Example:<br />

RSP_UD: 42 7A 23 01 07 79 78 56 34 12 65 32 14 0E 0C 78 32 54<br />

76 98<br />

Memory block #1 (DIF = 42)<br />

Memory position<br />

291 (123h)<br />

Device ID 12345678<br />

Manufacturer ID<br />

LSE (3265h)<br />

Version<br />

20 (14h)<br />

Medium<br />

14 (0Eh)<br />

In the response, too, the lowest-value byte is transmitted first (LSB<br />

first).<br />

If the memory location is not used or if the memory location number<br />

selected is invalid, only a shortened response will come up:<br />

RSP_UD #1:<br />

42 7A mp mp<br />

RSP_UD #2:<br />

82 01 7A mp mp<br />

mp mp queried memory location number (memory position) –<br />

(16-bit binary value (unsigned integer))<br />

Search Run und<br />

Readout of an M-<br />

bus with <strong>Network</strong><br />

<strong>Node</strong><br />

Search Run of<br />

Primary-address<br />

Devices<br />

In order for an M-bus master to communicate with an M-bus slave,<br />

the master must know the address of the device. To this end, it must<br />

learn in all the available devices on the M-bus when it is first started.<br />

The master uses different approaches for primary-address and<br />

secondary-address devices.<br />

A total 251 M-bus slaves may be connected to an M-bus line.<br />

1. Accessing test address 254 with SND_NKE<br />

a. If no response has been received within the<br />

maximum response delay, there are no devices on<br />

the M-bus. (The master should repeat the test.)<br />

b. If exactly one CONFIRM has been received within<br />

the maximum response delay, there is only one<br />

device on the M-bus. The master sends an<br />

REQ_UD2 to read out the device data.<br />

36/56 For intra-company use only<br />

Siemens<br />