POWER TERMINAL RATINGS<br />

WIRE RANGE: 14-1/0 AWG (2.5-35 MM 2 )<br />

TORQUE: 32 IN-LB (3.6 N-M)<br />

STRIP LENGTH: 0.67 IN (17 MM)<br />

USE 75 C CU WIRE ONLY<br />

17<br />

GROUND TERMINAL RATINGS (PE)<br />

WIRE RANGE: 6-1/0 AWG (16-35 MM 2 )<br />

TORQUE: 44 IN-LB (5 N-M)<br />

STRIP LENGTH: 0.83 IN (21 MM)<br />

21<br />

300 VDC EXT PWR SPLY TERM (PS+, PS-)<br />

WIRE RANGE: 22-10 AWG (0.5-4 MM 2 )<br />

TORQUE: 5.3 IN-LB (0.6 N-M)<br />

STRIP LENGTH: 0.35 IN (9 MM)<br />

9<br />

1-8 Installation/Wiring<br />

<strong>AC</strong> Input Phase Selection (Frames 5 & 6 Only)<br />

!<br />

ATTENTION: To avoid a shock hazard, ensure that all power to the<br />

drive has been removed before performing the following.<br />

Moving the “Line Type” jumper shown in Figure 1.2 will allow single or<br />

three-phase operation.<br />

Important: When selecting single-phase operation, input power must<br />

be applied to the R (L1) and S (L2) terminals only to assure<br />

power to the fan.<br />

Selecting/Verifying Fan Voltage (Frames 5 & 6 Only)<br />

Important: Read Attention statement above!<br />

Frames 5 & 6 utilize a transformer to match the input line voltage to the<br />

internal fan voltage. If your line voltage is different than the voltage class<br />

specified on the drive nameplate, it may be necessary to change<br />

transformer taps as shown below. Common Bus (DC input) drives<br />

require user supplied 120 or 240V <strong>AC</strong> to power the cooling fans. The<br />

power source is connected between “0 V<strong>AC</strong>” and the terminal<br />

corresponding to your source voltage (see Figure 1.4).<br />

Table 1.C Fan VA ratings (DC Input Only)<br />

Frame Rating (120V or 240V)<br />

5 100 VA<br />

6 138 VA<br />

Figure 1.2 Typical Locations - Phase Select Jumper & Transformer (Frame 5 shown)<br />

Optional<br />

Communications<br />

Module<br />

3-PH 1-PH<br />

LINE<br />

TYPE<br />

SPARE 1<br />

SPARE 2<br />

Phase Selection<br />

Jumper<br />

Fan Voltage<br />

OUTPUT<br />

INPUT <strong>AC</strong><br />

690 Volt Tap<br />

600 Volt Tap<br />

480 Volt Tap<br />

400 Volt Tap<br />

Publication 20B-UM002C-EN-P