PowerFlex 700 AC Drives
PowerFlex 700 AC Drives
PowerFlex 700 AC Drives
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
3-2 Programming and Parameters<br />
➊➋➌➍<br />
File<br />
Group<br />
No.<br />
UTILITY<br />
Drive . . .<br />
Diagnostics<br />
MOTOR . . .<br />
Torq . . .<br />
Parameter Name & Description<br />
198 [Load Frm Usr Set]<br />
Loads a previously saved set of<br />
parameter values from a selected user<br />
set location in drive nonvolatile memory<br />
to active drive memory.<br />
216 [Dig In Status]<br />
Status of the digital inputs.<br />
Values<br />
Default:<br />
Options:<br />
x x x x x x x x x x 0 0 0 0 0 0<br />
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0<br />
Bit #<br />
434 [Torque Ref B Mult]<br />
Default:<br />
FV<br />
Defines the value of the multiplier for the<br />
[Torque Ref B Sel] selection.<br />
➎<br />
Digital In6<br />
Digital In5<br />
Digital In4<br />
Digital In3<br />
Digital In2<br />
Digital In1<br />
Min/Max:<br />
Units:<br />
Related<br />
0<br />
0<br />
1<br />
2<br />
3<br />
“Ready”<br />
“Ready”<br />
“User Set 1”<br />
“User Set 2”<br />
“User Set 3”<br />
199<br />
Read Only 361<br />
thru<br />
366<br />
1 = Input Present<br />
0 = Input Not Present<br />
x = Reserved<br />
1.0<br />
–/+32767.0<br />
0.1<br />
➏<br />
053<br />
No.<br />
➊<br />
➋<br />
➌<br />
➍<br />
➎<br />
Description<br />
File – Lists the major parameter file category.<br />
Group – Lists the parameter group within a file.<br />
No. – Parameter number. Note that all parameters in the <strong>PowerFlex</strong> <strong>700</strong>VC are 32 bit.<br />
= Parameter value cannot be changed until drive is stopped.<br />
FV = Parameter only displayed when [Motor Cntl Sel] is set to “4.”<br />
Parameter Name & Description – Parameter name as it appears on an LCD HIM, with a brief<br />
description of the parameter’s function.<br />
Values – Defines the various operating characteristics of the parameter. Three types exist.<br />
ENUM Default: Lists the value assigned at the factory. “Read Only” = no default.<br />
Options: Displays the programming selections available.<br />
Bit Bit: Lists the bit place holder and definition for each bit.<br />
Numeric Default: Lists the value assigned at the factory. “Read Only” = no default.<br />
Min/Max: The range (lowest and highest setting) possible for the parameter.<br />
Units: Unit of measure and resolution as shown on the LCD HIM.<br />
Important: Some parameters will have two unit values:<br />
• Analog inputs can be set for current or voltage with [Anlg In Config], param. 320.<br />
• Setting [Speed Units], parameter 79 selects Hz or RPM.<br />
Important: When sending values through DPI ports, simply remove the decimal<br />
point to arrive at the correct value (i.e. to send “5.00 Hz,” use “500”).<br />
➏ Related – Lists parameters (if any) that interact with the selected parameter. The symbol “ ”<br />
indicates that additional parameter information is available in Appendix C.<br />
Publication 20B-UM002C-EN-P