S4000<br />

Basic device – SNT 4M63K<br />

Overview of devices | part numbers<br />

Type Rated voltage Terminals Part no. Std. pack<br />

SNT 4M63K-A 24 V AC/DC Screw terminals, pluggable<br />

R1.188.1050.0 1<br />

115 – 120 V AC Screw terminals, pluggable<br />

R1.188.1060.0 1<br />

230 V AC Screw terminals, pluggable<br />

R1.188.1070.0 1<br />

SNT 4M63K-C 24 V AC/DC Cage clamp, pluggable<br />

R1.188.2390.0 1<br />

Technical data<br />

Function<br />

Emergency stop relay, valve position and <strong>safety</strong> gate monitoring<br />

Function display<br />

3 LEDs, green<br />

Power supply circuit<br />

Rated voltage U N A1, A2 24 V AC/DC, 115-120 V AC, 230 V AC<br />

Rated consumption 24 V DC 2.0 W<br />

115-120 V AC, 230 V AC 2,6 W / 3.2 VA<br />

Rated frequency<br />

50 - 60 Hz<br />

S4000<br />

Operating voltage range U B<br />

0.85 - 1.1 x U N<br />

<strong>Electric</strong>al isolation supply circuit - control circuit<br />

yes (at U N = 115-230 V AC, 230 V AC)<br />

Control circuit<br />

Rated output voltage S13/S23 22 V DC<br />

Input current / peak current S14/S33, S22/S24 40 mA / 100 mA<br />

S34, S35 5 mA / 50 mA<br />

Response time t A1 / t A2<br />

40 ms / 600 ms<br />

Minimum ON time t M<br />

80 ms<br />

Recovery time t w<br />

100 ms<br />

Release time t R<br />

15 ms<br />

Synchronous time t s<br />

200 ms (CH1 → CH2)<br />

Max. resistivity, per channel 1) 24 V AC/DC ≤ (5 + (1.176 x U B / U N - 1) x 100) Ω<br />

115-120 V AC, 230 V AC ≤ (5 + (1.176 x U B / U N - 1) x 100) Ω<br />

Ausgangskreise<br />

Enabling paths 13/14, 23/24, 33/34 normally open contact<br />

Contact assignment<br />

forcebly guided<br />

Contact type<br />

Ag-alloy, gold-plated<br />

Rated switching voltage enabling path 230 V AC<br />

Max. thermal current I th enabling path 6 A<br />

Max. total current I² of all current path (Tu = 55 ºC) 9 A²<br />

Application category (NO) AC-15 U e 230 V, I e 3 A<br />

DC-13<br />

U e 24 V, I e 2.5 A<br />

Short-circuit protection (NO), lead fuse / circuit breaker<br />

6 A class gG / melting integral < 100 A²s<br />

Mechanical life<br />

10 7 switching cycles<br />

General data<br />

Creepage distances and clearances between the circuits EN 60664-1<br />

Protection degree according to DIN EN 60529 (housing / terminals)<br />

IP40 / IP20<br />

Ambient temperature / storage temperature -25 ºC - +55 ºC / -25 ºC - + 75 ºC<br />

Wire ranges screw terminals, fine-stranded / solid 1 x 0.14 mm² – 2.5 mm² / 2 x 0.14 mm² – 0.75 mm²<br />

fine-stranded with ferrules 1 x 0.25 mm² – 2.5 mm² / 2 x 0.25 mm² – 0.5 mm²<br />

Permissible torque<br />

0.5 - 0.6 Nm<br />

Wire ranges cage clamp terminals<br />

1 x 0.25 mm² – 1-5 mm²<br />

Weight<br />

0-21 kg / 0-25 kg<br />

Standards EN ISO 13849-1, EN 62061<br />

Approvals<br />

Y t h<br />

1)<br />

If two-channel devices are installed as single channel, the value is halved.<br />