1-26 Installation/Wiring<br />

Lifting/Torque Proving<br />

For Lifting/Torque Proving details, refer to page C-4.<br />

Using <strong>PowerFlex</strong> <strong>Drives</strong> with Regenerative Units<br />

If a Regenerative unit (i.e. 1336 REGEN) is used as a bus supply or<br />

brake, the common mode capacitors should be disconnected as described<br />

in Table 1.E.<br />

Connections to the 1336 REGEN<br />

Regen Brake Mode<br />

Frame(s)<br />

Terminals<br />

1336 REGEN <strong>PowerFlex</strong> <strong>700</strong><br />

0-4 DC+ BR1<br />

DC–<br />

DC–<br />

5-6 DC+ DC+<br />

DC–<br />

DC–<br />

Regenerative Bus Supply Mode<br />

Frame(s)<br />

Terminals<br />

1336 REGEN <strong>PowerFlex</strong> <strong>700</strong><br />

0-4 DC+ DC+<br />

DC–<br />

DC–<br />

5-6 DC+ DC+ of Common Bus <strong>Drives</strong><br />

DC–<br />

DC– of Common Bus <strong>Drives</strong><br />

Publication 20B-UM002C-EN-P