Addressing<br />

Primary Addressing<br />

Secondary<br />

Addressing<br />

The network node supports primary and secondary addressing.<br />

Primary addresses 0...250 can be assigned to the network node.<br />

Primary address "0“ is preset by the manufacturer. In addition to the<br />

assigned primary address, the network node also responds to test<br />

address 254 and broadcast address 255. The primary address<br />

always serves to address the M-bus connected network node itself.<br />

The (virtual) devices stored in it can only be addressed through<br />

secondary addressing. (See also Page 8.)<br />

If the master sets the primary address to 253, the slaves will be<br />

identified through the secondary address. The slave, for its part, will<br />

respond with the correct primary address (provided that it has a<br />

primary address). The devices stored in the network node do not<br />

have any primary address and will equally respond on the M-bus<br />

with primary address 253.<br />

The secondary address succeeds the CI field (CI = 72) and is<br />

always structured as follows:<br />

Name Format Example<br />

Device<br />

4 bytes (BCD) 01234567<br />

Identification<br />

Manufacturer 2 bytes (binary) 3265h (12901dez.) = "LSE"<br />

Code<br />

Version 1 byte (binary) 01h<br />

Medium 1 byte (binary) 0Eh<br />

Table 2: Secondary Address on the M-bus<br />

The example shown in Table 2 is transmitted on the M-bus in the<br />

following order:<br />

67 45 23 01 65 32 01 0E<br />

Device<br />

Identification<br />

The device identification is always given as an 8-digit figure shown in<br />

binary-coded decimal numbers (BCD).<br />

18/56 For intra-company use only<br />

Siemens<br />

Netzwerkknoten <strong>WTT16</strong>/<strong>WTX16</strong><br />

Building Technologies The <strong>Network</strong> <strong>Node</strong> 09.03.2007