Reliability Tests: Humidity Freeze Test<br />
In the Low Temperature test, the MICRO Inverter will be considered meeting the<br />
Humidity Freeze requirements if it can turn-on and exports the maximum output<br />
power without any variations on performance.<br />
• 59.2VDC, 230VAC, 50Hz, CDD communication active<br />
• -40°C to +85°C, 85%RH (relative humidity)<br />
• 10 thermal cycles of 20 hours high, 4 hours low temperature<br />
• Inverters producing full rated output power<br />
• No faults detected