Prescor safety valves:<br />
a complete range for the safety of your system<br />
If you are looking for reliable safety valves, you need<br />
look no further than <strong>Flamco</strong>'s Prescor range. The<br />
best protection for all sealed heating and chilled<br />
systems from overpressure. The Prescor valves are<br />
suitable for systems with a capacity of no higher than<br />
580 kW at 3.0 bar. Systems with greater capacity will<br />
need the heavy-duty Prescor S.<br />
The benefits of Prescor<br />
• High-quality materials and construction guarantee<br />
reliable function when you need it most.<br />
• If there is a rapid build-up of pressure, the valve will<br />
'pop' open. The pressure can then be discharged<br />
quickly.<br />
• CE conformity mark.<br />
• The opening pressure of all valves is individually<br />
tested 100%.<br />
Cap of high-impact<br />
plastic.<br />
Anti-ageing spring steel prevents the<br />
set pressure from drifting.<br />
Robust brass housing.<br />
The diaphragm prevents moisture and dirt<br />
from getting into the moving parts of the<br />
safety valve during blowing off.<br />
Valve seal of high-quality rubber, heat-resistant<br />
to 140 ºC. The hardness of the rubber is<br />
adapted to the set pressure of the valve. These<br />
properties mean that the valve will not stick to<br />
the valve seat.<br />
PRESCOR<br />
All Prescor safety valves are set to the specified<br />
opening pressure during manufacture. This setting<br />
cannot be adjusted. It is important to check the<br />
requirements for the Prescor valve in advance.<br />
When choosing a Prescor safety valve, the capacity<br />
shown on the safety valve must exceed the nominal<br />
boiler capacity.<br />
The set pressure and maximum output for which the<br />
valve is suitable are indicated on the valve.<br />
Mount on the boiler, or as close as possible to it, in the supply<br />
line. Never fit a stopcock between the boiler and the valve.<br />