03.01.2015 Views

Product Overview - Flamco

Product Overview - Flamco

Product Overview - Flamco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Pre-set<br />

pressure<br />

Temperature increase<br />

Pre-set pressure 0.5 bar(g)<br />

• Increase in volume of water in %<br />

The table below shows data on the increase in<br />

volume of water in percentage points<br />

at increases in water temperature from<br />

10 °C to 110 °C.<br />

Volume increase<br />

10 - 25 °C 0.35%<br />

10 - 30 °C 0.43%<br />

10 - 35 °C 0.63%<br />

10 - 40 °C 0.75%<br />

10 - 45 °C 0.96%<br />

10 - 50 °C 1.18%<br />

10 - 55 °C 1.42%<br />

10 - 60 °C 1.68%<br />

10 - 70 °C 2.25%<br />

10 - 80 °C 2.89%<br />

10 - 90 °C 3.58%<br />

10 - 100 °C 4.34%<br />

10 - 110 °C 5.16%<br />

Pre-set pressure 1.0 bar(g)<br />

• Temperature in the Flexcon expansion vessel<br />

The maximum continuous temperature in the<br />

Flexcon expansion vessel is 70 °C.<br />

The minimum permitted temperature in the Flexcon<br />

expansion vessel is -10 °C.<br />

6<br />

5<br />

Volume increase [%]<br />

4<br />

3<br />

2<br />

1<br />

0<br />

10 20 30 40 50 60 70 80 90 100 110 120<br />

Temperature [°C]<br />

The graph shows the figures<br />

for other temperatures.<br />

20 <strong>Product</strong>overview • 2012 Technical specifications are subject to change.