrical metallic tubing, except that<br />

rigid plastic conduit may be used under slab-on-grade. Conductors shall be<br />

color coded. Conductors used for the same functions shall be similarly<br />

color coded. Wiring code color shall remain uniform throughout the circuit.<br />

Pigtail or T-tap connections to initiating device circuits, supervisory<br />

alarm circuits, and notification appliance circuits are prohibited.<br />

2.10 TRANSMITTERS<br />

2.10.1 Radio Alarm Transmitters<br />

Transmitters shall be compatible with proprietary supervising station<br />

receiving equipment. Each radio alarm transmitter shall be the<br />

manufacturer's recognized commercial product, completely assembled, wired,<br />

factory tested, and delivered ready for installation and operation.<br />

Transmitters shall be provided in accordance with applicable portions of<br />

NFPA 72, NFPA 1221, and 47 CFR 15. Transmitter electronics module shall be<br />

contained within the physical housing as an integral, removable assembly.<br />

The proprietary supervising station receiving equipment is Monaco and the<br />

transceiver shall be fully compatible with this equipment. At the<br />

Contractors option, and if UL listed, the transmitter may be housed in the<br />

same panel as the fire alarm control panel. Monaco BTX. Ft. Lewis Fire<br />

Alarm Transceiver frequency is 139.6750 MHz.<br />

2.10.1.1 Transmitter Power Supply<br />

Each radio alarm transmitter shall be powered by a combination of locally<br />

available 120-volt ac power and a sealed, lead-acid battery.<br />

a. Operation: Each transmitter shall operate from 120-volt ac power.<br />

In the event of 120-volt ac power loss, the transmitter shall<br />

automatically switch to battery operation. Switchover shall be<br />

accomplished with no interruption of protective service, and shall<br />

automatically transmit a trouble message. Upon restoration of ac<br />

power, transfer back to normal ac power supply shall also be automatic.<br />

b. Battery Power: Transmitter standby battery capacity shall provide<br />

sufficient power to operate the transmitter in a normal standby status<br />

for a minimum of 72 hours and be capable of transmitting alarms during<br />

that period.<br />

2.10.1.2 Radio Alarm Transmitter Housing<br />

Transmitter housing shall be NEMA Type 1. The housing shall contain a lock<br />

that is keyed identical to the fire alarm system for the building. Radio<br />

alarm transmitter housing shall be factory painted with a suitable priming<br />

coat and not less than two coats of a hard, durable weatherproof enamel.<br />

2.10.1.3 Antenna<br />

Provide antennas as stated in the Delivery or Task Order for radio alarm<br />

transmitters with a driving point impedance to match transmitter output.<br />

The antenna and antenna mounts shall be corrosion resistant and designed to<br />

SECTION 28 31 64 Page 20


withstand wind velocities of 100 mph. Antennas shall not be mounted to any<br />

portion of the building roofing system. Apply silicone sealant at all<br />

threaded connections on the antenna mast to waterproof the joint.<br />

2.10.2 Master Fire Alarm Boxes<br />

Master fire alarm boxes shall be of the coded, noninterfering type with<br />

succession features having a compatible auxiliary tripping device, and of<br />

the prewound, open-door, pull-lever type. Mechanism shall be housed in a<br />

weatherproof cottage shell type of housing with metallic or rigid plastic<br />

code number plate mounted on the exterior face of the cottage shell.<br />

a. Operation of the actuating pull lever shall cause the box to<br />

transmit four complete rounds of code to gongs, recorders, and other<br />

devices on the same circuit. Driving springs shall have the capability<br />

to transmit not less than eight complete four-round groups of code<br />

before being rewound.<br />

b. Boxes shall be designed for operation of 100 milliamperes dc, but<br />

with capability of full operation of 70 milliamperes and up to 120<br />

milliamperes. Activation of box when a single open fault is present on<br />

exterior fire alarm circuit shall have box to idle for one complete<br />

round only, then immediately transmit four complete code rounds via the<br />

box earth ground connection.<br />

c. Each box shall be equipped with manual signaling key, telephone<br />

jack, silent test device, and box shunt device. Box shall be mounted<br />

as indicated with center of box 61 inches above grade, and provided<br />

with lighting fixture. Mounting bolts, brackets, fastenings, and<br />

conduit shall be copper alloy, cadmium, or zinc-coated steel. Code<br />

wheel shall be metallic and box code shall be as directed.<br />

Electrically powered master fire alarm boxes shall have standby sealed,<br />

lead acid battery capacity for a minimum of 72 hours and be capable of<br />

transmitting alarms during that period.<br />

2.10.3 Telephonic Reporting System<br />

Transmitters shall be compatible with existing receiving equipment at the<br />

Supervising Station and shall comply with applicable requirements of UL 632.<br />

Transmitter shall respond to the actuation of the fire alarm control panel<br />

and shall be of the electric motor-driven or prewound spring mechanism type;<br />

it shall transmit not less than four rounds of code. When motor-driven<br />

transmitters are provided, the motor shall be connected to a supervised<br />

circuit in a control panel. Metallic or rigid plastic code number plates on<br />

the exterior face of transmitters shall be provided. Transmitters shall be<br />

designed to provide the same features as the fire alarm boxes for<br />

electrically-supervised, coded noninterfering type and shall have the<br />

ability to transmit signals on grounded or open circuits. Activation of box<br />

when a single open fault is present on exterior fire alarm circuit shall<br />

have box to idle for one complete round only, then immediately transmit four<br />

complete code rounds via the box earth ground connection. Transmitter shall<br />

have a compatible auxiliary tripping device. Code wheel shall be metallic<br />

and box code shall be as directed. Wiring shall be extended to the<br />

indicated telephone terminating location and connected to specific twisted<br />

pair cable identified by the COR in the field.<br />

SECTION 28 31 64 Page 21


PART 3<br />

EXECUTION<br />

3.1 EXAMINATION<br />

After becoming familiar with details of the work, verify dimensions in the<br />

field and advise the Contracting Officer of any discrepancy before<br />

performing the work. Install fire alarm panels, transceivers, and other<br />

sensitive electrical or electronic equipment in dedicated electrical<br />

equipment rooms accessible to maintenance personnel from the building<br />

exterior. Equipment is not allowed to be installed in mechanical spaces or<br />

other areas subject to excessive temperature and moisture.<br />

3.2 INSTALLATION<br />

Install all work as shown, in accordance with NFPA 70 and NFPA 72, and in<br />

accordance with the manufacturer's diagrams and recommendations, unless<br />

otherwise specified. All devices shall be installed per NFPA 72; 4.4.4.1<br />

and 4.4.4.2.4 to meet the requirements of voltage, temperature and humidity<br />

variation. All addressable devices shall be identified with the address<br />

number with a machine-made label. Install a rubber gasket where devices are<br />

mounted externally on brick or exterior surfaces to reduce electrolysis and<br />

grounds. Smoke detectors shall not be installed until construction is<br />

essentially complete and the building has been thoroughly cleaned.<br />

3.2.1 Power Supply for the System<br />

Provide a single dedicated circuit connection for supplying power from a<br />

branch circuit to each building fire alarm system. The power shall be<br />

supplied as shown on the drawings. The power supply shall be accessible<br />

only to authorized personnel and shall be equipped with a locking mechanism<br />

and marked in red with the words "<strong>FIRE</strong> <strong>ALARM</strong> CIRCUIT CONTROL". The location<br />

of the circuit disconnecting means shall be permanently identified at the<br />

fire alarm control unit.<br />

3.2.2 Wiring<br />

Conduit size for wiring shall be in accordance with NFPA 70. Wiring for the<br />

fire alarm system shall not be installed in conduits, junction boxes, or<br />

outlet boxes with conductors of lighting and power systems. Not more than<br />

two conductors shall be installed under any device screw terminal. The<br />

wires under the screw terminal shall be straight when placed under the<br />

terminal then clamped in place under the screw terminal. The wires shall be<br />

broken and not twisted around the terminal. Circuit conductors entering or<br />

leaving any mounting box, outlet box enclosure, or cabinet shall be<br />

connected to screw terminals with each terminal and conductor marked in<br />

accordance with the wiring diagram. Connections and splices shall be made<br />

using screw terminal blocks. The use of wire nut type connectors in the<br />

system is prohibited. Wiring within any control equipment shall be readily<br />

accessible without removing any component parts. The fire alarm equipment<br />

manufacturer's representative shall be present for the connection of wiring<br />

to the control panel. Wiring on fire alarm system components shall be Class<br />

A (Style 7) signaling line circuits (SLC), Class A notification appliance<br />

circuits (NAC) and Class A Initiating device circuit (IDC). Overhead,<br />

underground, or direct burial cables shall be specifically approved for the<br />

purpose.<br />

SECTION 28 31 64 Page 22


3.2.3 Control Panel<br />

The control panel and its assorted components shall be mounted so that no<br />

part of the enclosing cabinet is less than 12 inches nor more than 78 inches<br />

above the finished floor. Manually operable controls shall be between 36<br />

and 42 inches above the finished floor. Panel shall be installed to comply<br />

with the requirements of UL 864.<br />

3.2.4 Detectors<br />

Detectors shall be located and installed in accordance with NFPA 72.<br />

Detectors shall be connected into signal line circuits or initiating device<br />

circuits as indicated on the drawings. Detectors shall be at least 12<br />

inches from any part of any lighting fixture. Detectors shall be located at<br />

least 3 feet from diffusers of air handling systems. Each detector shall be<br />

provided with appropriate mounting hardware as required by its mounting<br />

location. Detectors which mount in open space shall be mounted directly to<br />

the end of the stubbed down rigid conduit drop. Conduit drops shall be<br />

firmly secured to minimize detector sway. Where length of conduit drop from<br />

ceiling or wall surface exceeds 3 feet, sway bracing shall be provided.<br />

Detectors installed in concealed locations (above ceiling, raised floors,<br />

etc.) shall have a remote visible indicator LED/LCD.<br />

Smoke detectors in addressable systems shall be analog type, providing<br />

information that the control unit stores in memory, and uses to provide a<br />

history of detector stability, and notification at the control unit where<br />

sensitivity is outside its acceptable sensitivity range. Smoke detectors in<br />

sleeping rooms shall be fully addressable, self resetting (no manual reset<br />

required at the FACP) with a sounder base operated from the fire alarms<br />

controls panel power and having reverse polarity sounding capability for<br />

local and general alarms. Activation of the sleeping room smoke detector<br />

will only set off its sounder base for local audible alarm. A general alarm<br />

will also activate the sounder base. Upon an alarm condition the detector<br />

shall be non-latching, not require reset at the fire alarm panel after a<br />

local alarm, and not cause the transmitter to send an alarm or trouble.<br />

3.2.5 Notification Appliances<br />

Notification appliances shall be mounted 80 inches above the finished floor<br />

or 6 inches below the ceiling, whichever is lower.<br />

3.2.6 Annunciator Equipment<br />

Annunciator equipment shall be mounted where indicated on the drawings.<br />

Separate annunciator panels are not desired fire alarm system components on<br />

JBLM. Do not include annunciators in fire alarm system designs unless<br />

specifically called for by JBLM Fire Department.<br />

3.2.7 Addressable Initiating Device Circuits Module<br />

The initiating device circuits module shall be used to connect supervised<br />

conventional initiating devices (water flow switches, water pressure<br />

switches, manual fire alarm stations, high/low air pressure switches, and<br />

tamper switches). The module shall mount in an electrical box adjacent to<br />

or connected to the device it is monitoring and shall be capable of Style B<br />

supervised wiring to the initiating device. In order to maintain proper<br />

supervision, there shall be no T-taps allowed on style B lines. Addressable<br />

SECTION 28 31 64 Page 23


initiating device circuits modules shall monitor only one initiating device<br />

each. Contacts in suppression systems and other fire protection subsystems<br />

shall be connected to the fire alarm system to perform supervisory and alarm<br />

functions as specified in Section 21 13 13.00 10 WET PIPE SPRINKLER <strong>SYSTEM</strong>,<br />

<strong>FIRE</strong> PROTECTION or 21 13 17.00 10 DRY PIPE SPRINKLER <strong>SYSTEM</strong>, <strong>FIRE</strong><br />

PROTECTION. Fire alarm systems with 4 or more devices per alarm initiating<br />

device zone shall be of the addressable type, except in troop housing where<br />

all systems shall be addressable type (reduced maintenance time, improved<br />

FLFD response).<br />

3.2.8 Addressable Control Module<br />

Addressable and control modules shall be installed in the outlet box or<br />

adjacent to the device they are controlling. If a supplementary suppression<br />

releasing panel is provided, then the monitor modules shall he mounted in a<br />

common enclosure adjacent to the suppression releasing panel and both this<br />

enclosure and the suppression releasing panel shall be in the same room as<br />

the releasing devices. All interconnecting wires shall be supervised unless<br />

an open circuit or short circuit abnormal condition does not affect the<br />

required operation of the fire alarm system. If control modules are used as<br />

interfaces to other systems, such as HVAC or elevator control, they shall be<br />

within the control panel or immediately adjacent to it. Control modules<br />

that control a group of notification appliances shall be adjacent to the<br />

first notification appliance in the notification appliance circuits.<br />

Control modules that connect to devices shall supervise the notification<br />

appliance circuits. Control modules that connect to auxiliary systems or<br />

interface with other systems (non-life safety systems) and where not<br />

required by NFPA 72, shall not require the secondary circuits to be<br />

supervised. Contacts in suppression systems and other fire protection<br />

subsystems shall be connected to the fire alarm system to perform required<br />

alarm functions as specified in Section 21 13 13.00 10 WET PIPE SPRINKLER<br />

<strong>SYSTEM</strong>, <strong>FIRE</strong> PROTECTION or 21 13 17.00 10 DRY PIPE SPRINKLER <strong>SYSTEM</strong>, <strong>FIRE</strong><br />

PROTECTION.<br />

3.3 OVERVOLTAGE AND SURGE PROTECTION<br />

3.3.1 Power Line Surge Protection<br />

All equipment connected to alternating current circuits shall be protected<br />

from surges in accordance with IEEE C62.41.1/IEEE C62.41.2 B3 combination<br />

waveform and NFPA 70. Fuses shall not be used for surge protection. The<br />

surge protector shall be rated for a maximum let thru voltage of 350 Volts<br />

ac (line-to-neutral) and 350 Volt ac (neutral-to-ground).<br />

3.3.2 Low Voltage DC Circuits Surge Protection<br />

All IDC, NAC, and communication cables/conductors, except fiber optics,<br />

shall have surge protection installed at each point where it exits or enters<br />

a building. Equipment shall be protected from surges in accordance with<br />

IEEE C62.41.1/IEEE C62.41.2 B3 combination waveform and NFPA 70. The surge<br />

protector shall be rated to protect the 24 Volt dc equipment. The maximum<br />

dc clamping voltages shall be 36 V (line-to-ground) and 72 Volt dc (line-toline).<br />

3.3.3 Signal Line Circuit Surge Protection<br />

SECTION 28 31 64 Page 24


All SLC cables/conductors, except fiber optics, shall have surge<br />

protection/isolation circuits installed at each point where it exits or<br />

enters a building. The circuit shall be protected from surges in accordance<br />

with IEEE C62.41.1/IEEE C62.41.2 B3 combination waveform and NFPA 70. The<br />

surge protector/isolator shall be rated to protect the equipment.<br />

3.4 GROUNDING<br />

Grounding shall be provided by connecting to building ground system.<br />

3.5 SUPERVISING STATION PROVISIONS<br />

The supervising equipment shall be as defined in Delivery Order<br />

3.5.1 Revisions to Existing Facilities<br />

Existing supervising components shall be modified as indicated on the<br />

drawings and programming shall be updated if required to accommodate the<br />

revised configuration. Acceptance testing shall include procedures that<br />

would demonstrate that operation of existing equipment has not been degraded<br />

and that the revised configuration plus interfacing components operates<br />

compatibly with the new fire alarm system at the protected premises. Work<br />

on existing equipment shall be performed in accordance with the<br />

manufacturer's instructions or under supervision of the manufacturer's<br />

representative.<br />

3.5.2 Additions to Existing Facilities<br />

Supplemental components shall be added to the existing supervising equipment<br />

as required to accommodate the new fire alarm system to be installed at the<br />

protected premises or as indicated on the drawings. All present functions<br />

shall be extended, including recording and storage in memory, and<br />

programming shall be updated if required to accommodate the revised<br />

configuration. Acceptance testing shall include procedures that would<br />

demonstrate that operation of existing equipment has not been degraded and<br />

that the expanded configuration operates compatibly with the new fire alarm<br />

system. The Proprietary Supervising Station is located in the FLECC. The<br />

equipment is manufactured by Monaco.<br />

3.6 TRAINING<br />

Provide training course for the operations and maintenance staff. Conduct<br />

the course in the building where the system is installed or as designated by<br />

the Contracting Officer. The training period for systems operation shall<br />

consist of 1 training day (8 hours per day) and shall start after the system<br />

is functionally completed but prior to final acceptance tests. The training<br />

period for systems maintenance shall consist of 2 training days (8 hours per<br />

day) and shall start after the system is functionally completed but prior to<br />

final acceptance tests. The instructions shall cover items contained in the<br />

operating and maintenance instructions. In addition, training shall be<br />

provided on performance of expansions or modifications to the fire detection<br />

and alarm system, such as adding or deleting devices, programming or editing<br />

software, and use of factory technical support. The training period for<br />

system expansions and modifications shall consist of at least 1 training day<br />

(8 hours per day) and shall start after the system is functionally completed<br />

but prior to final acceptance tests. Additional system training shall<br />

provide the designated government personnel adequate knowledge, tools and<br />

SECTION 28 31 64 Page 25


equipment that will be required to diagnose, repair, maintain, and expand<br />

functions inherent to the system and be conducted on site and/or off site as<br />

necessary to fully qualify the government operations and maintenance<br />

technicians to perform all levels of maintenance, expansions, and<br />

modifications to the fire alarm system, hardware, software, and components.<br />

This training will include and turn over to the government all proprietary<br />

licenses, software, and tools to perform the required tasks. All specialized<br />

equipment and/or training to program, edit existing program, add or delete<br />

devices, etc. shall be provided as part of the fire alarm system.<br />

3.7 TESTING<br />

Notify the Contracting Officer at least 10 days before the preliminary and<br />

acceptance tests are to be conducted. Coordinate all testing with Public<br />

Works, Fire Department, Physical Security, and the Contracting Officer. The<br />

ring down test proving battery capacity shall be done the morning of the<br />

final acceptance test. The pre-test form shall be on hand at the time of the<br />

acceptance test. The contractor shall obtain the transmitter number from the<br />

JBLM Emergency Control Center (building 4101). Forward and reflective power<br />

reading of the transmitter and transmitter zones shall be written inside the<br />

transmitter cabinet. The contractor shall ensure a set of as-built drawings<br />

are on hand during the final acceptance test. Perform the tests in<br />

accordance with the approved test procedures in the presence of the<br />

Contracting Officer. The control panel manufacturer's representative shall<br />

be present to supervise tests. Furnish instruments and personnel required<br />

for the tests.<br />

3.7.1 Preliminary Tests<br />

Upon completion of the installation, subject the system to functional and<br />

operational performance tests including tests of each installed initiating<br />

and notification appliance, when required. Tests shall include the<br />

meggering of system conductors to determine that the system is free from<br />

grounded, shorted, or open circuits. Conduct the megger test prior to the<br />

installation of fire alarm equipment. If deficiencies are found,<br />

corrections shall be made and the system shall be retested to assure that it<br />

is functional. After completing the preliminary testing complete and submit<br />

the NFPA 72, Certificate of Completion and Testing Form. Require the<br />

contractor to submit the BTX form available from the design standards web<br />

site to acquire a transmitter number from the 911 center.<br />

3.7.2 Acceptance Test<br />

Acceptance testing shall not be performed until the Contractor has completed<br />

and submitted the Certificate of Completion. Testing shall be in accordance<br />

with NFPA 72. The recommended tests in NFPA 72 shall be considered<br />

mandatory and shall verify that previous deficiencies have been corrected.<br />

The test shall include all requirements of NFPA 72 and the following:<br />

a. Test of each function of the control panel.<br />

b. Test of each circuit in both trouble and normal modes.<br />

c. Tests of each alarm initiating devices in both normal and trouble<br />

conditions.<br />

d. Tests of each control circuit and device.<br />

SECTION 28 31 64 Page 26


e. Tests of each alarm notification appliance.<br />

f. Tests of the battery charger and batteries.<br />

g. Complete operational tests under emergency power supply.<br />

h. Visual inspection of wiring connections.<br />

i. Opening the circuit at each alarm initiating device and<br />

notification appliance to test the wiring supervisory feature.<br />

j. Ground fault.<br />

k. Short circuit faults.<br />

l. Stray voltage.<br />

m. Loop resistance.<br />

n. The 72 hour - 15 minute ring down test shall be done the morning of<br />

the final acceptance test. The pre-test form shall be on hand at the<br />

time of the acceptance test. The contractor shall obtain the<br />

transmitter number from the JBLM Emergency Control Center. Forward and<br />

reflective power reading of the transmitter and transmitter zones shall<br />

be written inside the transmitter. The contractor shall ensure a set of<br />

as-built drawings are on hand during the final acceptance test.<br />

-- End of Section --<br />

SECTION 28 31 64 Page 27


SECTION 28 31 64 Page 28


JBLM DESIGN STANDARDS<br />

SECTION 28 31 64.00 10 - <strong>FIRE</strong> DETECTION AND <strong>ALARM</strong> <strong>SYSTEM</strong>, ADDRESSABLE<br />

<strong>Design</strong> Requirements<br />

a. The transceiver number and the transceiver zones to be used for each project shall be<br />

designated by the Ft. Lewis Fire Inspectors / DPW Fire Alarm Maintenance personnel.<br />

The Ft. Lewis Fire Alarm Transceiver frequency is 139.6750 MHz.<br />

b. The following initiating events or troubles shall require their own transmitted zone<br />

-deluge sprinkler system<br />

-water flow (sprinkler)<br />

-low air pressure (dry sprinkler)<br />

-separate buildings or quads<br />

-FACP common trouble<br />

c. No conduit in the top or bottom of transmitter enclosures<br />

d. All threaded connections on the antenna mast shall have silicone seal added for water<br />

proofing the joint.<br />

e. All fire alarm transceivers must be listed or approved for use with the existing Monaco<br />

D-21M base reporting system and meet the following minimum requirements:<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

o<br />

FM approved<br />

Narrowband radio communications with the Monaco D-21 base reporting system.<br />

• FCC certified for narrowband operation and meets the requirements of the<br />

NTIA<br />

• Manual of Regulations and Procedures for Federal frequency<br />

Management.<br />

Fallback communications to hardwire connection if wired (phone line backup).<br />

Transmits live-voice and pre-recorded messages from the D-21 Mass Notification<br />

System to within-building mass notification panels or wide-area speaker stations.<br />

Receives live voice from radio, telephone, and microphone.<br />

Pre-recorded messages can be triggered via relay contact closure.<br />

Security features prevents unauthorized take over of live-voice transmissions.<br />

Supervised connection to mass notification panel.<br />

Status LEDs reflect the status of the transciever: general trouble, system fault,<br />

in-communication, carrier detect, transmit, primary power, battery boost charge,<br />

and battery float charge.<br />

Communication LEDs indicate the method of communication used: radio or<br />

hardwire and whether or not a live-voice message is being sent.<br />

Full-duplex RS-232 port used to program the transciever via connection to a<br />

laptop computer.<br />

115 or 230 Vac power is monitored with automatic switchover to backup battery<br />

power that provides standby power.<br />

Self test, stuck transmitter disconnect, reset, acknowledge, and battery reconnect<br />

switches.<br />

Local audible alert.<br />

Real time clock and calendar.<br />

SECTION 28 31 76 Page 1


o<br />

o<br />

o<br />

At least 1/2 Mb of program memory.<br />

At least 1/2 Mb of non-volatile data storage.<br />

One selectable RS-422/RS-485 port for communication with peripheral<br />

equipment or hardwire connection to multiple units connected together for<br />

communication with the D-21.<br />

JBLM & JBLM-YTC - Mass Notification Specifications and Requirements<br />

1. System Requirements<br />

System mass notification hardware shall integrate with the Monaco D21 fire system<br />

through the use of a mass notification panel or a fire/mass notification combination panel.<br />

System shall be programmed and integrated with the existing head end hardware and<br />

work station(s) and made capable of remote activation from the JBLM Emergency<br />

Operation Command (FLEC) facility. Remote activation connectivity between the FLEC<br />

and project shall be through the Monaco BT-XM transmitter panel. Installation approved<br />

messages shall be provided by JBLM, Directorate of Emergency Services, Physical<br />

Security Branch.<br />

Mass Notification/Public Announcement Systems Integration is allowed for smaller<br />

systems. It is not recommended for larger projects, however it is not prohibited, provided<br />

the following system(s) engineering design requirements are included as part of the<br />

overall integration;<br />

• They shall share the same commo/power race ways and speaker<br />

• PA must have its own power supply and amplifier, it shall not share the same amp<br />

as the Mass Notification (MN).<br />

• PA systems control panel shall be separate and stand alone from the MN panel<br />

(Anti-Feed back issues must be addressed and eliminated if co-locating or Local<br />

Operating Console (LOC) is placed near the LOC for either of these systems).<br />

• Two panels are clearly labeled and easily identified as either PA or MN<br />

• PA panel lock set is not the same as the MN panel, AHJ will provide core<br />

information.<br />

• PA shall not share any UPS or back up power source used to support MN.<br />

• PA commands/messaging shall be subordinate to MN/Fire messaging.<br />

• PA system shall not remote tie in to the FLEC.<br />

• Speaker technology shall be designed to meet the minimum requirements for MN.<br />

• Mass Notification Visual alerting devices shall not light upon activation of the PA<br />

system.<br />

2. Company, Integrator, Programmer and Installer Certification Requirements<br />

Proof of certifications of integrators, installers and maintenance personnel required by<br />

UFC 4-021-01 shall be provided prior to award.<br />

SECTION 28 31 76 Page 2


3. Final Testing and Acceptance<br />

Final acceptance test shall be performed by installation engineers and/or security<br />

specialist for system functionality and required intelligibility. A minimum of .7 on the<br />

Sound Transmission Index (STI), at an expected average ambient noise level for the<br />

environment being tested, as registered by the DSP 30 analyzer will be required. Test<br />

points shall be identified and conducted throughout the facility at a point furthest from<br />

any single speaker and/or at the mid point between any two speakers servicing the target<br />

area. Dependent on building ADA category and placement of visual alerting devices,<br />

recommend a reading at the speaker. Additional information or deviation from sections 1<br />

- 4 requirements shall be routed thru construction project manager to DES as AHJ for<br />

approval. Current calibration certificate shall be provided at the time of testing.<br />

Upon completion of work and contractors 100% system test, contractor shall schedule a<br />

100% Performance Verification Test (PVT) with Directorate of Emergency Services,<br />

SAC-D, Physical Security Branch. Upon acceptance, contractor shall receive results of<br />

the performance verification test.<br />

4. Warranty and Repair<br />

Warranty for materials and labor shall be 1 year from date of 100% acceptance. Response<br />

by qualified technicians to warranty issues that have rendered the Mass Notification<br />

system not operational shall be within 24 hours or the next business day from the time of<br />

notification. Repairs shall be completed and the system restored within 48 hours of<br />

technicians arrival.<br />

Notes to <strong>Design</strong>ers on Drawing Content<br />

All as-builts shall be required to show the exact run of conduit, quantity of wires, wire color<br />

code, location of every initiating device, signaling device, module, and any major junction boxes<br />

or power supplies. The plans will also show loop number and the address of each device, or<br />

module, if system is addressable.<br />

SECTION 28 31 76<br />

INTERIOR <strong>FIRE</strong> <strong>ALARM</strong> AND MASS NOTIFICATION <strong>SYSTEM</strong><br />

11/08<br />

PART 1<br />

GENERAL<br />

1.1 RELATED SECTIONS<br />

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, applies to<br />

this section, with the additions and modifications specified herein. In<br />

addition, refer to the following sections for related work and coordination:<br />

SECTION 28 31 76 Page 3


Section 21 30 00 <strong>FIRE</strong> PUMPS<br />

Section 21 13 13.00 10 WET PIPE SPRINKLER <strong>SYSTEM</strong>, <strong>FIRE</strong> PROTECTION<br />

Section 21 13 17.00 10 DRY PIPE SPRINKLER <strong>SYSTEM</strong>, <strong>FIRE</strong> PROTECTION<br />

Section 21 13 18.00 10 PREACTION AND DELUGE SPRINKLER <strong>SYSTEM</strong>S, <strong>FIRE</strong><br />

PROTECTION<br />

Section 21 13 24.00 10 AQUEOUS FILM-FORMING FOAM (AFFF) <strong>FIRE</strong> PROTECTION<br />

<strong>SYSTEM</strong><br />

Section 21 21 03.00 10 WET CHEMICAL <strong>FIRE</strong> EXTINGUISHING <strong>SYSTEM</strong>.<br />

Section 08 71 00 DOOR HARDWARE for door release, door unlocking and<br />

additional work related to finish hardware.<br />

Section 14 24 00 HYDRAULIC ELEVATORS for additional work related to<br />

elevators.<br />

Section 07 84 00 <strong>FIRE</strong>STOPPING for additional work related to<br />

firestopping.<br />

1.2 REFERENCES<br />

The publications listed below form a part of this specification to the<br />

extent referenced. The publications are referred to within the text by the<br />

basic designation only. Criteria and requirements appearing in bold apply<br />

to work on JBLM only.<br />

ACOUSTICAL SOCIETY OF AMERICA (ASA)<br />

ASA S3.2<br />

(1989; R 1999) Method for Measuring the<br />

Intelligibility of Speech Over Communication<br />

Systems (ASA 85)<br />

ASME INTERNATIONAL (ASME)<br />

ASME A17.1<br />

(2007) Safety Code for Elevators and<br />

Escalators<br />

FM GLOBAL (FM)<br />

FM P7825a<br />

(2005) Approval Guide Fire Protection<br />

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)<br />

IEEE C62.41.1<br />

IEEE C62.41.2<br />

(2002) IEEE Guide on the Surges Environment<br />

in Low-Voltage (1000 V and Less) AC Power<br />

Circuits<br />

(2002) IEEE Recommended Practice on<br />

Characterization of Surges in Low-Voltage<br />

(1000 V and Less) AC Power Circuits<br />

INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)<br />

SECTION 28 31 76 Page 4


IEC 60268-16 (2003) Sound System Equipment - Part 16:<br />

Objective Rating Of Speech Intelligibility By<br />

Speech Transmission Index<br />

INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)<br />

ISO 7240-16 (2007) Fire Detection And Alarm Systems —<br />

Part 16: Sound System Control And Indicating<br />

Equipment<br />

NATIONAL <strong>FIRE</strong> PROTECTION ASSOCIATION (NFPA)<br />

NFPA 101<br />

NFPA 170<br />

NFPA 241<br />

(2008) Life Safety Code, 2006 Edition<br />

(2005) Fire Safety Symbols<br />

(2004) Safeguarding Construction,Alteration,<br />

and Demolition Operations<br />

NFPA 70 (2007; AMD 1 2008) National Electrical Code -<br />

2008 Edition<br />

NFPA 72<br />

NFPA 90A<br />

(2006) National Fire Alarm Code<br />

(2008) Standard for the Installation of Air<br />

Conditioning and Ventilating Systems<br />

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)<br />

47 CFR 15 Radio Frequency Devices<br />

47 CFR 90 Private Land Mobile Radio Services<br />

UNDERWRITERS LABORATORIES (UL)<br />

UL 1480<br />

UL 1638<br />

UL 1971<br />

UL 2017<br />

UL 228<br />

UL 268<br />

UL 268A<br />

(2003; Rev thru Dec 2006); Standard for<br />

Safety Speakers for Fire Alarm, Emergency,<br />

and Commercial and Professional Use<br />

(2001; Rev thru Oct 2008) Visual Signaling<br />

Appliances - Private Mode Emergency and<br />

General Utility Signaling<br />

(2002; Rev thru May 2006) Signaling Devices<br />

for the Hearing Impaired<br />

(2000; Rev thru Aug 2005) Standard for Safety<br />

for General-Purpose Signaling Devices and<br />

Systems<br />

(2006) Door Closers-Holders, With or Without<br />

Integral Smoke Detectors<br />

(2006) Standard for Smoke Detectors for Fire<br />

Alarm Signaling Systems<br />

(2008) Smoke Detectors for Duct Application<br />

SECTION 28 31 76 Page 5


UL 464<br />

UL 521<br />

UL 864<br />

UL Electrical Constructn<br />

UL Fire Prot Dir<br />

(2003; Rev thru Feb 2008) Standard for<br />

Audible Signal Appliances<br />

(1999; Rev thru Jul 2005) Heat Detectors for<br />

Fire Protective Signaling Systems<br />

(2003; Rev thru May 2007) Control Units and<br />

Accessories for Fire Alarm Systems<br />

(2008) Electrical Construction Equipment<br />

Directory<br />

(2008) Fire Protection Equipment Directory<br />

1.3 DEFINITIONS<br />

Wherever mentioned in this specification or on the drawings, the equipment,<br />

devices, and functions shall be defined as follows:<br />

a. Analog/Addressable System: A system where multiple signals are<br />

transmitted via the same conduction path to a remote fire alarm control<br />

unit and fire alarm control panel, decoded and separated so that each<br />

signal will initiate the specified response.<br />

b. Hard Wired System: A system where alarm and supervisory initiating<br />

devices are directly connected, through individual dedicated<br />

conductors, to a central control panel without the use of<br />

analog/addressable circuits or devices.<br />

c. Interface Device: An addressable device that interconnects hard<br />

wired systems or devices to an analog/addressable system.<br />

d. Remote Fire Alarm and Mass Notification Control Unit: A control<br />

panel, electronically remote from the fire alarm and mass notification<br />

control panel, that receives inputs from automatic and manual fire<br />

alarm devices; may supply power to detection devices and interface<br />

devices; may provide transfer of power to the notification appliances;<br />

may provide transfer of condition to relays or devices connected to the<br />

control unit; and reports to and receives signals from the fire alarm<br />

control panel.<br />

e. Fire Alarm and Mass Notification Control Panel (FACP/FMCP): A<br />

master control panel having the features of a fire alarm and mass<br />

notification control unit and fire alarm and mass notification control<br />

units are interconnected. The panel has central processing, memory,<br />

input and output terminals, video display units (VDUs), and printers as<br />

stated in the Delivery or Task Order.<br />

f. Terminal Cabinet: A steel cabinet with locking, hinge-mounted door<br />

that terminal strips are securely mounted.<br />

1.4 <strong>SYSTEM</strong> DESCRIPTION<br />

1.4.1 Scope<br />

SECTION 28 31 76 Page 6


a. This work includes completion of design and providing a complete<br />

analog/addressable fire alarm and mass notification system as described<br />

herein and on the contract drawings. Include in the system wiring,<br />

raceways, pull boxes, terminal cabinets, outlet and mounting boxes,<br />

control equipment, alarm, and supervisory signal initiating devices,<br />

alarm notification appliances, supervising station fire alarm system<br />

transmitter, and other accessories and miscellaneous items required for<br />

a complete operating system even though each item is not specifically<br />

mentioned or described. Provide systems complete and ready for<br />

operation.<br />

b. Provide equipment, materials, installation, workmanship,<br />

inspection, and testing in strict accordance with the required and<br />

advisory provisions of NFPA 72, ISO 7240-16, IEC 60268-16, except as<br />

modified herein. The system layouts on the drawings show the intent of<br />

coverage and are shown in suggested locations. Final quantity, system<br />

layout, and coordination are the responsibility of the Contractor.<br />

c. Where remote fire alarm control units are needed, they shall be<br />

provided at a terminal cabinet location. Each remote fire alarm<br />

control unit shall be powered from a wiring riser specifically for that<br />

use or from a local emergency power panel located on the same floor as<br />

the remote fire alarm control unit. Where remote fire control units<br />

are provided, equipment for notification appliances may be located in<br />

the remote fire alarm control units.<br />

1.4.2 Technical Data and Computer Software<br />

Technical data and computer software (meaning technical data that relates to<br />

computer software) that are specifically identified in this project, and may<br />

be defined/required in other specifications, shall be delivered, strictly in<br />

accordance with the CONTRACT CLAUSES. Identify data delivered by reference<br />

to the particular specification paragraph against which it is furnished.<br />

Data to be submitted shall include complete system, equipment, and software<br />

descriptions. Descriptions shall show how the equipment will operate as a<br />

system to meet the performance requirements of this contract. The data<br />

package shall also include the following:<br />

a. Identification of programmable portions of system equipment and<br />

capabilities.<br />

b. Description of system revision and expansion capabilities and<br />

methods of implementation detailing both equipment and software<br />

requirements.<br />

c. Provision of operational software data on all modes of programmable<br />

portions of the fire alarm and detection system.<br />

d. Description of Fire Alarm Control Panel equipment operation.<br />

e. Description of auxiliary and remote equipment operations.<br />

f. Library of application software.<br />

g. Operation and maintenance manuals.<br />

SECTION 28 31 76 Page 7


1.4.3 Keys<br />

Keys and locks for equipment shall be identical. Provide not less than six<br />

keys of each type required. All keys and locks shall be mastered to a<br />

single key as required by the local AHJ. JBLM locks shall be keyed to a 211<br />

key.<br />

1.5 SUBMITTALS<br />

Government approval is required for submittals with a "G" designation;<br />

submittals not having a "G" designation are for information only. When<br />

used, a designation following the "G" designation identifies the office that<br />

will review the submittal for the Government. Submit the following in<br />

accordance with Section 01 33 00 SUBMITTAL PROCEDURES:<br />

SD-02 Shop Drawings<br />

Annotated catalog data, in table format on the drawings, showing<br />

manufacturer's name, model, voltage, and catalog numbers for<br />

equipment and components. Submitted shop drawings shall not be<br />

smaller than ISO A1.<br />

Wiring Diagrams; G<br />

Point-to-point wiring diagrams showing the points of connection<br />

and terminals used for electrical field connections in the system,<br />

including interconnections between the equipment or systems that<br />

are supervised or controlled by the system. Diagrams shall show<br />

connections from field devices to the FACP and remote fire alarm<br />

control units, initiating circuits, switches, relays and terminals.<br />

Complete riser diagrams indicating the wiring sequence of devices<br />

and their connections to the control equipment. Include a color<br />

code schedule for the wiring. Include floor plans showing the<br />

locations of devices and equipment.<br />

System Layout; G<br />

Plan view drawing showing device locations, terminal cabinet<br />

locations, junction boxes, other related equipment, conduit<br />

routing, wire counts, circuit identification in each conduit, and<br />

circuit layouts for all floors. Drawings shall comply with the<br />

requirements of NFPA 170, Fire Safety Symbols.<br />

System Operation; G<br />

A complete list of device addresses and corresponding messages.<br />

Notification Appliances; G<br />

Data on each circuit to indicate that there is at least 25<br />

percent spare capacity for notification appliances, 25 percent<br />

spare capacity for initiating devices. Annotate data for each<br />

circuit on the drawings.<br />

Amplifiers; G<br />

SECTION 28 31 76 Page 8


Data to indicate that the amplifiers have sufficient capacity to<br />

simultaneously drive all notification speakers at the maximum<br />

rating plus 50 percent spare capacity. Annotate data for each<br />

circuit on the drawings.<br />

As-Built Drawings; G<br />

Three sets of detailed as-built drawings. Furnish one set of CD<br />

or DVD discs containing software back-up and CAD based drawings in<br />

latest version of AutoCAD and DXF format of as-built drawings and<br />

schematics. The drawings shall include complete wiring diagrams<br />

showing connections between devices and equipment, both factory and<br />

field wired. Include a riser diagram and drawings showing the asbuilt<br />

location of devices and equipment. The drawings shall show<br />

the system as installed, including deviations from both the project<br />

drawings and the approved shop drawings. These drawings shall be<br />

submitted within two weeks after the final acceptance test of the<br />

system. At least one set of as-built (marked-up) drawings shall be<br />

provided at the time of, or prior to the final acceptance test.<br />

As-built drawings shall show the sequence of operation table,<br />

details of the different devices and the external wiring<br />

connections, exact run of conduit, quantity of wires, wire color<br />

code, location of every initiating device, signaling device,<br />

module, and any major junction boxes or power supplies. Plans shall<br />

show Loop numbers and the address of each device or module.<br />

SD-03 Product Data<br />

UL or FM listing cards for equipment provided.<br />

Technical Data And Computer Software; G<br />

Fire alarm control panel (FACP); G<br />

Fire Alarm And Mass Notification Control Panel (FACP/FMCP); G<br />

Terminal cabinets/assemblies; G<br />

Manual stations; G<br />

Transmitters (including housing); G<br />

Batteries; G<br />

Battery chargers; G<br />

Smoke sensors; G<br />

Thermal sensors; G<br />

Wiring and cable; G<br />

Notification appliances; G<br />

Addressable interface devices; G<br />

Amplifiers; G<br />

Tone generators; G<br />

Digitalized voice generators; G<br />

Firefighter telephone; G<br />

Waterflow detectors; G<br />

Tamper switches; G<br />

Electromagnetic door holders; G<br />

Remote fire alarm control units; G<br />

Radio transmitter and interface panels; G<br />

Digital alarm communicator transmitter (DACT); G<br />

SD-05 <strong>Design</strong> Data<br />

System Operation; G<br />

SECTION 28 31 76 Page 9


A complete description of the system operation in matrix format<br />

on the drawings.<br />

Battery power; G<br />

Battery calculations as required in paragraph Battery Power<br />

Calculations.<br />

SD-06 Test Reports<br />

Field Quality Control<br />

Testing Procedures; G<br />

Smoke sensor testing procedures; G<br />

SD-07 Certificates<br />

Company, Integrator, Programmer and Installer; G<br />

Proof of certifications of integrators, installers and maintenance<br />

personnel required by UFC 4-021-01 shall be provided.<br />

Certificate of Fitness<br />

Provide Certificate of Fitness for any individual,<br />

business, or firm engaged in the inspecting, designing, testing,<br />

maintaining or servicing of fire and life safety systems.<br />

SD-09 Manufacturer's Field Reports<br />

Mass Notification System; G<br />

A unique identifier for each device, including the control panel<br />

and initiating and indicating devices, with an indication of test<br />

results, and signature of the factory-trained technician of the<br />

control panel manufacturer and equipment installer. With reports<br />

on preliminary tests, include printer information. Include the<br />

NFPA 72 Record of Completion and NFPA 72 Inspection and Testing<br />

Form, with the appropriate test reports.<br />

SD-10 Operation and Maintenance Data<br />

Operation and Maintenance (O&M) Instructions; G<br />

Two complete hard copies and one electronic copy in Adobe Acrobat<br />

(.pdf) format on CD or DVD of the Operation and Maintenance<br />

Instructions, indexed and in booklet form. The Operation and<br />

Maintenance Instructions shall be a single volume or in separate<br />

volumes, and may be submitted as a Technical Data Package. Manuals<br />

shall be approved prior to training. Provide one set of as-built<br />

drawings, two copies of the fire alarm system database and all<br />

software/hardware required for programming/editing to the<br />

Department of Public Works at the time of acceptance testing.<br />

Original and backup copies of all software delivered for this<br />

project, on each type of CD/DVD media utilized.<br />

SECTION 28 31 76 Page 10


Instruction of Government Employees<br />

The installers training history for the employees involved with<br />

this contract.<br />

1.6 QUALITY ASSURANCE<br />

Equipment and devices shall be compatible and operable with existing station<br />

fire alarm system and shall not impair reliability or operational functions<br />

of existing supervising station fire alarm system.<br />

a. In NFPA publications referred to herein, consider advisory<br />

provisions to be mandatory, as though the word "shall" had been<br />

substituted for "should" wherever it appears; interpret reference to<br />

"authority having jurisdiction" as defined in UFC 3-600-01.<br />

b. The recommended practices stated in the manufacturer's literature<br />

or documentation shall be considered as mandatory requirements.<br />

c. Devices and equipment for fire alarm service shall be listed by UL<br />

Fire Prot Dir or approved by FM P7825a.<br />

1.6.1 Qualifications<br />

1.6.1.1 Company, Integrator, Programmer and Installer<br />

Proof of certifications of integrators, installers and maintenance personnel<br />

required by UFC 4-021-01 shall be provided prior to award.<br />

1.6.1.1 <strong>Design</strong> Services<br />

Installations requiring completion of installation drawings and<br />

specification or modifications of fire detection, fire alarm, mass<br />

notification system, fire suppression systems or mass notification systems<br />

shall require the services and review of a qualified engineer. For the<br />

purposes of meeting this requirement, a qualified engineer is defined as an<br />

individual meeting the requirements of UFC 3-600-01.<br />

1.6.1.2 Supervisor<br />

The installing Contractor shall provide the following: NICET Fire Alarm<br />

Technicians to perform the installation of the system. A NICET Level 3 Fire<br />

Alarm Technician shall supervise the installation of the fire alarm<br />

system/mass notification system. The Fire Alarm technicians supervising the<br />

installation of equipment shall be factory trained in the installation,<br />

adjustment, testing, and operation of the equipment specified herein and on<br />

the drawings. Any individual, business, or firm engaged in the inspecting,<br />

testing, maintaining, designing or servicing of fire and life safety systems<br />

and equipment shall be certified to perform these activities in accordance<br />

with Appendix G of FL REG 420-30. A certificate of fitness can be obtained<br />

by completing the Employee Application for Certification of Fitness with<br />

supporting credentials to the JBLM Fire Prevention branch. Allow five<br />

working days for processing of application for Certificate of Fitness.<br />

Contact the JBLM Fire Prevention Branch at 253-966-7155 or 253-966-1764 for<br />

additional information. Submit a copy of certificate of fitness to the<br />

SECTION 28 31 76 Page 11


Contracting Officer or the Contracting Officer's Representative prior to<br />

starting work on life safety system and equipment.<br />

1.6.1.3 Technician<br />

The installing Contractor shall provide the following: Fire Alarm<br />

Technicians with a minimum of four years of experience utilized to assist in<br />

the installation and terminate fire alarm/mass notification devices,<br />

cabinets and panels. The Fire Alarm technicians installing the equipment<br />

shall be factory trained in the installation, adjustment, testing, and<br />

operation of the equipment specified herein and on the drawings. Any<br />

individual, business, or firm engaged in the inspecting, testing,<br />

maintaining, designing or servicing of fire and life safety systems and<br />

equipment shall be certified to perform these activities in accordance with<br />

Appendix G of FL REG 420-30. A certificate of fitness can be obtained by<br />

completing the Employee Application for Certification of Fitness with<br />

supporting credentials to the JBLM Fire Prevention branch. Allow five<br />

working days for processing of application for Certificate of Fitness.<br />

Contact the JBLM Fire Prevention Branch at 253-966-7155 or 253-966-1764 for<br />

additional information. Submit a copy of certificate of fitness to the<br />

Contracting Officer or the Contracting Officer's Representative prior to<br />

starting work on life safety system and equipment.<br />

1.6.1.4 Installer<br />

The installing Contractor shall provide the following: Fire Alarm installer<br />

with a minimum of two years of experience utilized to assist in the<br />

installation of fire alarm/mass notification devices, cabinets and panels.<br />

An electrician shall be allowed to install wire or cable and to install<br />

conduit for the fire alarm system/mass notification system. The Fire Alarm<br />

installer shall be factory trained in the installation, adjustment, testing,<br />

and operation of the equipment specified herein and on the drawings. Any<br />

individual, business, or firm engaged in the inspecting, testing,<br />

maintaining, designing or servicing of fire and life safety systems and<br />

equipment shall be certified to perform these activities in accordance with<br />

Appendix G of FL REG 420-30. A certificate of fitness can be obtained by<br />

completing the Employee Application for Certification of Fitness with<br />

supporting credentials to the JBLM Fire Prevention branch. Allow five<br />

working days for processing of application for Certificate of Fitness.<br />

Contact the JBLM Fire Prevention Branch at 253-966-7155 or 253-966-1764 for<br />

additional information. Submit a copy of certificate of fitness to the<br />

Contracting Officer or the Contracting Officer's Representative prior to<br />

starting work on life safety system and equipment.<br />

1.6.1.5 Test Personnel<br />

The installing Contractor shall provide the following: Fire Alarm<br />

Technicians with a minimum of four years of experience utilized to test and<br />

certify the installation of the fire alarm/mass notification devices,<br />

cabinets and panels. The Fire Alarm technicians testing the equipment shall<br />

be factory trained in the installation, adjustment, testing, and operation<br />

of the equipment specified herein and on the drawings. Any individual,<br />

business, or firm engaged in the inspecting, testing, maintaining, designing<br />

or servicing of fire and life safety systems and equipment shall be<br />

certified to perform these activities in accordance with Appendix G of FL<br />

REG 420-30. A certificate of fitness can be obtained by completing the<br />

Employee Application for Certification of Fitness with supporting<br />

SECTION 28 31 76 Page 12


credentials to the JBLM Fire Prevention branch. Allow five working days for<br />

processing of application for Certificate of Fitness. Contact the JBLM Fire<br />

Prevention Branch at 253-966-7155 or 253-966-1764 for additional<br />

information. Submit a copy of certificate of fitness to the Contracting<br />

Officer or the Contracting Officer's Representative prior to starting work<br />

on life safety system and equipment.<br />

1.6.1.6 Manufacturer's Representative<br />

The fire alarm and mass notification equipment manufacturer's representative<br />

shall be present for the connection of wiring to the control panel. The<br />

Manufacturer's Representative shall be an employee of the manufacturer with<br />

necessary technical training on the system being installed.<br />

1.6.1.7 Manufacturer<br />

Components shall be of current design and shall be in regular and recurrent<br />

production at the time of installation. Provide design, materials, and<br />

devices for a protected premises fire alarm system, complete, conforming to<br />

NFPA 72, except as otherwise or additionally specified herein.<br />

1.6.2 Regulatory Requirements<br />

1.6.2.1 Requirements for Fire Protection Service<br />

Equipment and material shall have been tested by UL and listed in UL Fire<br />

Prot Dir or approved by FM and listed in FM P7825a. Where the terms<br />

"listed" or "approved" appear in this specification, they shall mean listed<br />

in UL Fire Prot Dir or FM P7825a. The omission of these terms under the<br />

description of any item of equipment described shall not be construed as<br />

waiving this requirement. All listings or approval by testing laboratories<br />

shall be from an existing ANSI or UL published standard.<br />

1.6.2.2 Mass Notification System<br />

The equipment furnished shall be compatible and be UL listed, FM approved,<br />

or approved or listed by a nationally recognized testing laboratory for the<br />

intended use. All listings or approval by testing laboratories shall be<br />

from an existing ANSI or UL published standard.<br />

1.6.2.3 Testing Services or Laboratories<br />

Fire alarm and fire detection equipment shall be constructed in accordance<br />

with UL Fire Prot Dir, UL Electrical Constructn, or FM P7825a.<br />

1.7 DELIVERY, STORAGE, AND HANDLING<br />

Protect equipment delivered and placed in storage from the weather,<br />

humidity, and temperature variation, dirt and dust, and other contaminants.<br />

1.8 OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS<br />

The Interior Fire Alarm And Mass Notification System Operation and<br />

Maintenance Instructions shall include:<br />

a. "Manufacturer Data Package 5" as specified in Section 01 78 23<br />

OPERATION AND MAINTENANCE DATA.<br />

SECTION 28 31 76 Page 13


. Operating manual outlining step-by-step procedures required for<br />

system startup, operation, and shutdown. The manual shall include the<br />

manufacturer's name, model number, service manual, parts list, and<br />

complete description of equipment and their basic operating features.<br />

c. Maintenance manual listing routine maintenance procedures, possible<br />

breakdowns and repairs, and troubleshooting guide. The manuals shall<br />

include conduit layout, equipment layout and simplified wiring, and<br />

control diagrams of the system as installed.<br />

d. The manuals shall include complete procedures for system revision<br />

and expansion, detailing both equipment and software requirements.<br />

e. Software delivered for this project shall be provided, on each type<br />

of CD/DVD media utilized. All passwords and codes required to utilize<br />

the software shall be provided to the government with the media.<br />

f. Printouts of configuration settings for all devices.<br />

g. Routine maintenance checklist. The routine maintenance checklist<br />

shall be arranged in a columnar format. The first column shall list<br />

all installed devices, the second column shall state the maintenance<br />

activity or state no maintenance required, the third column shall state<br />

the frequency of the maintenance activity, and the fourth column for<br />

additional comments or reference.<br />

1.9 EXTRA MATERIALS<br />

1.9.1 Warranty, Repair Service/Replacement Parts<br />

Warranty for materials and labor shall be one year from the date of final<br />

acceptance by the Contracting Officer. During guarantee period, the service<br />

technician shall be on-site within 24 hours or the next business day after<br />

notification. All repairs shall be completed within 24 hours of arrival onsite.<br />

1.9.2 Interchangeable Parts<br />

Spare parts furnished shall be directly interchangeable with the<br />

corresponding components of the installed system. Spare parts shall be<br />

suitably packaged and identified by nameplate, tagging, or stamping. Spare<br />

parts shall be delivered to the Contracting Officer at the time of the final<br />

acceptance testing.<br />

1.9.3 Spare Parts<br />

Furnish to the Contracting Officer software (including proprietary software,<br />

codes, and passwords) connecting cables, proprietary equipment necessary for<br />

the maintenance, testing, and reprogramming of the equipment.<br />

Furnish the following spare parts and accessories:<br />

a. Four fuses for each fused circuit<br />

1.9.4 Special Tools<br />

SECTION 28 31 76 Page 14


Software, connecting cables and proprietary equipment, necessary for the<br />

maintenance, testing, and reprogramming of the equipment shall be furnished<br />

to the Contracting Officer.<br />

PART 2<br />

PRODUCTS<br />

2.1 MATERIALS AND EQUIPMENT<br />

2.1.1 Standard Products<br />

Provide materials, equipment, and devices that have been tested by a<br />

nationally recognized testing laboratory, such as UL or FM, and listed or<br />

approved for fire protection service when so required by NFPA 72 or this<br />

specification. Select material from one manufacturer, where possible, and<br />

not a combination of manufacturers, for any particular classification of<br />

materials. Material and equipment shall be the standard products of a<br />

manufacturer regularly engaged in the manufacture of the products for at<br />

least two years prior to bid opening. Preferred Materials/Manufacturers:<br />

Silent Knight, EST, Simplex, Notifier. Fire alarm transmitters shall be<br />

equal in all aspects to Monaco transmitter.<br />

2.1.2 Nameplates<br />

Major components of equipment shall have the manufacturer's name, address,<br />

type or style, model or serial number, catalog number, date of installation,<br />

installing Contractor's name and address, and the contract number provided<br />

on a new plate permanently affixed to the item or equipment. Major<br />

components include, but are not limited to, the following:<br />

a. FACPs<br />

b. Automatic transmitter<br />

c. Printer<br />

Furnish nameplates to obtain approval by the Contracting Officer before<br />

installation. Obtain approval by the Contracting Officer for installation<br />

locations. Nameplates shall be etched metal or plastic, permanently<br />

attached by screws to panels or adjacent walls.<br />

2.2 GENERAL PRODUCT REQUIREMENT<br />

All fire alarm and mass notification equipment shall be listed for use under<br />

the applicable reference standards. Interfacing of Listed UL 864 or similar<br />

approved industry listing with Mass Notification Panels listed to UL 2017 or<br />

equal shall be done in a laboratory listed configuration, if the software<br />

programming features cannot provide a listed interface control. If a field<br />

modification is needed, such as adding equipment like relays, the<br />

manufacturer of the panels being same or different brand from manufacturer<br />

shall provide the installing contractor for review and confirmation by the<br />

installing contractor. The installing contractor shall, as part of the<br />

submittal documents, provide this information.<br />

2.3 <strong>SYSTEM</strong> OPERATION<br />

The Addressable Interior Fire Alarm and Mass Notification System shall be a<br />

complete, supervised, noncoded, analog/addressable fire alarm and mass<br />

notification system conforming to NFPA 72, UL 864 Ninth Edition, and UL<br />

2017. The system shall be activated into the alarm mode by actuation of any<br />

SECTION 28 31 76 Page 15


alarm initiating device. The system shall remain in the alarm mode until<br />

the initiating device is reset and the fire alarm control panel is reset and<br />

restored to normal. The system may be placed in the alert mode by local<br />

microphones or remotely from authorized locations/users.<br />

2.3.1 Alarm Initiating Devices<br />

Connect alarm initiating devices to initiating device circuits (IDC), Style<br />

D, or to signal line circuits (SLC), Style 6 and installed in accordance<br />

with NFPA 72. The system shall have an interconnected riser loop or network<br />

having Style 6 supervision for interconnection of other FA/MNS control<br />

panels.<br />

a. Alarm notification appliances shall be connected to the Voice<br />

Notification System, Style Z in accordance with NFPA 72. A looped<br />

conduit system shall be provided so that if the conduit and all<br />

conductors within are severed or exposed to fire at any point, all IDC,<br />

NAC and SLC will remain functional. Should the design or building<br />

layout preclude separation then a fire rated separation shall be<br />

provided in accordance with NFPA 72. The return portion of the loop<br />

shall be remote from the supply portion of the loop.<br />

b. Where the building has two stairs for egress from floors above<br />

grade, a single impairment cannot adversely affect more than one floor.<br />

Where three or more stairs are provided for egress from floors above<br />

grade, a single impairment cannot adversely affect more than 1/2 of any<br />

floor. Any single impairment of the system shall not affect the system<br />

on more than one-half of any floor.<br />

c. The system shall operate in the alarm mode upon actuation of any<br />

alarm initiating device. The system shall remain in the alarm mode<br />

until initiating device(s) are reset and the fire alarm control panel<br />

is manually reset and restored to normal. The conduit loop requirement<br />

is not applicable to the signal transmission link from the local panels<br />

(at the protected premises) to the Supervising Station (fire station,<br />

fire alarm central communication center). Audible, and visual<br />

appliances and systems shall comply with NFPA 72. Fire alarm<br />

system/mass notification system components requiring power, except for<br />

the control panel power supply, shall operate on 24 Volts dc.<br />

2.3.2 Functions and Operating Features<br />

The system shall provide the following functions and operating features:<br />

a. The FACP/FMCP and fire alarm and mass notification control units,<br />

if used, shall provide power, annunciation, supervision, and control<br />

for the system. Addressable systems shall be microcomputer<br />

(microprocessor or microcontroller) based with a minimum word size of<br />

eight bits with sufficient memory to perform as specified.<br />

b. Provide Style B initiating device circuits for conductor lengths of<br />

10 feet or less.<br />

c. Provide Style 6 signaling line circuits for each floor.<br />

d. Provide Style 6 signaling line circuits for the network.<br />

SECTION 28 31 76 Page 16


e. Provide Style Z notification appliance circuits. The visual alarm<br />

notification appliances shall have the flash rates synchronized.<br />

f. Provide electrical supervision of the primary power (AC) supply,<br />

presence of the battery, battery voltage, and placement of system<br />

modules within the control panel.<br />

g. Provide an audible and visual trouble signal to activate upon a<br />

single break or open condition, or ground fault. The trouble signal<br />

shall also operate upon loss of primary power (AC) supply, absence of a<br />

battery supply, low battery voltage, or removal of alarm or supervisory<br />

panel modules. Provide a trouble alarm silence feature that shall<br />

silence the audible trouble signal, without affecting the visual<br />

indicator. After the system returns to normal operating conditions,<br />

the trouble signal shall again sound until the trouble is acknowledged.<br />

A smoke sensor in the process of being verified for the actual presence<br />

of smoke shall not initiate a trouble condition.<br />

h. Provide a notification appliance silencing switch, that when<br />

activated, will silence the audible signal appliance, but will not<br />

affect the visual alarm indicator, the liquid crystal display, or the<br />

automatic notification of the JBLM Emergency Control Center in building<br />

4101.. This switch shall be overridden upon activation of a subsequent<br />

alarm.<br />

i. Provide alarm verification capability for smoke sensors. Alarm<br />

verification shall initially be set for 30 seconds.<br />

j. Provide program capability via switches in a locked portion of the<br />

FACP to bypass the automatic notification appliance circuits, fire<br />

reporting system, air handler shutdown, smoke control operation,<br />

elevator recall and door release features. Operation of this<br />

programming shall indicate this action on the FACP display and printer<br />

output.<br />

k. Alarm, supervisory, and/or trouble signals shall be automatically<br />

transmitted to the JBLM Emergency Control Center in building 4101..<br />

l. Alarm functions shall override trouble or supervisory functions.<br />

Supervisory functions shall override trouble functions.<br />

m. The system shall be capable of being programmed from the panel’s<br />

keyboard. Programmed information shall be stored in non-volatile<br />

memory.<br />

n. The system shall be capable of operating, supervising, and/or<br />

monitoring both addressable and non-addressable alarm and supervisory<br />

devices.<br />

o. There shall be no limit, other than maximum system capacity, as to<br />

the number of addressable devices that may be in alarm simultaneously.<br />

p. Where the fire alarm system is responsible for initiating an action<br />

in another emergency control device or system, such as an HVAC system,<br />

an atrium exhaust system, a smoke control system, or an elevator<br />

system, the addressable fire alarm relay shall be within 3 feet of the<br />

emergency control device.<br />

SECTION 28 31 76 Page 17


q. An alarm signal shall automatically initiate the following<br />

functions:<br />

(1) Transmission of an alarm signal to the JBLM Emergency Control<br />

Center in building 4101.<br />

(2) Visual indication of the device operated on the fire alarm<br />

control panel (FACP), and on the graphic annunciator. Indication<br />

on the graphic annunciator, if required by code, shall be by floor,<br />

zone or circuit, and type of device.<br />

(3) Continuous actuation of all alarm notification appliances,<br />

except those in stairs or in elevator cabs.<br />

(4) Recording of the event in the system history log of the fire<br />

control system unit.<br />

(5) Release of doors held open by electromagnetic devices.<br />

(6) Operation of the smoke control system and atrium exhaust<br />

system as stated in the Delivery or Task Order.<br />

(7) Release of power to electric locks on doors that are part of<br />

the means of egress.<br />

(8) Operation of a smoke sensor in an elevator lobby or other<br />

location associated with the automatic recall of elevators, shall<br />

recall the elevators in addition to other requirements of this<br />

paragraph.<br />

(9) Operation of a duct smoke sensor shall shut down the<br />

appropriate air handler in accordance with NFPA 90A in addition to<br />

other requirements of this paragraph.<br />

(10) Operation of a sprinkler waterflow switch serving an<br />

elevator machinery room or elevator shaft shall operate shunt trip<br />

circuit breaker(s) to shut down power to the elevators in<br />

accordance with ASME A17.1.<br />

(11) Operation of an interface, that operates vibrating pagers<br />

worn by hearing-impaired occupants.<br />

r. A supervisory signal shall automatically initiate the following<br />

functions:<br />

(1) Visual indication of the device operated on the FACP (VDU),<br />

and on the graphic annunciator, and sound the audible alarm at the<br />

respective panel.<br />

(2) Transmission of a supervisory signal to the JBLM Emergency<br />

Control Center in building 4101.<br />

(3) Recording of the event electronically in the history log of<br />

the fire control system unit.<br />

SECTION 28 31 76 Page 18


s. A trouble condition shall automatically initiate the following<br />

functions:<br />

(1) Visual indication of the system trouble on the FACP (VDU),<br />

and on the graphic annunciator, and sound the audible alarm at the<br />

respective panel.<br />

(2) Transmission of a trouble signal to the JBLM Emergency<br />

Control Center in building 4101.<br />

(3) Recording of the event in the system history log of the fire<br />

control system unit.<br />

t. The maximum permissible elapsed time between the actuation of an<br />

initiating device and its indication at the FACP shall be 10 seconds.<br />

u. The maximum elapsed time between the occurrence of the trouble<br />

condition and its indication at the FACP shall not exceed 200 seconds.<br />

2.4 <strong>SYSTEM</strong> MONITORING<br />

2.4.1 Valves<br />

Each valve affecting the proper operation of a fire protection system,<br />

including automatic sprinkler control valves, standpipe control valves,<br />

sprinkler service entrance valve, valves at fire pumps, isolating valves for<br />

pressure type waterflow or supervision switches, and valves at backflow<br />

preventers, whether supplied under this contract or existing, shall be<br />

electrically monitored to ensure its proper position. Each tamper switch<br />

shall be provided with a separate address.<br />

2.4.2 Independent Fire Detection System<br />

Each existing independent smoke detection subsystem, and kitchen fire<br />

extinguishing system shall be monitored both for the presence of an alarm<br />

condition and for a trouble condition. Each monitored condition shall be<br />

provided with a separate address.<br />

2.5 MASS NOTIFICATION <strong>SYSTEM</strong> FUNCTIONS<br />

2.5.1 System Requirements<br />

System mass notification hardware shall integrate with the Monaco D21 fire<br />

system through the use of a mass notification panel or a fire/mass<br />

notification combination panel. System shall be programmed and integrated<br />

with the existing head end hardware and work station(s) and made capable of<br />

remote activation from the JBLM Emergency Operation Command (FLEC) facility.<br />

Remote activation connectivity between the FLEC and project shall be through<br />

the Monaco BT-XM transmitter panel. Mass Notification/Public Announcement<br />

Systems Integration is allowed for smaller systems. It is not recommended<br />

for larger projects. However, it is not prohibited, provided the following<br />

system(s) engineering design requirements are included as part of the<br />

overall integration:<br />

a. They shall share the same comm/power raceways and speaker.<br />

SECTION 28 31 76 Page 19


. PA must have its own power supply and amplifier. It shall not share<br />

the same amp as the Mass Notification System.<br />

c. PA system control panel shall be separate and stand alone from the<br />

MNS panel (Anti-Feed back issues must be addressed and eliminated if<br />

co-locating or if Local Operating Console (LOC) is placed near the LOC<br />

for either of these systems).<br />

d. Two panels are clearly labeled and easily identified as either PA<br />

or MNS.<br />

e. PA panel lock set is not the same as the MNS panel. AHJ will<br />

provide core information.<br />

f. PA shall not share any UPS or back-up power source used to support<br />

MNS.<br />

g. PA commands/messaging shall be subordinate to MNS/Fire Alarm<br />

messaging.<br />

h. PA system shall not remote tie in to the FLEC.<br />

i. Speaker technology shall be designed to meet the minimum<br />

requirements for MNS.<br />

j. Mass Notification System Visual alerting devices shall not light<br />

upon activation of the PA system.<br />

2.5.1 Notification Appliance Network<br />

The notification appliance network consists of audio speakers located to<br />

provide intelligible instructions at all locations in the building. The<br />

Mass Notification System announcements shall take priority over all other<br />

function of the system including the audible and visual output of the fire<br />

alarm system in a normal or alarm state. All fire alarm system functions<br />

shall continue in an alarm state except for the output signals of the<br />

audible and visual notification appliances.<br />

2.5.2 Strobes<br />

Strobes are also provided to alert hearing-impaired occupants.<br />

2.5.3 Text Displays<br />

LED text displays for hearing impaired occupants.<br />

2.5.4 Giant Voice<br />

The Giant Voice system (if available) in the area of the building shall be<br />

activated to provide a pre-recorded or live voice message.<br />

2.5.5 Door Operation<br />

Closure of doors held open by electromagnetic devices.<br />

2.5.6 Voice Notification<br />

SECTION 28 31 76 Page 20


An autonomous voice notification control unit is used to monitor and control<br />

the notification appliance network and provide consoles for local operation.<br />

Using a console, personnel in the building can initiate delivery of prerecorded<br />

voice messages, provide live voice messages and instructions, and<br />

initiate visual strobe and (optional) textual message notification<br />

appliances. The autonomous voice notification control unit will temporarily<br />

override audible fire alarm notification while delivering Mass Notification<br />

messages to ensure they are intelligible.<br />

2.5.7 Base-Wide Control<br />

If a base-wide control system for mass notification exists on the base, the<br />

autonomous control unit shall communicates with the central control unit of<br />

the base-wide system. The autonomous control unit shall receive<br />

commands/messages from the central control unit and provide status<br />

information.<br />

2.6 OVERVOLTAGE AND SURGE PROTECTION<br />

2.6.1 Signaling Line Circuit Surge Protection<br />

For systems having circuits located outdoors, communications equipment shall<br />

be protected against surges induced on any signaling line circuit and shall<br />

comply with the applicable requirements of IEEE C62.41.1 and IEEE C62.41.2.<br />

Cables and conductors that serve as communications links shall have surge<br />

protection circuits installed at each end that meet the following<br />

waveform(s):<br />

a. A 10 microsecond by 1000 microsecond waveform with a peak voltage<br />

of 1500 volts and a peak current of 60 amperes.<br />

b. An 8 microsecond by 20 microsecond waveform with a peak voltage of<br />

1000 volts and a peak current of 500 amperes. Protection shall be<br />

provided at the equipment. Additional triple electrode gas surge<br />

protectors, rated for the application, shall be installed on each<br />

wireline circuit within 3 feet of the building cable entrance. Fuses<br />

shall not be used for surge protection.<br />

2.6.2 Sensor Wiring Surge Protection<br />

Digital and analog inputs and outputs shall be protected against surges<br />

induced by sensor wiring installed outdoors and as shown. The inputs and<br />

outputs shall be tested with the following waveforms:<br />

a. A 10 by 1000 microsecond waveform with a peak voltage of 1500 volts<br />

and a peak current of 60 amperes.<br />

b. An 8 by 20 microsecond waveform with a peak voltage of 1000 volts<br />

and a peak current of 500 amperes. Fuses shall not be used for surge<br />

protection.<br />

2.7 ADDRESSABLE INTERFACE DEVICES<br />

The initiating device being monitored shall be configured as a Style D<br />

initiating device circuits. The system shall be capable of defining any<br />

module as an alarm module and report alarm trouble, loss of polling, or as a<br />

supervisory module, and reporting supervisory short, supervisory open or<br />

SECTION 28 31 76 Page 21


loss of polling such as waterflow switches, valve supervisory switches, fire<br />

pump monitoring, independent smoke detection systems, relays for output<br />

function actuation, etc. The module shall be UL or FM listed as compatible<br />

with the control panel. The monitor module shall provide address setting<br />

means compatible with the control panel's SLC supervision and store an<br />

internal identifying code. Monitor module shall contain an integral LED<br />

that flashes each time the monitor module is polled. Pull stations with a<br />

monitor module in a common backbox are not required to have an LED. Where<br />

indicated, existing fire alarm system initiating device circuits shall be<br />

connected to a single module to power and supervise the circuit.<br />

2.8 ADDRESSABLE CONTROL MODULE<br />

The control module shall be capable of operating as a relay (dry contact<br />

form C) for interfacing the control panel with other systems, and to control<br />

door holders or initiate elevator fire service. The module shall be UL or<br />

FM listed as compatible with the control panel. The indicating device or<br />

the external load being controlled shall be configured as a Style Y<br />

notification appliance circuits. The system shall be capable of<br />

supervising, audible, visual and dry contact circuits. The control module<br />

shall have both an input and output address. The supervision shall detect a<br />

short on the supervised circuit and shall prevent power from being applied<br />

to the circuit. The control model shall provide address setting means<br />

compatible with the control panel's SLC supervision and store an internal<br />

identifying code. The control module shall contain an integral LED that<br />

flashes each time the control module is polled. Control Modules shall be<br />

located in environmental areas that reflect the conditions to which they<br />

were listed.<br />

2.9 ISOLATION MODULES<br />

Provide isolation modules to subdivide each signaling line circuit into<br />

groups of not more than 20 addressable devices between adjacent isolation<br />

modules.<br />

2.10 SMOKE SENSORS<br />

2.10.1 Photoelectric Smoke Sensors<br />

Provide addressable photoelectric smoke sensors as follows:<br />

a. Provide analog/addressable photoelectric smoke sensors utilizing<br />

the photoelectric light scattering principle for operation in<br />

accordance with UL 268. Smoke sensors shall be listed for use with the<br />

fire alarm control panel.<br />

b. Provide self-restoring type sensors that do not require any<br />

readjustment after actuation at the FACP to restore them to normal<br />

operation. Sensors shall be UL listed as smoke-automatic fire sensors.<br />

c. Components shall be rust and corrosion resistant. Vibration shall<br />

have no effect on the sensor's operation. Protect the detection<br />

chamber with a fine mesh metallic screen that prevents the entrance of<br />

insects or airborne materials. The screen shall not inhibit the<br />

movement of smoke particles into the chamber.<br />

SECTION 28 31 76 Page 22


d. Provide twist lock bases for the sensors. The sensors shall<br />

maintain contact with their bases without the use of springs. Provide<br />

companion mounting base with screw terminals for each conductor.<br />

Terminate field wiring on the screw terminals. The sensor shall have a<br />

visual indicator to show actuation.<br />

e. The sensor address shall identify the particular unit, its location<br />

within the system, and its sensitivity setting. Sensors shall be of<br />

the low voltage type rated for use on a 24 VDC system.<br />

f. Public Works Fire Alarm Maintenance Technicians shall have the<br />

capability to manually access the following information for each<br />

initiating device.<br />

(1) Primary status<br />

(2) Device type<br />

(3) Present average value<br />

(4) Present sensitivity selected<br />

(5) Sensor range (normal, dirty, etc.)<br />

2.10.2 Ionization Type Smoke Sensors<br />

Provide addressable ionization type smoke sensors as follows:<br />

a. Provide analog smoke sensors that operate on the ionization<br />

principle and are actuated by the presence of visible or invisible<br />

products of combustion. Smoke sensors shall be listed for use with the<br />

fire alarm control panel. Manufacturers of ionization detectors shall<br />

provide for no cost disposal of their detectors.<br />

b. Provide self-restoring type sensors that do not require any<br />

readjustment after actuation at the FACP to restore them to normal<br />

operation. Sensors shall be UL or FM listed as smoke-automatic fire<br />

sensors.<br />

c. Components shall be rust and corrosion resistant. Vibration shall<br />

have no effect on the sensor's operation. Protect the detection<br />

chamber with a fine mesh metallic screen that prevents the entrance of<br />

insects or airborne materials. The screen shall not inhibit the<br />

movement of smoke particles into the chamber.<br />

d. Provide twist lock bases for the sensors. The sensors shall<br />

maintain contact with their bases without the use of springs. Provide<br />

companion mounting base with screw terminals for each conductor.<br />

Terminate field wiring on the screw terminals. The sensor shall have a<br />

visual indicator to show actuation.<br />

e. The sensor address shall identify the particular unit, its location<br />

within the system, and its sensitivity setting. Sensors shall be of<br />

the low voltage type rated for use on a 24 VDC system.<br />

SECTION 28 31 76 Page 23


f. Public Works Fire Alarm Maintenance Technicians shall have the<br />

capability to manually access the following information for each<br />

initiating device.<br />

(1) Primary status<br />

(2) Device type<br />

(3) Present average value<br />

(4) Present sensitivity selected<br />

(5) Sensor range (normal, dirty, etc.)<br />

(6) Sensitivity adjustments for smoke detectors.<br />

2.10.3 Projected Beam Smoke Detectors<br />

Detectors shall be designed for detection of abnormal smoke densities.<br />

Detectors shall consist of separate transmitter and receiver units. The<br />

transmitter unit shall emit an infrared beam to the receiver unit. When the<br />

signal at the receiver falls below a preset sensitivity, the detector shall<br />

initiate an alarm. The receiver shall contain an LED that is powered upon<br />

an alarm condition. Long-term changes to the received signal caused by<br />

environmental variations shall be automatically compensated. Detectors<br />

shall incorporate features to assure that they are operational; a trouble<br />

signal shall be initiated if the beam is obstructed, the limits of the<br />

compensation circuit are reached, or the housing cover is removed.<br />

Detectors shall have multiple sensitivity settings in order to meet UL<br />

listings for the different distances covered by the beam. In the event of<br />

beam interference for more than three seconds a trouble alarm shall be<br />

transmitted.<br />

2.10.4 Duct Smoke Sensors<br />

Duct-mounted photoelectric smoke detectors shall be furnished and installed<br />

where indicated and in accordance with NFPA 90A. Units shall consist of a<br />

smoke detector as specified in paragraph Photoelectric Detectors, mounted in<br />

a special housing fitted with duct sampling tubes. Detector circuitry shall<br />

be mounted in a metallic enclosure exterior to the duct. Detectors shall<br />

have a manual reset. Detectors shall be rated for air velocities that<br />

include air flows between 500 and 4000 fpm. Detectors shall be powered from<br />

the fire alarm panel.<br />

a. Sampling tubes shall run the full width of the duct. The duct<br />

detector package shall conform to the requirements of NFPA 90A, UL<br />

268A, and shall be UL listed for use in air-handling systems. The<br />

control functions, operation, reset, and bypass shall be controlled<br />

from the fire alarm control panel.<br />

b. Lights to indicate the operation and alarm condition; and the test<br />

and reset buttons shall be visible and accessible with the unit<br />

installed and the cover in place. Detectors mounted above 6 feet and<br />

those mounted below 6 feet that cannot be easily accessed while<br />

standing on the floor, shall be provided with a remote detector<br />

indicator panel containing test and reset switches.<br />

SECTION 28 31 76 Page 24


c. Remote lamps and switches as well as the affected fan units shall<br />

be properly identified in etched plastic placards. Detectors shall<br />

provide for control of auxiliary contacts that provide control,<br />

interlock, and shutdown functions specified in Section 23 09 23 DIRECT<br />

DIGITAL CONTROL FOR HVAC AND OTHER LOCAL BUILDING <strong>SYSTEM</strong>S. Auxiliary<br />

contacts provide for this function shall be located within 3 feet of<br />

the controlled circuit or appliance. The detectors shall be supplied<br />

by the fire alarm system manufacturer to ensure complete system<br />

compatibility.<br />

2.10.5 Smoke Sensor Testing<br />

Smoke sensors shall be tested in accordance with NFPA 72 and manufacturer's<br />

recommended calibrated test method. Submit smoke sensor testing procedures<br />

for approval.<br />

2.11 THERMAL SENSORS<br />

2.11.1 Heat Detectors<br />

Heat detectors shall be designed for detection of fire by fixed temperature,<br />

combination fixed temperature and rate-of-rise principle or ratecompensating<br />

principle as stated in the Delivery or Task Order. The alarm<br />

condition shall be determined by comparing sensor valve with the stored<br />

values. Heat detector spacing shall be rated in accordance with UL 521.<br />

Detectors located in areas subject to moisture, exterior atmospheric<br />

conditions, or hazardous locations as defined by NFPA 70 and as shown on<br />

drawings, shall be types approved for such locations.<br />

2.11.1.1 Combination Fixed-Temperature and Rate-of-Rise Detectors<br />

Detectors shall be designed for outlet box mounting and supported<br />

independently of wiring connections. Contacts shall be self-resetting after<br />

response to rate-of-rise principle. Under fixed temperature actuation, the<br />

detector shall have a permanent external indication that is readily visible.<br />

Detector units located in boiler rooms, showers, or other areas subject to<br />

abnormal temperature changes shall operate on fixed temperature principle<br />

only. The UL 521 test rating for the fixed temperature portion shall be 135<br />

degrees F or as shown. The UL 521 test rating for the Rate-of-Rise<br />

detectors shall be rated for 50 by 50 feet.<br />

2.11.1.2 Rate Compensating Detectors<br />

Detector mounting type shall be as stated in the Delivery or Task Order,<br />

with outlet box supported independently of wiring connections. Detectors<br />

shall be hermetically sealed and automatically resetting. Rate Compensated<br />

detectors shall be rated for 50 by 50 feet.<br />

2.11.1.3 Fixed Temperature Detectors<br />

Detectors shall be designed for outlet box mounting and supported<br />

independently of wiring connections. Detectors shall be designed to detect<br />

high heat. The detectors shall have a specific temperature setting of 135<br />

degrees F or as shown. The UL 521 test rating for the fixed temperature<br />

detectors shall be rated for 15 by 15 feet.<br />

SECTION 28 31 76 Page 25


2.11.2 Heat Sensing<br />

A moving average of the sensors heat sensing value to automatically<br />

compensate for conditions that could affect detection operations. System<br />

shall automatically maintain a constant heat sensing sensitivity from each<br />

sensor by compensating for environmental factors.<br />

2.11.3 Self-Test Routines<br />

Automatic self-test routines shall be performed on each sensor that will<br />

functionally check sensor sensitivity electronics and ensure the accuracy of<br />

the value being transmitted. Any sensor that fails this test shall indicate<br />

a trouble condition with the sensor location at the control panel.<br />

2.11.4 Operator Access<br />

Public Works Fire Alarm Maintenance Technicians shall have the capability to<br />

manually access the following information for each heat sensor:<br />

a. Primary status<br />

b. Device type<br />

c. Present average value<br />

d. Sensor range<br />

2.11.5 Operator Control<br />

Public Works Fire Alarm Maintenance Technicians shall have the capability to<br />

manually control the following information for each heat sensor:<br />

a. Alarm detection sensitivity values<br />

b. Enable or disable the point/device<br />

c. Control sensors relay driver output<br />

2.12 FLAME DETECTORS<br />

The detectors shall comply with FM P7825a. The detectors shall be sensitive<br />

to the micron range best suited for their intended use. The detectors shall<br />

operate over electrically supervised wiring circuits and the loss of power<br />

to the detector shall result in a trouble signal. A self-test feature shall<br />

be provided for each detector to be individually tested.<br />

2.12.1 Infrared (IR) Single Frequency Flame Detector<br />

The detector shall be sensitive in the range best suited for the intended<br />

service.<br />

2.12.2 Infrared (IR) Multiple Frequency Flame Detector<br />

The IR detector shall consist of two or more IR sensors, each selected for a<br />

different IR frequency. The primary sensor shall be sensitive in the range<br />

best suited for the intended service. Secondary sensors are tuned to<br />

SECTION 28 31 76 Page 26


different IR wavelengths to null out the effect of black body radiation to<br />

the primary sensor.<br />

2.12.3 Ultraviolet (UV) Flame Detectors<br />

UV flame detector shall be of the narrow band response type that operates on<br />

radiated ultraviolet energy and shall be sensitive in the range best suited<br />

for the intended service. The cone of vision shall be 80 degrees or<br />

greater. Each detector shall be completely insensitive to light sources in<br />

the visible frequency range.<br />

2.12.4 Combination UV/IR Flame Detector<br />

The UV/IR detector shall provide discrimination against false alarms by<br />

requiring both UV and IR flame detection before an alarm is sent. The UV<br />

sensor shall be sensitive in the range of 0.185 to 0.265 micrometers only.<br />

The IR sensor shall be sensitive in the range best suited for the intended<br />

service. Detectors shall be completely insensitive to light sources in the<br />

visible frequency range.<br />

2.13 ELECTRIC POWER<br />

2.13.1 Power Supply for the System<br />

Power shall be 120 VAC service for the FACP from the normal or emergency AC<br />

service to the building as stated in the Delivery or Task Order.<br />

2.13.2 Generator<br />

Where any emergency generator provides a standby power supply for life<br />

safety system circuits, provide a connection from one of the circuits for<br />

the fire alarm system. When a generator buss circuit is available for the<br />

fire alarm, mass notification, and life safety equipment, then the fire<br />

alarm control unit shall monitor the generator with the following<br />

supervisory signals:<br />

(a) Generator Selector Switch in a position other than automatic start<br />

(b) Generator Running<br />

(c) Low Fuel<br />

(d) Failure to Start<br />

(e) Abnormal conditions such as low oil, high temperature, and low<br />

coolant.<br />

(f) Low Battery<br />

(g) Emergency transfer in proper mode while generator running<br />

The Mass Notification system shall also be connected to the generator. If<br />

the generator is not installed for the specific purpose of powering life<br />

safety systems then this requirement does not apply. The designer should<br />

only apply this requirement in the instance when a generator is installed to<br />

power a fire pump or other life safety circuit.<br />

2.14 EMERGENCY POWER SUPPLY<br />

Provide for system operation in the event of primary power source failure.<br />

Transfer from normal to auxiliary (secondary) power or restoration from<br />

auxiliary to normal power shall be automatic and shall not cause<br />

transmission of a false alarm.<br />

SECTION 28 31 76 Page 27


2.14.1 Batteries<br />

Provide sealed, maintenance-free, lead acid batteries as the source for<br />

emergency power to the FACP. Batteries shall contain suspended electrolyte.<br />

The battery system shall be maintained in a fully charged condition by means<br />

of a solid state battery charger. Provide an automatic transfer switch to<br />

transfer the load to the batteries in the event of the failure of primary<br />

power.<br />

2.14.1.1 Capacity<br />

Provide the batteries with sufficient capacity to operate the system under<br />

supervisory and trouble conditions, including audible trouble signal devices<br />

for 72 hours and audible and visual signal devices under alarm conditions<br />

for an additional 15 minutes.<br />

2.14.1.2 Battery Power Calculations<br />

a. Verify that battery capacity exceeds supervisory and alarm power<br />

requirements.<br />

1). Substantiate the battery calculations for alarm, alert, and<br />

supervisory power requirements. Ampere-hour requirements for each<br />

system component and each panel component, and the batteryrecharging<br />

period shall be included.<br />

2). Provide complete battery calculations for both the alarm,<br />

alert, and supervisory power requirements. Ampere-hour<br />

requirements for each system component shall be submitted with the<br />

calculations.<br />

3). A voltage drop calculation to indicate that sufficient voltage<br />

is available for proper operation of the system and all components,<br />

at the minimum rated voltage of the system operating on batteries.<br />

b. For battery calculations use the following assumptions: Assume a<br />

starting voltage of 24 VDC for starting the calculations to size the<br />

batteries. Calculate the required Amp-Hours for the specified standby<br />

time, and then calculate the required Amp-Hours for the specified alarm<br />

time. Calculate the nominal battery voltage after operation on<br />

batteries for the specified time period. Using this voltage perform a<br />

voltage drop calculation for circuit containing device and/or<br />

appliances remote from the power sources.<br />

2.14.2 Battery Chargers<br />

Provide a solid state, fully automatic, variable charging rate battery<br />

charger. The charger shall be capable of providing 150 percent of the<br />

connected system load and shall maintain the batteries at full charge. In<br />

the event the batteries are fully discharged (18 Volts dc), the charger<br />

shall recharge the batteries back to 95 percent of full charge within 48<br />

hours. Provide pilot light to indicate when batteries are manually placed<br />

on a high rate of charge as part of the unit assembly if a high rate switch<br />

is provided.<br />

SECTION 28 31 76 Page 28


2.15 <strong>FIRE</strong> <strong>ALARM</strong> AND MASS NOTIFICATION CONTROL PANEL (FACP/FMCP)<br />

Provide a complete control panel fully enclosed in a lockable steel<br />

enclosure as specified herein. Operations required for testing or for<br />

normal care and maintenance of the systems shall be performed from the front<br />

of the enclosure. If more than a single unit is required at a location to<br />

form a complete control panel, the unit enclosures shall match exactly.<br />

a. Each control unit shall provide power, supervision, control, and<br />

logic for the entire system, utilizing solid state, modular components,<br />

internally mounted and arranged for easy access. Each control unit<br />

shall be suitable for operation on a 120 volt, 60 hertz, normal<br />

building power supply. Provide each panel with supervisory functions<br />

for power failure, internal component placement, and operation.<br />

b. Visual indication of alarm, supervisory, or trouble initiation on<br />

the fire alarm control panel shall be by liquid crystal display or<br />

similar means with a minimum of 80 characters, that at least 32 are<br />

field changeable. The MNS Control panel shall have the capability of<br />

temporarily deactivate the fire alarm audible notification appliances<br />

while delivering voice messages. Provide conductor integrity<br />

monitoring for strobe, display, temporary deactivation of fire alarm<br />

audible notification appliances and speaker wiring.<br />

c. Provide secure operator console for initiating recorded messages,<br />

strobes and displays; and for delivering live voice messages. Provide<br />

capacity for at least four pre-recorded messages. Provide the ability<br />

to automatically repeat pre-recorded messages. Provide a secure<br />

microphone for delivering live messages. Provide adequate discrete<br />

outputs to temporarily deactivate fire alarm audible notification, and<br />

initiate/synchronize strobes. Provide a complete set of selfdiagnostics<br />

for controller and appliance network. Provide local<br />

diagnostic information display and local diagnostic information and<br />

system event log file.<br />

2.15.1 Cabinet<br />

Install control panel components in cabinets large enough to accommodate all<br />

components and also to allow ample gutter space for interconnection of<br />

panels as well as field wiring. The enclosure shall be identified by an<br />

engraved laminated phenolic resin nameplate. Lettering on the nameplate<br />

shall say "Fire Alarm and Mass Notification Control Panel" and shall not be<br />

less than one inch high. Provide prominent rigid plastic or metal<br />

identification plates for lamps, circuits, meters, fuses, and switches. The<br />

cabinet shall be provided in a sturdy steel housing, complete with back box,<br />

hinged steel door with cylinder lock, and surface mounting provisions.<br />

2.15.2 Control Modules<br />

Provide power and control modules to perform all functions of the FACP.<br />

Provide audible signals to indicate any alarm, supervisory, or trouble<br />

condition. The alarm signals shall be different from the trouble signal.<br />

Connect circuit conductors entering or leaving the panel to screw-type<br />

terminals with each terminal marked for identification. Locate diodes and<br />

relays, if any, on screw terminals in the FACP. Circuits operating at 24<br />

VDC shall not operate at less than 21.6 volts. Circuits operating at any<br />

SECTION 28 31 76 Page 29


other voltage shall not have a voltage drop exceeding 10 percent of nominal<br />

voltage.<br />

2.15.3 Silencing Switches<br />

a. Alarm Silencing Switch: Provide an alarm silencing switch at the<br />

FACP that shall silence the audible signal but not affect the visual<br />

alarm indicator. This switch shall be overridden upon activation of a<br />

subsequent alarm.<br />

b. Supervisory/Trouble Silencing Switch: Provide supervisory and<br />

trouble silencing switch that shall silence the audible trouble and<br />

supervisory signal, but not extinguish the visual indicator. This<br />

switch shall be overridden upon activation of a subsequent alarm,<br />

supervision, or trouble condition. Audible trouble indication must<br />

resound automatically every 24 hours after the silencing feature has<br />

been operated.<br />

2.15.4 Non-Interfering<br />

Power and supervise each circuit such that a signal from one device does not<br />

prevent the receipt of signals from any other device. Circuits shall be<br />

manually reset by switch from the FACP after the initiating device or<br />

devices have been restored to normal.<br />

2.15.5 Voice Notification System<br />

The Voice Notification System shall be designed per UFC 3-600-01 and shall<br />

comply with the requirements of UFC 4-021-01 and the requirements of NFPA 72<br />

for Emergency Voice/Alarm Communications System requirements ISO 7240-16,<br />

IEC 60268-16, except as specified herein. The system shall be a one-way<br />

multi-channel voice notification system incorporating user selectability of<br />

a minimum 8 distinct sounds for tone signaling, and the incorporation of a<br />

voice module for delivery of prerecorded messages. Textual audible<br />

appliances shall produce a slow whoop tone for three cycles followed by a<br />

voice message that is repeated until the control panel is reset or silenced.<br />

Automatic messages shall be broadcast through speakers on appropriate<br />

floors, but not in stairs or elevator cabs. The visual strobes and audible<br />

message shall automatically be broadcast on the floor of fire alarm origin,<br />

the floor immediately above the floor of fire alarm origin, and the floor<br />

immediately below the floor of fire alarm origin. A live voice message<br />

shall override the automatic audible output through use of a microphone<br />

input at the control panel.<br />

a. When using the microphone, live messages shall be broadcast through<br />

speakers in stairs, in elevator cabs, and throughout a selected floor<br />

or floors. The system shall be capable of operating all speakers at<br />

the same time. The Voice Notification System shall support Public<br />

Address (PA) paging for the facility. The digitalized voice message<br />

shall consist of a non-volatile (EPROM) microprocessor based input to<br />

the amplifiers. The microprocessor shall actively interrogate<br />

circuitry, field wiring, and digital coding necessary for the immediate<br />

and accurate rebroadcasting of the stored voice data into the<br />

appropriate amplifier input. Loss of operating power, supervisory<br />

power, or any other malfunction that could render the digitalized voice<br />

module inoperative shall automatically cause the slow whoop tone to<br />

take over all functions assigned to the failed unit.<br />

SECTION 28 31 76 Page 30


. The Mass Notification functions shall override the manual or<br />

automatic fire alarm notification or Public Address (PA) functions.<br />

The system shall have the capability of utilizing a remote microphone<br />

station with redundant controls of the notification system control<br />

panel. Class "A" Notification Appliance Circuits (NAC) shall be<br />

provided for the activation of strobe appliances. The activation of<br />

the NAC Circuits shall follow the operation of the speaker NAC<br />

circuits. Audio output shall be selectable for line level (600 ohms),<br />

25, 70.7 or 100 volt output. The audio amplifier outputs shall be not<br />

greater than 100 watts RMS output. The strobe NAC Circuits shall<br />

provide at least 2 amps of 24 VDC power to operate strobes and have the<br />

ability to synchronize all strobes. A hand held microphone shall be<br />

provided and, upon activation, shall take priority over any tone<br />

signal, recorded message or PA microphone operation in progress, while<br />

maintaining the strobe NAC Circuits activation.<br />

All outputs and operational modules shall be fully supervised with on-board<br />

diagnostics and trouble reporting circuits. Form "C" contacts shall be<br />

provided for system alarm and trouble conditions. Circuits shall be<br />

provided for operation of auxiliary appliance during trouble conditions.<br />

During a Mass Notification event the panel shall not generate nor cause any<br />

trouble alarms to be generated with the Fire Alarm system. The Control<br />

Panel for the Voice Notification System shall be independent of the Fire<br />

alarm system and shall be capable of autonomous operation. The system shall<br />

be housed in a separate panel that contains an independent power supply and<br />

batteries, as specified above . Mass Notification functions shall take<br />

precedence over all other function performed by the Voice Notification<br />

System. Installation approved messages shall be provided by JBLM,<br />

Directorate of Emergency Services, Physical Security Branch. Obtain .wav<br />

files with recordings of the following messages from the Contracting<br />

Offices:<br />

1) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. JBLM is experiencing an incident<br />

of civil disturbance; military personnel contact your unit. All<br />

personnel avoid installation access points. Tune into JBLM command<br />

TV 21 and AM Radio 1500." (provide 2-second pause and repeat<br />

message)<br />

2) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. Evacuate the area immediately,<br />

evacuate the area immediately and follow the instructions of public<br />

safety personnel. Tune into JBLM command TV 21 and AM Radio 1500."<br />

(provide 2-second pause and repeat message)<br />

3) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. Seek shelter immediately and<br />

secure all doors and windows. Tune into JBLM command TV 21 and AM<br />

Radio 1500." (provide 2-second pause and repeat message)<br />

SECTION 28 31 76 Page 31


4) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. Seek shelter immediately, close<br />

all doors and windows, shut off all heating, ventilation, and air<br />

conditioning units. Tune into JBLM command TV 21 and AM Radio<br />

1500." (provide 2-second pause and repeat message)<br />

5) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. Severe weather storm warning,<br />

severe weather storm warning, take cover immediately. Tune into<br />

JBLM command TV 21 and AM Radio 1500." (provide 2-second pause and<br />

repeat message)<br />

6) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. Prepare for a live voice<br />

announcement." (provide 2-second pause and repeat message two<br />

times)<br />

7) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. The previously declared<br />

emergency no longer exists." (provide 2-second pause and repeat<br />

message two times)<br />

8) 1000 Hz tones (1 sec on, 1/2 second off, 1 second on, 1/2 second<br />

off, 1 second on)<br />

"Attention, Attention, Attention. This is only a test. This is a<br />

test of the JBLM early warning system." (provide 2-second pause and<br />

repeat message)<br />

a. The Remote Microphone station shall incorporate a Push-To-Talk<br />

(PTT) microphone, redundant controls and system status indicators<br />

of/for the system. The unit shall incorporate microphone override of<br />

any tone generation or prerecorded messages. The unit shall be fully<br />

supervised from the control panel. The housing shall contain a lock<br />

that is keyed identical to the fire alarm system for the building.<br />

b. Auxiliary Input Module shall be designed to be an outboard<br />

expansion module to either expand the number of optional remote<br />

microphone stations, or allow a telephone interface.<br />

c. Remote Microphone station (PA) shall incorporate a Push-To-Talk<br />

(PTT) microphone, and controls to allow Public Address paging in the<br />

facility. The Public Address paging function shall not override any<br />

alarm or notification functions. The microphone shall be desktop or<br />

hand-held style as stated in the Delivery or Task Order.<br />

2.15.6 Memory<br />

SECTION 28 31 76 Page 32


Provide each control unit with non-volatile memory and logic for all<br />

functions. The use of long life batteries, capacitors, or other agedependent<br />

devices shall not be considered as equal to non-volatile<br />

processors, PROMS, or EPROMS.<br />

2.15.7 Field Programmability<br />

Provide control units and control panels that are fully field programmable<br />

for control, initiation, notification, supervisory, and trouble functions of<br />

both input and output. The system program configuration shall be menu<br />

driven. System changes shall be password protected and shall be<br />

accomplished using personal computer based equipment. Any proprietary<br />

equipment and proprietary software needed by Public Works Fire Alarm<br />

Maintenance Technicians to implement future changes to the fire alarm system<br />

shall be provided as part of this contract.<br />

2.15.8 Input/Output Modifications<br />

The FACP shall contain features that allow the bypassing of input devices<br />

from the system or the modification of system outputs. These control<br />

features shall consist of a panel mounted keypad. Any bypass or<br />

modification to the system shall indicate a trouble condition on the FACP<br />

(VDU) and a printed output of the trouble condition.<br />

2.15.9 Resetting<br />

Provide the necessary controls to prevent the resetting of any alarm,<br />

supervisory, or trouble signal while the alarm, supervisory or trouble<br />

condition on the system still exists.<br />

2.15.10 Instructions<br />

Provide a typeset printed or typewritten instruction card mounted behind a<br />

Lexan plastic or glass cover in a stainless steel or aluminum frame.<br />

Install the instructions on the interior of the FACP. The card shall show<br />

those steps to be taken by an operator when a signal is received as well as<br />

the functional operation of the system under all conditions, normal, alarm,<br />

supervisory, and trouble. The instructions shall be approved by the<br />

Contracting Officer before being posted.<br />

2.15.11 Walk Test<br />

The FACP shall have a walk test feature. When using this feature, operation<br />

of initiating devices shall result in limited system outputs, so that the<br />

notification appliances operate for only a few seconds and the event is<br />

indicated on the system printer, but no other outputs occur.<br />

2.15.12 History Logging<br />

The control panel shall have the ability to store a minimum of 400 events in<br />

a log. These events shall be stored in a battery-protected memory and shall<br />

remain in the memory until the memory is downloaded or cleared manually.<br />

Resetting of the control panel shall not clear the memory.<br />

2.15.13 RS-232-C Output<br />

SECTION 28 31 76 Page 33


Each local control panel shall be capable of operating remote service type<br />

cathode ray tubes (CRTs), printers, and/or modems. The output shall be<br />

paralleled ASCII from an EIA RS-232-C connection with a baud rate of 1200 or<br />

2400 to allow use of any commonly available CRT, printer, or modem.<br />

2.15.14 Remote LED Text Display<br />

An LED text display shall be provided at locations as shown on the drawings.<br />

The LED text display shall be at least 2 lines with a minimum of 20<br />

characters per line. The size shall not exceed 16 inches length by 6 inches<br />

height by 3 inches deep. The text display shall as a minimum meet the<br />

following requirements:<br />

a. Two lines of information for high priority messaging.<br />

b. Minimum of 20 characters per line (40 total) displayed.<br />

c. Text shall be no less than 1/2 inch in height and readable from 1<br />

foot to 20 feet away.<br />

d. 32K character memory.<br />

e. RS232 or RS485 serial interface included.<br />

f. Display shall be wall or ceiling mounted.<br />

g. Mounting brackets for a convenient wall/cubicle mount.<br />

h. During non-emergency periods, date and time shall be displayed.<br />

i. All programming shall be accomplished from the Mass Notification<br />

network. No user programming shall be required.<br />

An LED text display shall be provided at locations as shown on the drawings.<br />

The LED text display shall have minimum character size of 4-inches high and<br />

shall spell out the words "EVACUATE" and "ANNOUNCEMENT". The design of LED<br />

text display shall be such that it cannot be read when not illuminated. The<br />

LED text display shall be capable of being wall or ceiling mounted.<br />

2.16 REMOTE <strong>FIRE</strong> <strong>ALARM</strong> CONTROL UNITS<br />

Provide complete remote control units fully enclosed in a lockable steel<br />

enclosure as specified herein. Operations required for testing or for<br />

normal care and maintenance of the control units shall be performed from the<br />

front of the enclosure. If more than a single unit is required at a<br />

location to form a complete control panel, the unit enclosures shall match<br />

exactly. Each control unit shall provide power, supervision, control, and<br />

logic for its portion of the entire system, utilizing solid state, modular<br />

components, internally mounted and arranged for easy access. Each control<br />

unit shall be suitable for operation on a 120 volt, 60 hertz, normal<br />

building power supply. Provide each unit with supervisory functions for<br />

power failure, internal component placement, and operation.<br />

2.16.1 Cabinet<br />

Install remote control unit components in cabinets large enough to<br />

accommodate components and also to allow ample gutter space for<br />

SECTION 28 31 76 Page 34


interconnection of units as well as field wiring. The enclosure shall be<br />

identified by an engraved laminated phenolic resin nameplate. Lettering on<br />

the nameplate shall be labeled "Remote Fire Alarm Control Unit" and shall<br />

not be less than one inch high. Provide prominent rigid plastic or metal<br />

identification plates for lamps, circuits, meters, fuses, and switches. The<br />

cabinet shall be provided in a sturdy steel housing, complete with back box,<br />

hinged steel door with cylinder lock, and surface mounting provisions.<br />

2.16.2 Control Modules<br />

Provide power and control modules to perform all functions of the remote<br />

control unit. Provide audible signals to indicate any alarm or trouble<br />

condition. The alarm signals shall be different from the trouble signal.<br />

Connect circuit conductors entering or leaving the panel to screw-type<br />

terminals with each terminal marked for identification. Locate diodes and<br />

relays, if any, on screw terminals in the remote control unit. Circuits<br />

operating at 24 VDC shall not operate at less than 21.6 volts. Circuits<br />

operating at any other voltage shall not have a voltage drop exceeding 10<br />

percent of nominal voltage. Circuits shall be arranged so that there is 25<br />

percent spare capacity for any circuit.<br />

2.16.3 Silencing Switches<br />

Provide an alarm silencing switch at the remote control unit that shall<br />

silence the audible signal but not affect the visual alarm indicator. This<br />

switch shall be overridden upon activation of a subsequent alarm. Provide<br />

trouble and supervisory silencing switch that shall silence the audible<br />

trouble and supervisory signal, but not extinguish the visual indicator.<br />

This switch shall be overridden upon activation of a subsequent trouble or<br />

supervisory signal. Audible trouble indication must resound automatically<br />

every 24 hours after the silencing feature has been operated.<br />

2.16.4 Non-Interfering<br />

Power and supervise each circuit such that a signal from one device does not<br />

prevent the receipt of signals from any other device. Circuits shall be<br />

manually resettable by switch from the remote control unit after the<br />

initiating device or devices have been restored to normal.<br />

2.16.5 Memory<br />

Provide each control unit with non-volatile memory and logic for all<br />

functions. The use of long life batteries, capacitors, or other agedependent<br />

devices shall not be considered as equal to non-volatile<br />

processors, PROMS, or EPROMS.<br />

2.16.6 Field Programmability<br />

Provide control units that are fully field programmable for control,<br />

initiating, supervisory, and trouble functions of both input and output.<br />

The system program configuration shall be menu driven. System changes shall<br />

be password protected and shall be accomplished using personal computer<br />

based equipment. Any proprietary equipment and proprietary software needed<br />

by Public Works Fire Alarm Maintenance Technicians to implement future<br />

changes to the fire alarm system shall be provided as part of this contract.<br />

SECTION 28 31 76 Page 35


2.16.7 Input/Output Modifications<br />

Each remote control unit shall contain features that allow the elimination<br />

of input devices from the system or the modification of system outputs. Any<br />

such modifications shall indicate a trouble condition on the remote control<br />

unit, the FACP, and a printed output of the trouble condition.<br />

2.16.8 Resetting<br />

Provide the necessary controls to prevent the resetting of any alarm,<br />

supervisory, or trouble signal while the alarm, supervisory, or trouble<br />

condition on the system still exists.<br />

2.16.9 Instructions<br />

Provide a typeset printed or typewritten instruction card mounted behind a<br />

Lexan plastic or glass cover in a stainless steel or aluminum frame.<br />

Install the frame in a conspicuous location observable from the remote fire<br />

alarm control unit. The card shall show those steps to be taken by an<br />

operator when a signal is received as well as the functional operation of<br />

the system under all conditions, normal, alarm, supervisory, and trouble.<br />

The instructions shall be approved by the Contracting Officer before being<br />

posted.<br />

2.16.10 Walk Test<br />

Each remote control unit shall have a walk test feature. When using this<br />

feature, operation of initiating devices shall result in limited system<br />

outputs, so that the notification appliances operate for only a few seconds<br />

and the event is indicated on the system printer, but no other outputs<br />

occur.<br />

2.16.11 History Logging<br />

The control panel shall have the ability to store a minimum of 400 events in<br />

a log. These events shall be stored in a battery-protected memory and shall<br />

remain in the memory until the memory is downloaded or cleared manually.<br />

Resetting of the control panel shall not clear the memory.<br />

2.17 AMPLIFIERS, PREAMPLIFIERS, TONE GENERATORS<br />

Any amplifiers, preamplifiers, tone generators, digitalized voice<br />

generators, and other hardware necessary for a complete, operational,<br />

textual audible circuit conforming to NFPA 72 shall be housed in a fire<br />

alarm control unit, terminal cabinet, or in the fire alarm control panel.<br />

The system shall automatically operate and control all building fire alarm<br />

speakers except those installed in the stairs and within elevator cabs. The<br />

speakers in the stairs and elevator cabs shall operate only when the<br />

microphone is used to deliver live messages. Each amplifier shall be single<br />

output channel.<br />

2.17.1 Construction<br />

Amplifiers shall utilize computer grade solid state components and shall be<br />

provided with output protection devices sufficient to protect the amplifier<br />

against any transient up to 10 times the highest rated voltage in the<br />

system.<br />

SECTION 28 31 76 Page 36


2.17.2 Inputs<br />

Each system shall be equipped with separate inputs from the tone generator,<br />

digitalized voice driver and panel mounted microphone. Microphone inputs<br />

shall be of the low impedance, balanced line type. Both microphone and tone<br />

generator input shall be operational on any amplifier.<br />

2.17.3 Tone Generator<br />

The tone generator shall be of the modular, plug-in type with securely<br />

attached labels to identify the component as a tone generator and to<br />

identify the specific tone it produces. The tone generator shall produce a<br />

slow whoop tone that shall slowly ascend from low (500 hertz) to high (1200<br />

hertz), and shall be constantly repeated until interrupted by either the<br />

digitalized voice message, the microphone input, or the alarm silence mode<br />

as specified. Each slow whoop cycle shall last approximately 4 seconds.<br />

The tone generator shall be single channel with an automatic backup<br />

generator per channel such that failure of the primary tone generator causes<br />

the backup generator to automatically take over the functions of the failed<br />

unit and also causes transfer of the common trouble relay.<br />

2.17.4 Protection Circuits<br />

Each amplifier shall be constantly supervised for any condition that could<br />

render the amplifier inoperable at its maximum output. Failure of any<br />

component shall cause automatic transfer to a designated backup amplifier,<br />

illumination of a visual "amplifier trouble" indicator on the control panel,<br />

appropriate logging of the condition on the system printer, and other<br />

actions for trouble conditions as specified.<br />

2.18 <strong>FIRE</strong>FIGHTER TELEPHONE COMMUNICATION <strong>SYSTEM</strong><br />

When required by code, provide a firefighter telephone system as follows:<br />

a. Provide a firefighter telephone communication system with complete,<br />

common talk, closed circuits. The system shall include, but not be<br />

limited to, a master control station mounted in the fire alarm control<br />

panel, a power supply and standby battery system, and remote telephone<br />

stations.<br />

b. Provide a master control station that shall provide power,<br />

supervision, and control for wiring, components, and circuits. The act<br />

of lifting any remote telephone hand set from its cradle shall cause<br />

both a visual and audible signal to annunciate at the master control<br />

station. Removing the hand set at the master control station and<br />

depressing a button at the remote telephone hand set shall cause the<br />

automatic silencing of the audible signal. Communication between the<br />

master control station hand set and any/or all remote handsets shall<br />

require the depressing of a push-to-talk switch located on any/all<br />

remote handsets. During the time that the master control hand set is<br />

removed from its cradle it shall be possible to communicate between<br />

five remote handsets and the master control station. Handsets shall be<br />

able to monitor any conversation in progress and join the conversation<br />

by pressing the push-to-talk button. It shall not be possible to<br />

communicate between two or more remote handsets with the master control<br />

station hand set in its cradle. The master control station hand set<br />

SECTION 28 31 76 Page 37


shall be red in color and equipped with a 5-foot long strain-relieved<br />

coiled cord. Wiring connections shall be made to terminal strips. The<br />

master control station shall monitor wire and connections for any<br />

opens, shorts, or grounds that would render the system inoperable or<br />

unintelligible. The master control station shall be equipped with a<br />

silencing switch and ring-back feature such that any audible trouble<br />

signal can be silenced and shall be so indicated by the lighting of an<br />

amber LED. Once any trouble condition has been corrected, the amber<br />

LED shall be extinguished and the silencing switch shall sound again<br />

until the switch is restored to its original position. The master<br />

control station shall be equipped with a separate, LED annunciated<br />

switch for each telephone circuit. In addition, LEDs shall provide for<br />

the annunciation of operating and supervisory power. The loss of<br />

operating or supervisory power shall cause an audible and visual<br />

indication at the master control station and shall also cause the fire<br />

alarm trouble signal to sound on the FACP. Switches, LEDs, and<br />

controls shall be fully labeled.<br />

c. Provide remote telephone stations as stated in the Delivery or Task<br />

Order. Each station shall be equipped with a hinged door that is<br />

magnetically locked. Each hand set shall be permanently wired in place<br />

with a coiled cord. Each hand set shall be red high-impact cycolac and<br />

shall be equipped with a push-to-talk switch that, when operated, shall<br />

signal the master control station and a switch-equipped, storage<br />

cradle.<br />

d. Provide operating and supervising power from the same supply<br />

circuit(s) utilized for the fire alarm control panel.<br />

2.19 MANUAL STATIONS<br />

Provide metal or plastic, semi-flush mounted, double action, addressable<br />

manual stations that are not subject to operation by jarring or vibration.<br />

Stations shall be equipped with screw terminals for each conductor.<br />

Stations that require the replacement of any portion of the device after<br />

activation are not permitted. Stations shall be finished in fire-engine red<br />

with molded raised lettering operating instructions of contrasting color.<br />

The use of a 211 key shall be required to reset the station. Manual<br />

stations shall be mounted at 54 inches. Stations shall have a separate<br />

screw terminal for each conductor.<br />

2.20 NOTIFICATION APPLIANCES<br />

2.20.1 Fire Alarm/Mass Notification Speakers<br />

Audible appliances shall conform to the applicable requirements of UL 464.<br />

Appliances shall be connected into notification appliance circuits. Audible<br />

appliances shall generate a unique audible sound from other devices provided<br />

in the building and surrounding area. Surface mounted audible appliances<br />

shall be painted red. Recessed audible appliances shall be installed with a<br />

grill that is painted with a factory finish to match the surface to which it<br />

is mounted.<br />

a. Speakers shall conform to the applicable requirements of UL 1480.<br />

Speakers shall have six different sound output levels and operate with<br />

audio line input levels of 100 VAC, 70 VAC, 7 VAC, and 25 VAC, by means<br />

of selectable tap settings. Tap settings shall include taps of 1/4,<br />

SECTION 28 31 76 Page 38


1/2, 1, 2, and 8 watt. Speakers shall incorporate a high efficiency<br />

speaker for maximum output at minimum power across a frequency range of<br />

400Hz to 4000Hz, and shall have a sealed back construction. Speakers<br />

shall be capable of installation on standard 4 inch square electrical<br />

boxes. Where speakers and strobes are provided in the same location,<br />

they may be combined into a single unit. All inputs shall be polarized<br />

for compatibility with standard reverse polarity supervision of circuit<br />

wiring via the Fire Alarm Control Panel.<br />

b. Provide speaker mounting plates constructed of cold rolled steel<br />

having a minimum thickness of 16 gauge and equipped with mounting holes<br />

and other openings as needed for a complete installation. Fabrication<br />

marks and holes shall be ground and finished to provide a smooth and<br />

neat appearance for each plate. Each plate shall be primed and<br />

painted.<br />

2.20.2 Visual Notification Appliances<br />

Visual notification appliances shall conform to the applicable requirements<br />

of UL 1971 and conform to the Americans With Disabilities Act (ADA).<br />

Colored lens such as amber, the notifications appliances shall comply with<br />

UL 1638. The manufacturer shall have the color lens tests to the full UL<br />

1971 polar plotting criteria, voltage drop, and temperature rise as stated<br />

in 1971. Fire Alarm Notification Appliances shall have clear high intensity<br />

optic lens, xenon flash tubes, and output white light and be marked "Fire"<br />

in red letters. Mass Notification Appliances shall have amber high<br />

intensity optic lens, xenon flash tubes, and output white light and be<br />

marked "ALERT" in red letters. The light pattern shall be disbursed so that<br />

it is visible above and below the strobe and from a 90 degree angle on both<br />

sides of the strobe. Strobe flash rate shall be 1 flash per second and a<br />

minimum candela rating as stated in the Delivery or Task Order (actual<br />

output after derating for tinted lens) based on the UL 1971 test. Where<br />

more than two appliances are located in the same room or corridor, provide<br />

synchronized operation.<br />

2.20.3 Fire Alarm Horns<br />

Provide electronic multi-tone horns that produce a minimum of four distinct<br />

sounds, suitable for use in an electrically supervised circuit. Horns shall<br />

have a rating of 90 dBA at 10 feet when tested in accordance with UL 464<br />

while emitting a slow whoop tone. Output from the horn shall be the slow<br />

whoop tone. Where horns and strobes are provided in the same location, they<br />

may be combined into a single unit. Horns used in exterior locations shall<br />

be specifically listed or approved for outdoor use and be provided with<br />

metal housing and protective grilles.<br />

2.20.4 Fire Alarm Bells<br />

Bells shall be surface mounted with the matching mounting back box suitable<br />

for use in an electrically supervised circuit. Bells shall be suitable for<br />

use in an electrically supervised circuit. Bells shall be the underdome<br />

type producing a minimum output rating of 90 dBA at 10 feet. Bells used in<br />

exterior locations shall be specifically listed or approved for outdoor use<br />

and be provided with metal housing and protective grilles. Single stroke,<br />

electrically operated, supervised, solenoid bells shall be used for coded<br />

applications.<br />

SECTION 28 31 76 Page 39


2.20.5 Chimes<br />

Chimes shall be electrically operated, supervised, electronic type, with an<br />

adjustable frequency of 800 to 1200 Hertz. Chimes shall have a minimum<br />

sound rating of 80 dBA at 10 feet. Chimes shall ring the bell codes, as<br />

indicated.<br />

2.20.6 Connections<br />

Provide screw terminals for each notification appliance. Terminals shall be<br />

designed to accept the size conductors used in this project without<br />

modification.<br />

2.21 ENVIRONMENTAL ENCLOSURES OR GUARDS<br />

Environmental enclosures shall be provided to permit Fire Alarm or Mass<br />

Notification components to be used in areas that exceed the environmental<br />

limits of the listing. The enclosure shall be listed for the device or<br />

appliance as either a manufactured part number or as a listed compatible<br />

accessory for the UL category that the component is currently listed.<br />

Guards required to deter mechanical damage shall be either a listed<br />

manufactured part or a listed accessory for the category of the initiating<br />

device or notification appliance.<br />

2.22 VALVE MONITOR SWITCHES (TAMPER SWITCHES)<br />

Provide a tamper switch for each fire protection system control valve.<br />

Tamper switches shall be UL listed as "Extinguishing System Attachment" for<br />

the location and type of valve supervised. The device shall contain double<br />

pole, double throw contacts. Operation of the switch shall cause a<br />

supervisory signal to be transmitted to the FACP upon not more than two<br />

complete turns of the valve wheel or a closure of 10 percent, whichever is<br />

less. Tamper switches shall be equipped with screw terminals for each<br />

conductor.<br />

2.23 WATERFLOW DETECTORS<br />

a. Provide vane type waterflow detectors for wet pipe sprinkler<br />

systems. The device shall contain double pole, double throw contacts.<br />

Equip the detector with a pneumatic time delay, field adjustable from 0<br />

to 90 seconds. The time delay shall be set initially to 30 seconds.<br />

The device shall be a UL listed extinguishing system attachment rated<br />

for the particular pressure and location that it is installed. Flow<br />

switches shall be equipped with screw terminals for each conductor.<br />

b. Provide pressure type waterflow detectors for dry pipe sprinkler<br />

systems, pre-action, and deluge systems. Switch shall be equipped with<br />

equipped to provide a time delay from 0 to 90 second. The device shall<br />

contain double pole, double throw contacts. The device shall be a UL<br />

listed extinguishing system attachment rated for the particular<br />

pressure and location that it is installed. Switch shall be equipped<br />

with screw terminals for each conductor.<br />

2.24 ELECTROMAGNETIC DOOR HOLDERS<br />

Where indicated on the drawings, provide magnetic fire door hold open<br />

devices. The electromagnetic holding devices shall be designed to operate<br />

SECTION 28 31 76 Page 40


at the voltage indicated, and require not more than 3 watts of power to<br />

develop 25 psi of holding force. Under normal conditions, the magnets shall<br />

attract and hold the doors open. The initiation of any fire alarm shall<br />

cause the release of the electromagnetic door holding device permitting the<br />

door to be closed by the door closer. Operation shall be fail safe with no<br />

moving parts. Electromagnetic door hold-open devices shall not be required<br />

to be held open during building power failure. The device shall be UL<br />

listed based on UL 228 tests.<br />

2.25 INTERFACE TO THE BASE WIDE MASS NOTIFICATION NETWORK<br />

2.25.1 Wide Area Network/Local Area Network (WAN/LAN)<br />

The Wide Area Network/Local Area Network (WAN/LAN) Interface shall be a<br />

10BASE-T/100BASE-TX Category 6. The ANSI/TIA/EIA 568 wiring method of the<br />

RJ-45 outlet shall be as specified in Section 27 10 00 BUILDING<br />

TELECOMMUNICATIONS CABLING <strong>SYSTEM</strong>. The WAN/LAN Interface shall support<br />

sensitive data at rated data transmission speeds with DES/3DES encryption,<br />

MD5 and SHA-1 hashing, RFC 2402 authentication and meet security features of<br />

FIPS 140-2 criteria. The WAN/LAN Interface shall have the following<br />

characteristics:<br />

a. 10BASE-T/100BASE-TX, autonegotiation<br />

b. WAN/LAN Connection: RJ-45<br />

c. Cabling: as specified in Section 27 10 00 BUILDING<br />

TELECOMMUNICATIONS CABLING <strong>SYSTEM</strong><br />

d. Security Protocols: 168-bit 3DES, 56-bit DES, SHA-1, MD5, RFC 2402;<br />

up to 75 security associations<br />

e. Network protocols: TCP/IP, ISO 8802-3<br />

2.25.2 Fiber Optic<br />

The fiber optic transceiver shall be fully compatible with EIA standards for<br />

RS-232, RS-422 and RS-485 at data rates from 0 (DC) to 2.1 mbps (200 kbps<br />

for RS-232) in the low speed mode or from 10 kbps to 10 mbps in the highspeed<br />

mode. The fiber optic transceiver shall be capable of simplex or full<br />

duplex asynchronous transmissions in both point-to-point systems and dropand-repeat<br />

data networks. The fiber optic transceiver shall be user<br />

configurable for the protocol, speed and mode of operation required. The<br />

fiber optic transceiver shall be installed as a stand-alone unit. The fiber<br />

optic transceiver shall operate on Single-mode fiber optic cable. The fiber<br />

optic transceiver shall be supplied with ST type optical connectors.<br />

Cabling: as specified in Section 27 10 00 BUILDING TELECOMMUNICATIONS<br />

CABLING <strong>SYSTEM</strong>.<br />

2.25.3 Radio<br />

The radio transceiver shall be bi-direction and meet all the requirements of<br />

paragraph, <strong>RADIO</strong> TRANSMITTER AND INTERFACE PANELS as specified in this<br />

Specification Section. The transceiver utilized in the Mass Notification<br />

System shall be capable of the following:<br />

SECTION 28 31 76 Page 41


a. Communication with the Central Control/Monitoring System to provide<br />

supervision of communication link and status changes are reported by<br />

automatic and manual poll/reply/acknowledge routines.<br />

b. All monitored points/status changes are transmitted immediately and<br />

at programmed intervals until acknowledged by the Central<br />

Control/Monitoring System.<br />

c. Each transceiver shall transmits a unique identity code as part of<br />

all messages; the code is set by the user at the transceiver.<br />

2.25.3.1 Radio Frequency Communications<br />

Use of radio frequency-type communications systems shall comply with<br />

National Telecommunications and Information Administration (NTIA)<br />

requirements.<br />

2.25.3.2 Licensed Radio Frequency Systems<br />

An approved DD Form 1494 for the system is required prior to operation.<br />

2.25.4 Telephone<br />

A modem shall be provide for communication with the Central<br />

Control/Monitoring System. The modem shall be 56k, compatible with data<br />

mode V.90, utilizing Hayes compatible command codes. The modem shall be<br />

capable of Auto dialing a preset number based on preprogrammed events. The<br />

modem shall auto answer and provide a secure password protection system.<br />

Cabling: as specified in Section 27 10 00 BUILDING TELECOMMUNICATIONS<br />

CABLING <strong>SYSTEM</strong>.<br />

2.25.5 RS-232/RS-485<br />

The panel shall support a direct connect via RS-232 or RS-485 connections.<br />

2.25.6 Secure Radio System<br />

2.25.6.1 Communications Network<br />

The communications network provides two-way signals between central control<br />

units and autonomous control units (in individual building systems), and<br />

should include redundant (primary and backup) communication links. The<br />

system shall incorporate technology to prevent easy interruption of the<br />

radio traffic for MNS Alerting.<br />

2.25.6.2 Radio Frequency Communications<br />

Use of radio frequency-type communications systems shall comply with<br />

National Telecommunications and Information Administration (NTIA)<br />

requirements. The systems shall be designed to minimize the potential for<br />

interference, jamming, eavesdropping, and spoofing.<br />

2.25.6.3 Licensed Radio Frequency Systems<br />

An approved DD Form 1494 for the system is required prior to operation.<br />

SECTION 28 31 76 Page 42


2.26 AUTOMATIC <strong>FIRE</strong> TRANSMITTERS<br />

2.26.1 Radio Transmitter and Interface Panels<br />

Transmitters shall be compatible with proprietary supervising station<br />

receiving equipment. Each radio alarm transmitter shall be the<br />

manufacturer's recognized commercial product, completely assembled, wired,<br />

factory tested, and delivered ready for installation and operation.<br />

Transmitters shall be provided in accordance with applicable portions of<br />

NFPA 72, Federal Communications Commission (FCC) 47 CFR 90 and Federal<br />

Communications Commission (FCC) 47 CFR 15. Transmitter electronics module<br />

shall be contained within the physical housing as an integral, removable<br />

assembly. The proprietary supervising station receiving equipment is the<br />

Monaco D-21M base reporting system, and the transceiver shall be fully<br />

compatible with this equipment. The Ft. Lewis Fire Alarm Transceiver<br />

frequency is 139.6750 MHz. The transceiver number and the transceiver zones<br />

to be used for each project shall be designated by the JBLM Fire<br />

Inspectors/DPW Fire Alarm Maintenance personnel. The following initiating<br />

events or troubles shall require their own transmitted zone: Deluge<br />

sprinkler system, Water flow (sprinklers), Low air pressure (dry<br />

sprinklers), Separate buildings or quads, and FACP common trouble. At the<br />

contractors option, and if UL or FM listed, the transmitter may be housed in<br />

the same panel as the fire alarm control panel. The transmitter shall be<br />

Narrowband radio, with FCC certification for narrowband operation and meets<br />

the requirements of the NTIA (National Telecommunications and Information<br />

Administration) Manual of Regulations and Procedures for Federal Frequency<br />

Management.<br />

a. Operation: Each transmitter shall operate from 120-volt ac power.<br />

In the event of 120-volt ac power loss, the transmitter shall<br />

automatically switch to battery operation. Switchover shall be<br />

accomplished with no interruption of protective service, and shall<br />

automatically transmit a trouble message. Upon restoration of ac<br />

power, transfer back to normal ac power supply shall also be automatic.<br />

b. Battery Power: Transmitter standby battery capacity shall provide<br />

sufficient power to operate the transmitter in a normal standby status<br />

for a minimum of 72 hours and be capable of transmitting alarms during<br />

that period.<br />

c. Transmitter housing shall be NEMA Type 1. The housing shall<br />

contain a lock that is keyed identical to the fire alarm system for the<br />

building. Radio alarm transmitter housing shall be factory painted<br />

with a suitable priming coat and not less than two coats of a hard,<br />

durable weatherproof enamel. No conduits are allowed in the top or<br />

bottom of the transmitter enclosure.<br />

d. Antenna shall be as indicated with a driving point impedance to<br />

match transmitter output. The antenna and antenna mounts shall be<br />

corrosion resistant and designed to withstand wind velocities of 100<br />

mph. Antennas shall not be mounted to any portion of the building<br />

roofing system. Protect the antenna from physical damage. Apply<br />

silicone sealant at all threaded connections on the antenna mast to<br />

waterproof the joint.<br />

All fire alarm transceivers must be listed or approved for use with Monaco<br />

D-21M base reporting system and meet the following minimum requirements:<br />

SECTION 28 31 76 Page 43


a. FM approved, narrowband radio communications with Monaco D-21 base<br />

reporting system.<br />

b. FCC certified for narrowband operation and meets the requirements<br />

of the NTIA Manual of Regulations and Procedures for Federal Frequency<br />

Management.<br />

c. Fallback communications to hardwire connections if wired (phone<br />

line backup).<br />

d. Transmit live voice and pre-recorded messages from the D-21 mass<br />

notification system to within building mass notification panels or<br />

wide-area speaker stations.<br />

e. Receive live voice from radio, telephone, and microphone.<br />

f. Pre-recorded messages can be triggered via relay contact closure.<br />

g. Security features prevents unauthorized takeover of live voice<br />

transmissions.<br />

h. Supervised connection to mass notification panel.<br />

i. Status LED's reflect the status of the transceiver general trouble,<br />

system fault, in-communication, carrier detect, transmit, primary<br />

power, battery boost charge, and battery float charge.<br />

j. Communication LED's indicate the method of communication used:<br />

radio or hardwire, and whether or not a live voice message is being<br />

sent.<br />

k. Full-duplex RS-232 port used to program the transceiver via<br />

connection to a laptop computer.<br />

l. 115 or 230 VAC power is monitored with automatic switchover to<br />

backup battery power that provides standby power.<br />

m. Self test, stuck transmitter disconnect, reset, acknowledge, and<br />

battery reconnect switches.<br />

n. Local audible alert.<br />

o. Real time clock and calendar.<br />

p. At least 1/2 Mb of program memory.<br />

q. At least 1/2 Mb of non-volatile data storage.<br />

r. One selectable RS-422/RS-485 port for communication with peripheral<br />

equipment or hardwire connection to multiple units connected together<br />

for communication with the D-21.<br />

2.26.2 Digital Alarm Communicator Transmitter (DACT)<br />

Provide DACT that is compatible with the existing supervising station fire<br />

alarm system. Transmitter shall have a means to transmit alarm,<br />

SECTION 28 31 76 Page 44


supervisory, and trouble conditions via a single transmitter. Transmitter<br />

shall have a source of power for operation that conforms to NFPA 72.<br />

Transmitter shall be capable of initiating a test signal daily at any<br />

selected time. Transmitter shall be arranged to seize telephone circuits in<br />

accordance with NFPA 72.<br />

2.26.3 Master Fire Alarm Boxes<br />

Master fire alarm boxes shall be of the coded, non-interfering type with<br />

succession features having a compatible auxiliary tripping device, and of<br />

the prewound, open-door, pull-lever type. Mechanism shall be housed in a<br />

weatherproof cottage shell type of housing with metallic or rigid plastic<br />

code number plate mounted on the exterior face of the cottage shell.<br />

Operation of the actuating pull lever shall cause the box to transmit four<br />

complete rounds of code to gongs, recorders, and other devices on the same<br />

circuit. Driving springs shall have the capability to transmit not less<br />

than eight complete four-round groups of code before being rewound. Boxes<br />

shall be designed for operation of 100 milliamperes dc, but with capability<br />

of full operation of 70 milliamperes and up to 120 milliamperes. Activation<br />

of box when a single open fault is present on exterior fire alarm circuit<br />

shall have box to idle for one complete round only, then immediately<br />

transmit four complete code rounds via the box earth ground connection.<br />

Each box shall be equipped with manual signaling key, telephone jack, silent<br />

test device, and box shunt device. Box shall be mounted as indicated with<br />

center of box 48 inches above grade, and provided with lighting fixture.<br />

Mounting bolts, brackets, fastenings, and conduit shall be copper alloy,<br />

cadmium, or zinc-coated steel. Code wheel shall be metallic and box code<br />

shall be as directed. Electrically powered master fire alarm boxes shall<br />

have standby sealed, lead calcium battery capacity for a minimum of 72 hours<br />

and be capable of transmitting alarms during that period.<br />

2.26.4 Signals to Be Transmitted to the Base Receiving Station<br />

The following signals shall be sent to the base receiving station:<br />

a. Sprinkler water flow<br />

b. Manual pull stations<br />

c. Smoke detectors<br />

d. Duct smoke detectors<br />

e. Sleeping room smoke detectors<br />

f. Heat detectors<br />

g. Fire Extinguishing System<br />

h. Sprinkler valve supervision<br />

i. Fire pump running<br />

j. Fire pump supervision<br />

k. Water supply level and temperature<br />

SECTION 28 31 76 Page 45


l. Combustion Engine Drive Fire Pump Running<br />

2.27 WIRING<br />

(1) Selector Switch in position than automatic<br />

(2) Engine Over-speed<br />

(3) Low Fuel<br />

(4) Low Battery<br />

(5) Engine Trouble (Low Oil, Over temp, etc)<br />

Provide wiring materials under this section as specified in Section 26 20 00<br />

INTERIOR DISTRIBUTION <strong>SYSTEM</strong> with the additions and modifications specified<br />

herein.<br />

2.27.1 Alarm Wiring<br />

The SLC wiring shall be copper cable in accordance with the manufacturer’s<br />

requirements. Copper signaling line circuits and initiating device circuit<br />

field wiring shall be No. 14 AWG size conductors at a minimum. Notification<br />

appliance circuit conductors, that contain audible alarm devices, other than<br />

speakers, shall be solid copper No. 14 AWG size conductors at a minimum.<br />

Speaker circuits shall be copper No. 16 AWG size conductors at a minimum.<br />

Firefighter telephone circuits shall be No. 16 AWG size conductors as a<br />

minimum. Wire size shall be sufficient to prevent voltage drop problems.<br />

Circuits operating at 24 VDC shall not operate at less than 21.6 volts.<br />

Circuits operating at any other voltage shall not have a voltage drop<br />

exceeding 10 percent of nominal voltage. Power wiring, operating at 120 VAC<br />

minimum, shall be a minimum No. 12 AWG solid copper having similar<br />

insulation.<br />

2.27.2 Wiring to Station Telegraphic Fire Alarm Circuit<br />

Wiring from the master fire alarm box to the station telegraphic fire alarm<br />

circuit shall be a two-conductor No. 12 or 10 AWG type UF cable in conduit<br />

as stated in the Delivery or Task Order.<br />

PART 3<br />

EXECUTION<br />

3.1 INSTALLATION OF <strong>FIRE</strong> <strong>ALARM</strong> INITIATING AND INDICATING DEVICES<br />

a. FACP/FMCP: Locate the FACP/FMCP where indicated on the drawings.<br />

Mount the enclosure with the top of the cabinet 6 feet above the<br />

finished floor or center the cabinet at 5 feet, whichever is lower.<br />

Conductor terminations shall be labeled and a drawing containing<br />

conductors, their labels, their circuits, and their interconnection<br />

shall be permanently mounted in the FACP.<br />

b. Manual Stations: Locate manual stations as required by NFPA 101IEC<br />

60268, Part 16, and ASA S3.2 and NFPA 72. Mount stations so that their<br />

operating handles are 4 feet above the finished floor. Mount stations<br />

so they are located no farther than 5 feet from the exit door they<br />

serve, measured horizontally.<br />

SECTION 28 31 76 Page 46


c. Notification Appliance Devices: Locate notification appliance<br />

devices as required by NFPA 72. Mount assemblies on walls 90 inches<br />

above the finished floor or 6 inches below the ceiling whichever is<br />

lower. Ceiling mounted speakers shall conform to NFPA 72.<br />

d. Smoke and Heat Sensors: Locate sensors as required by NFPA 72 and<br />

their listings on a 4 inch mounting box. Sensors located on the<br />

ceiling shall be installed not less than 4 inches from a side wall to<br />

the near edge. Those located on the wall shall have the top of the<br />

sensor at least 4 inches below the ceiling, but not more than 12 inches<br />

below the ceiling. In raised floor spaces, the smoke sensors shall be<br />

installed to protect 225 square feet per sensor. Install smoke sensors<br />

no closer than 5 feet from air handling supply outlets.<br />

e. Graphic Annunciator: Locate the graphic annunciator as shown on<br />

the drawings. Surface mount the panel, with the top of the panel 6<br />

feet above the finished floor or center the panel at 5 feet, whichever<br />

is lower.<br />

f. Water Flow Detectors and Tamper Switches: Locate water flow<br />

detectors and tamper switches where shown on the drawings.<br />

g. Firefighter Telephones: Locate wall mounted in each stair at each<br />

floor landing, in each elevator lobby, and in each elevator cab 4 feet<br />

above the finished floor.<br />

h. The modification of any fire alarm system and the procedures shall<br />

comply with the requirements of NFPA 241.<br />

3.2 <strong>SYSTEM</strong> FIELD WIRING<br />

3.2.1 Wiring within Cabinets, Enclosures, and Boxes<br />

Provide wiring installed in a neat and workmanlike manner and installed<br />

parallel with or at right angles to the sides and back of any box,<br />

enclosure, or cabinet. Conductors that are terminated, spliced, or<br />

otherwise interrupted in any enclosure, cabinet, mounting, or junction box<br />

shall be connected to terminal blocks. Mark each terminal in accordance<br />

with the wiring diagrams of the system. Make connections with approved<br />

pressure type terminal blocks that are securely mounted. The use of wire<br />

nuts or similar devices shall be prohibited. Wiring shall conform to NFPA<br />

70.<br />

3.2.2 Terminal Cabinets<br />

Provide a terminal cabinet at the base of any circuit riser, on each floor<br />

at each riser, and where indicated on the drawings. Terminal size shall be<br />

appropriate for the size of the wiring to be connected. Conductor<br />

terminations shall be labeled and a drawing containing conductors, their<br />

labels, their circuits, and their interconnection shall be permanently<br />

mounted in the terminal cabinet. Minimum size is 8 inches by 8 inches.<br />

3.2.3 Alarm Wiring<br />

Provide all wiring in rigid metal conduit or intermediate metal conduit.<br />

Voltages shall not be mixed in any junction box, housing, or device, except<br />

those containing power supplies and control relays. Electrical metallic<br />

SECTION 28 31 76 Page 47


tubing conduit is acceptable in dry locations not enclosed in concrete or<br />

where not subject to mechanical damage. Conceal conduit in finished areas<br />

of new construction and wherever practicable in existing construction. The<br />

use of flexible conduit not exceeding a 6 foot length shall be permitted in<br />

initiating device circuits. Run conduit or tubing concealed unless<br />

specifically shown otherwise on the drawings. Shielded wiring shall be<br />

utilized where recommended by the manufacturer. For shielded wiring, the<br />

shield shall be grounded at only one point that shall be in or adjacent to<br />

the FACP. Pigtail or T-tap connections to signal line circuits, initiating<br />

device circuits, supervisory alarm circuits, and notification appliance<br />

circuits are prohibited. Color coding is required for circuits and shall be<br />

maintained throughout the circuit. Conductors used for the same functions<br />

shall be similarly color coded. Wiring shall conform to NFPA 70.<br />

3.2.4 Conductor Terminations<br />

Labeling of conductors at terminal blocks in terminal cabinets, FACP, and<br />

remote fire alarm control units shall be provided at each conductor<br />

connection. Each conductor or cable shall have a shrink-wrap label to<br />

provide a unique and specific designation. Each terminal cabinet, FACP, and<br />

fire alarm control unit shall contain a laminated drawing that indicates<br />

each conductor, its label, circuit, and terminal. The laminated drawing<br />

shall be neat, using 12 point lettering minimum size, and mounted within<br />

each cabinet, panel, or unit so that it does not interfere with the wiring<br />

or terminals. Maintain existing color code scheme where connecting to<br />

existing equipment.<br />

3.3 DISCONNECTION AND REMOVAL OF EXISTING <strong>SYSTEM</strong><br />

Existing fire alarm equipment shall be maintained fully operational until<br />

the new equipment has been tested and accepted by the Contracting Officer.<br />

As new equipment is installed, it shall be labeled "NOT IN SERVICE" until<br />

the new equipment is accepted. Once the new system is completed, tested,<br />

and accepted by the Government, it shall be placed in service and connected<br />

to the station fire alarm system. New equipment shall have tags removed and<br />

the existing equipment shall be tagged "NOT IN SERVICE" until removed from<br />

the building.<br />

a. After acceptance of the new system by the Contracting Officer,<br />

existing equipment not connected to the new system shall be removed,<br />

unused exposed conduit shall be removed, and damaged surfaces shall be<br />

restored. The material shall be removed from the site and disposed of<br />

by the Contractor.<br />

b. Disconnect and remove the existing fire alarm and smoke detection<br />

systems where indicated and elsewhere in the specification.<br />

c. Fire alarm control panels and fire alarm devices disconnected and<br />

removed shall be turned over to the Contracting Officer.<br />

d. Properly dispose of fire alarm outlet and junction boxes, wiring,<br />

conduit, supports, and other such items.<br />

3.4 CONNECTION OF NEW <strong>SYSTEM</strong><br />

SECTION 28 31 76 Page 48


The following new system connections shall be made during the last phase of<br />

construction, at the beginning of the preliminary tests. New system<br />

connections shall include:<br />

a. Connection of new control modules to existing magnetically held<br />

smoke door (hold-open) devices.<br />

b. Connection of new elevator recall smoke sensors to existing wiring<br />

and conduit.<br />

c. Connection of new system transmitter to existing base fire<br />

reporting system.<br />

Once these connections are made, system shall be left energized and new<br />

audio/visual devices deactivated. Report immediately to the Contracting<br />

Officer, coordination and field problems resulting from the connection of<br />

the above components.<br />

3.5 <strong>FIRE</strong>STOPPING<br />

Provide firestopping for holes at conduit penetrations through floor slabs,<br />

fire rated walls, partitions with fire rated doors, corridor walls, and<br />

vertical service shafts in accordance with Section 07 84 00 <strong>FIRE</strong>STOPPING.<br />

3.6 PAINTING<br />

Paint exposed electrical, fire alarm conduit, and surface metal raceway to<br />

match adjacent finishes in exposed areas. Paint junction boxes red in<br />

unfinished areas. Painting shall comply with Section 09 90 00 PAINTS AND<br />

COATINGS.<br />

3.7 FIELD QUALITY CONTROL<br />

3.7.1 Testing Procedures<br />

Detailed test procedures, prepared and signed by a Registered Professional<br />

Engineer or a NICET Level 3 Fire Alarm Technician, and signed by<br />

representative of the installing company, for the fire detection and alarm<br />

system 60 days prior to performing system tests. Detailed test procedures<br />

shall list all components of the installed system such as initiating devices<br />

and circuits, notification appliances and circuits, signaling line devices<br />

and circuits, control devices/equipment, batteries, transmitting and<br />

receiving equipment, power sources/supply, annunciators, special hazard<br />

equipment, emergency communication equipment, interface equipment, Guard's<br />

Tour equipment, and transient (surge) suppressors. Test procedures shall<br />

include sequence of testing, time estimate for each test, and sample test<br />

data forms. The test data forms shall be in a check-off format (pass/fail<br />

with space to add applicable test data) and shall be used for the<br />

preliminary testing and the acceptance testing. The test data forms shall<br />

record the test results and shall:<br />

a. Identify the NFPA Class and Style of all Initiating Device Circuits<br />

(IDC), Notification Appliance Circuits (NAC), Voice Notification<br />

System, and Signaling Line Circuits (SLC).<br />

SECTION 28 31 76 Page 49


. Identify each test required by NFPA 72 Test Methods and required<br />

test herein to be performed on each component, and describe how this<br />

test shall be performed.<br />

c. Identify each component and circuit as to type, location within the<br />

facility, and unique identity within the installed system. Provide<br />

necessary floor plan sheets showing each component location, test<br />

location, and alphanumeric identity.<br />

d. Identify all test equipment and personnel required to perform each<br />

test (including equipment necessary for testing smoke detectors using<br />

real smoke).<br />

e. Provide space to identify the date and time of each test. Provide<br />

space to identify the names and signatures of the individuals<br />

conducting and witnessing each test.<br />

3.7.2 Tests Stages<br />

a. Coordinate all testing with Public Works, Fire Department, Physical<br />

Security and the Contracting officer. The ring down test proving<br />

battery capacity shall be done the morning of the final acceptance<br />

test. The pre-test form shall be on hand at the time of the acceptance<br />

test. The contractor shall obtain the transmitter number from the JBLM<br />

Emergency Control Center (Building 4101). Forward and reflective power<br />

reading of the transmitter and transmitter zones shall be written<br />

inside the transmitter cabinet. The contractor shall ensure that a set<br />

of as-built drawings are on hand during the final acceptance test.<br />

a. Preliminary Testing: Conduct preliminary tests to ensure that<br />

devices and circuits are functioning properly. Tests shall meet the<br />

requirements of paragraph entitled "Minimum System Tests." After<br />

preliminary testing is complete, provide a letter certifying that the<br />

installation is complete and fully operable. The letter shall state<br />

that each initiating and indicating device was tested in place and<br />

functioned properly. The letter shall also state that panel functions<br />

were tested and operated properly. The letter shall include the names<br />

and titles of the witnesses to the preliminary tests. The Contractor<br />

and an authorized representative from each supplier of equipment shall<br />

be in attendance at the preliminary testing to make necessary<br />

adjustments.<br />

b. Request for Formal Inspection and Tests: When tests have been<br />

completed and corrections made, submit a signed, dated certificate with<br />

a request for formal inspection and Performance Verification Test (PVT)<br />

to the Contracting Offices <strong>Design</strong>ated Representative (COR), Directorate<br />

of Emergency Services, SAC-D, and Physical Security Branch. Upon<br />

acceptance, contractor shall receive results of the performance<br />

verification test.<br />

c. Final Testing: Notify the Contracting Officer in writing when the<br />

system is ready for final acceptance testing. Submit request for test<br />

at least 15 calendar days prior to the test date. The tests shall be<br />

performed in accordance with the approved test procedures in the<br />

presence of the Contracting Officer. Furnish instruments and personnel<br />

required for the tests. A final acceptance test will not be scheduled<br />

SECTION 28 31 76 Page 50


until the operation and maintenance (O&M) manuals are furnished to the<br />

Contracting Officer and the following are provided at the job site:<br />

(1) The systems manufacturer's technical representative<br />

(2) Marked-up red line drawings of the system as actually<br />

installed<br />

(3) Megger test results<br />

(4) Loop resistance test results<br />

(5) Complete program printout including input/output addresses<br />

The final tests shall be witnessed by the Contracting Offices <strong>Design</strong>ated<br />

Representative (COR). At this time, any and all required tests shall be<br />

repeated at their discretion. Following acceptance of the system, as-built<br />

drawings and O&M manuals shall be delivered to the Contracting Officer for<br />

review and acceptance. In existing buildings, the transfer of devices from<br />

the existing system to the new system and the permission to begin demolition<br />

of the old fire alarm system will not be permitted until the as-built<br />

drawings and O&M manuals are received.<br />

3.7.3 Minimum System Tests<br />

Test the system in accordance with the procedures outlined in NFPA 72, ISO<br />

7240-16, IEC 60268-16. The required tests are as follows:<br />

a. Megger Tests: After wiring has been installed, and prior to making<br />

any connections to panels or devices, wiring shall be megger tested for<br />

insulation resistance, grounds, and/or shorts. Conductors with 300<br />

volt rated insulation shall be tested at a minimum of 250 VDC.<br />

Conductors with 600 volt rated insulation shall be tested at a minimum<br />

of 500 VDC. The tests shall be witnessed by the Contracting Officer<br />

and test results recorded for use at the final acceptance test.<br />

b. Loop Resistance Tests: Measure and record the resistance of each<br />

circuit with each pair of conductors in the circuit short-circuited at<br />

the farthest point from the circuit origin. The tests shall be<br />

witnessed by the Contracting Officer and test results recorded for use<br />

at the final acceptance test.<br />

c. Verify the absence of unwanted voltages between circuit conductors<br />

and ground. The tests shall be accomplished at the preliminary test<br />

with results available at the final system test.<br />

d. Verify that the control unit is in the normal condition as detailed<br />

in the manufacturer's O&M manual.<br />

e. Test each initiating and indicating device and circuit for proper<br />

operation and response at the control unit. Smoke sensors shall be<br />

tested in accordance with manufacturer's recommended calibrated test<br />

method. Use of magnets is prohibited. Testing of duct smoke detectors<br />

shall comply with the requirements of NFPA 72.<br />

f. Test the system for specified functions in accordance with the<br />

contract drawings and specifications and the manufacturer's O&M manual.<br />

SECTION 28 31 76 Page 51


g. Test both primary power and secondary power. Verify, by test, the<br />

secondary power system is capable of operating the system for the time<br />

period and in the manner specified.<br />

h. Determine that the system is operable under trouble conditions as<br />

specified.<br />

i. Visually inspect wiring.<br />

j. Test the battery charger and batteries.<br />

k. Verify that software control and data files have been entered or<br />

programmed into the FACP. Hard copy records of the software shall be<br />

provided to the Contracting Officer.<br />

l. Verify that red-line drawings are accurate.<br />

m. Measure the current in circuits to ensure there is the calculated<br />

spare capacity for the circuits.<br />

n. Measure voltage readings for circuits to ensure that voltage drop<br />

is not excessive.<br />

o. Disconnect the verification feature for smoke sensors during tests<br />

to minimize the amount of smoke needed to activate the sensor. Testing<br />

of smoke sensors shall be conducted using real smoke. The use of<br />

canned smoke is prohibited.<br />

p. Measure the voltage drop at the most remote appliance (based on<br />

wire length) on each notification appliance circuit.<br />

q. Audibility Intelligibility testing of the Voice Evacuation<br />

Notification System shall be performed by installation engineers and/or<br />

security specialist for system functionality and required<br />

intelligibility in accordance with NFPA 72 for Voice Evacuation<br />

Systems, IEC 60268-16, and ASA S3.2. A minimum of .7 on the Sound<br />

Transmission Index (STI), at an expected average ambient noise level<br />

for the environment being tested, as registered by the DSP 30 analyzer<br />

will be required. Test points shall be identified and conducted<br />

throughout the facility at a point furthest from any single speaker<br />

and/or at the midpoint between any two speakers servicing the target<br />

area. Dependent on building ADA category and placement of visual<br />

alerting devices, recommend a reading at the speaker. Current<br />

calibration certificate shall be provided at the time of testing.<br />

r. Opening the circuit at not less than 10% of alarm initiating<br />

devices and notification appliances to test the wiring supervisory<br />

feature.<br />

s. Demonstrate modem communications with remote sites as specified by<br />

the COR. Dial in capability shall also, be demonstrated, using<br />

specified security.<br />

t. Demonstrate fiber optic communications with remote sites as<br />

specified by the COR. Dial in capability shall also, be demonstrated,<br />

using specified security.<br />

SECTION 28 31 76 Page 52


3.8 INSTRUCTION OF GOVERNMENT EMPLOYEES<br />

Equipment manufacturer shall provide 2 days on site. Training shall allow<br />

for classroom instruction as well as individual hands on programming,<br />

troubleshooting and diagnostics exercises. Additional system training shall<br />

provide the designated government personnel adequate knowledge, tools and<br />

equipment required to diagnose, repair, maintain and expand functions<br />

inherent to the system and shall be conducted on site and/or off site as<br />

necessary to fully qualify the government operations and maintenance<br />

technicians to perform all levels of maintenance, expansions and<br />

modifications to the fire alarm system, hardware, software and components.<br />

This training will include submittal to the government of all proprietary<br />

licenses, software, and tools to perform the required tasks. All<br />

specialized equipment and/or training to program, edit existing program, add<br />

or delete devices, etc. shall be provided as part of the fire alarm system.<br />

Systems that require factory certification to process or use their software<br />

shall include this training. Include transportation, lodging, etc. for two<br />

Government personnel when training is not available locally.<br />

3.8.1 Instructor<br />

Include in the project the services of an instructor, who has received<br />

specific training from the manufacturer for the training of other persons<br />

regarding the inspection, testing, and maintenance of the system provided.<br />

The instructor shall train the Government employees designated by the<br />

Contracting Officer, in the care, adjustment, maintenance, and operation of<br />

the fire alarm and fire detection system. Each instructor shall be<br />

thoroughly familiar with all parts of this installation. The instructor<br />

shall be trained in operating theory as well as in practical O&M work.<br />

3.8.2 Required Instruction Time<br />

Provide 16 hours of instruction after final acceptance of the system. The<br />

instruction shall be given during regular working hours on such dates and<br />

times as are selected by the Contracting Officer. The instruction may be<br />

divided into two or more periods at the discretion of the Contracting<br />

Officer. The training shall allow for rescheduling for unforeseen<br />

maintenance and/or fire department responses.<br />

3.8.3 Technical Data and Computer Software<br />

Provide, in manual format, lesson plans, operating instructions, maintenance<br />

procedures, and training data for the training courses. The operations<br />

training shall familiarize designated government personnel with proper<br />

operation of the installed system. The maintenance training course shall<br />

provide the designated government personnel adequate knowledge required to<br />

diagnose, repair, maintain, and expand functions inherent to the system.<br />

-- End of Section --<br />

SECTION 28 31 76 Page 53


SECTION 28 31 76 Page 54

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!