ÐаÑалог Weidmuller: Enclosures and Cable Glands
ÐаÑалог Weidmuller: Enclosures and Cable Glands
ÐаÑалог Weidmuller: Enclosures and Cable Glands
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Accessories<br />
Fuse plug<br />
PTSI 4<br />
FieldPower ®<br />
Max. power loss for G fuse terminals in<br />
accordance with IEC 60947-7-3:<br />
• Overload protection: 1.6 W (overload operation<br />
• Short-circuit protection: 2 W (rated operation)<br />
Max. power loss per fuse at 23°C Tu.<br />
Do not exceed the max. power loss when<br />
selecting fuse cartridges. When a fuse is<br />
defective, the subsequent circuit is not voltage<br />
free.<br />
A practical tip:<br />
Space for spare fuses<br />
F<br />
Technical data<br />
Rated data according to IEC 60947-7-1<br />
Rated cross-section<br />
Rated voltage / Rated current<br />
Rated impulse voltage<br />
General data<br />
Cartridge fuse<br />
Outage display<br />
Type of mounting<br />
Insulation material/material colour<br />
UL 94 flammability rating<br />
Continuous operating temp., min.-max.<br />
Outgoing direction of conductor<br />
Test point<br />
Can be coded<br />
Conductor connection system<br />
No. of poles<br />
Number of connections / pole<br />
Clamping capacity, Push-In connection<br />
Clamping range, min.-max.<br />
Solid, min.-max.<br />
Str<strong>and</strong>ed, min.-max.<br />
Flexible, min.-max.<br />
Flexible, ferrule, 8 mm, DIN 46228/1, min-max.<br />
Flexible, ferrule, 8 mm, DIN 46228/4, min-max.<br />
Flexible, ferrule, 12 mm, DIN 46228/1, min-max.<br />
Flexible, ferrule, 12 mm, DIN 46228/4, min-max.<br />
Flexible, min.-max.<br />
Stripping length/Blade size<br />
Rated data acc. to UL<br />
St<strong>and</strong>ard<br />
Rated voltage/Rated current<br />
AWG conductor (field wiring), min./max.<br />
4 mm²<br />
690 V / 32 A<br />
8 kV<br />
6.3 x 32 mm (1/4 x 1 1/4")<br />
LED red<br />
Plugged<br />
PA GF/black<br />
V0<br />
-50 °C ... 120 °C<br />
90°<br />
2 mm<br />
Yes/Coded on PE<br />
Push In<br />
5<br />
1<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
0.5 mm² … 4 mm²<br />
12 mm / 3.0 x 0.5 mm<br />
UL 1059<br />
600 V/20 A<br />
16 /12<br />
Fuses <strong>and</strong> power loss:<br />
Examples Current 1.0 A 1.6 A 2.0 A 4 A 6.3 A 8 A 10 A 12.5 A<br />
SIBA, 189140<br />
500 V,<br />
440 V, 250 V<br />
T<br />
SIBA, 7006584<br />
400 V<br />
gRL<br />
1.0 x I N 0.35 W 0.32 W 0.36 W 0.56 W 0.69 W 0.88 W 1 W 1.25 W<br />
1.5 x I N 0.9 W 1.1 W 1.2 W 1.5 W 2.2 W 2.6 W 3.0 W 3.5 W<br />
1.0 x I N – – – – 1.2 W 1.5 W 1.8 W 1.9 W<br />
1.25 x I N – – – – 2.5 W 3.2 W 3.7 W 3.9 W<br />
No responsibility is taken for the correctness of this information.<br />
Further details can be obtained from the fuse manufacturers.<br />
Deratings curve according to IEC 60947-7-3<br />
Power loss / W<br />
Overload <strong>and</strong> short-circuit<br />
for overload operations<br />
Ambient temperature / °C<br />
Only short-circuit for<br />
nominal operations<br />
Note<br />
Safety fuse not included in delivery.<br />
Rated voltage <strong>and</strong> rated current with fuse are determined by the G-fuse<br />
cartridge in use.<br />
Ordering data<br />
Type Qty. Order No.<br />
PTSI 4/LD 400V AC 1 1961770000<br />
Note<br />
Accessories<br />
Note<br />
ZVR ZP2.5 locking element 1816130000<br />
F.14