CoNdaIr FF2
CoNdaIr FF2
CoNdaIr FF2
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Condair <strong>FF2</strong><br />
Technical data<br />
Humidifying sector (length)<br />
Humidifying capacity<br />
Pump supply voltage<br />
Pump operating pressure (standard)<br />
Pump power consumption<br />
Flowing pressure of intake water upstream of pump<br />
Min 1.3 m<br />
35...1080 kg/h<br />
380...400 VAC/3, 50..60 Hz<br />
80 bar<br />
0.5....4.5 kW<br />
2...10 bar<br />
Temperature of intake water upstream of pump max. 45 °C<br />
Conductance of intake water from osmosis<br />
3...15 uS/cm<br />
Control signal connection 0..5 VDC, 1..5 VDC, 0..10 VDC, 2..10<br />
VDC, 0..16 VDC, 3.2..16 VDC, 0..20<br />
mA, 4..20 mA<br />
Relative humidity control accuracy up to +/-4%<br />
Required air filter class upstream of humidifier<br />
Permissible air velocity<br />
F7<br />
0.5..4.0 m/s<br />
2545099<br />
Solutions for Indoor Climate<br />
heating<br />
ventilation<br />
cooling<br />
humidification<br />
dehumidification<br />
Walter Meier (Climate International) Ltd.<br />
Talstrasse 35-37, 8808 Pfäffikon, Switzerland<br />
Tel. +41 55 416 61 11, Fax +41 55 416 62 62<br />
info@waltermeier.com, www.waltermeier.com