07.01.2015 Views

PowerFlex 700 AC Drives

PowerFlex 700 AC Drives

PowerFlex 700 AC Drives

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1-10 Installation/Wiring<br />

Power Terminal Block<br />

Refer to Figure 1.3 for typical locations.<br />

Table 1.D Power Terminal Block Specifications<br />

Wire Size Range (1) Torque<br />

No. Name Frame Description Maximum Minimum Maximum Recommended<br />

➊ Power Terminal 0 & 1 Input power and 4.0 mm 2 0.5 mm 2 1.7 N-m 0.8 N-m<br />

Block<br />

motor connections (10 AWG) (22 AWG) (15 lb.-in.) (7 lb.-in.)<br />

2 Input power and 10.0 mm 2 0.8 mm 2 1.7 N-m 1.4 N-m<br />

motor connections (6 AWG) (18 AWG) (15 lb.-in.) (12 lb.-in.)<br />

3 Input power and 25.0 mm 2 2.5 mm 2 3.6 N-m 1.8 N-m<br />

motor connections (3 AWG) (14 AWG) (32 lb.-in.) (16 lb.-in.)<br />

BR1, 2 terminals 10.0 mm 2 0.8 mm 2 1.7 N-m 1.4 N-m<br />

(6 AWG) (18 AWG) (15 lb.-in.) (12 lb.-in.)<br />

4 Input power and 35.0 mm 2 10.0 mm 2 4.0 N-m 4.0 N-m<br />

motor connections (1/0 AWG) (8 AWG) (35 lb.-in.) (35 lb.-in.)<br />

5 Input power, BR1, 50.0 mm 2 4.0 mm 2<br />

75 HP,<br />

480V/<br />

2, DC+, DC– and<br />

motor connections<br />

(1/0 AWG) (12 AWG)<br />

100 HP, PE 50.0 mm 2 4.0 mm 2<br />

600V<br />

(1/0 AWG) (12 AWG)<br />

5 Input power, DC+, 70.0 mm 2 10.0 mm 2 See Note (2)<br />

100 HP DC– and motor (2/0 AWG) (8 AWG)<br />

BR1, 2, terminals 50.0 mm 2<br />

(1/0 AWG)<br />

4.0 mm 2<br />

(12 AWG)<br />

PE 50.0 mm 2<br />

(1/0 AWG)<br />

4.0 mm 2<br />

(12 AWG)<br />

6 Input power, DC+, 150.0 mm 2 2.5 mm 2 6.0 N-m 6.0 N-m<br />

DC–, BR1, 2, PE, (300 MCM) (14 AWG) (52 lb.-in.) (52 lb.-in.)<br />

motor connections see note (3)<br />

➋ SHLD Terminal 0-6<br />

➌<br />

➍<br />

AUX Terminal<br />

Block<br />

Terminating point<br />

for wiring shields<br />

0-4<br />

5-6<br />

Auxiliary Control<br />

Voltage<br />

PS+, PS– (4)<br />

1.5 mm 2<br />

(16 AWG)<br />

4.0 mm 2<br />

(12 AWG)<br />

Fan Terminal 5-6 User Supplied<br />

Block (CB Only) Fan Voltage<br />

(page 1-8)<br />

— — 1.6 N-m<br />

(14 lb.-in.)<br />

4.0 mm 2<br />

(12 AWG)<br />

0.2 mm 2<br />

(24 AWG)<br />

0.5 mm 2<br />

(22 AWG)<br />

1.6 N-m<br />

(14 lb.-in.)<br />

— —<br />

0.6 N-m<br />

(5.3 lb.-in.)<br />

0.5 mm 2 0.6 N-m<br />

(22 AWG) (5.3 lb.-in.)<br />

0.6 N-m<br />

(5.3 lb.-in.)<br />

0.6 N-m<br />

(5.3 lb.-in.)<br />

(1) Maximum/minimum wire sizes that the terminal block will accept - these are not recommendations.<br />

(2) Refer to the terminal block label inside the drive.<br />

(3) Two wires connected in parallel to any of these terminals using two lugs may be required.<br />

(4) External control power: UL Installation-300V DC, ±10%, Non UL Installation-270-600V DC, ±10%<br />

0-3 Frame - 40 W, 165 mA, 5 Frame - 80 W, 90 mA. See Auxiliary Control Power Supply on page 1-9.<br />