Device Type (ASN)<br />
Example:<br />
Status / Error Date<br />
Example:<br />
<strong>Network</strong> Index<br />
Example:<br />
This data point shows the device type. For the network node, the<br />
device type is either <strong>WTT16</strong> or <strong>WTX16</strong>. Device types are presented<br />
as a 5-character ASCII string in inverse order.<br />
0D FD 0B 05 36 31 54 54 57<br />
shows a <strong>WTT16</strong>.<br />
The error date contains a valid value if the meter status indicates a<br />
permanent device error or temporary or permanent interruption of<br />
communication. (See also Page 29.) An invalid date is shown with<br />
FFh FFh.<br />
32 6C FF FF<br />
This is not a valid error date.<br />
For servicing purposes, it is often useful to establish exactly in which<br />
radio network the network node is located. This data point furnishes<br />
such information.<br />
02 FA 3D nn kk<br />
nn<br />
kk<br />
M-bus primary address of the network node through<br />
which the radioing devices are presented on the M-bus –<br />
8-bit binary coded<br />
is the primary radio broadcast address of the node itself.<br />
The primary radio broadcast address of a network node<br />
is shown on display level A - 8-bit binary coded.<br />
Example:<br />
Main Battery Power<br />
Consumption<br />
02 FA 3D 02 0A<br />
shows network node 10. It forms part of the network that is reached<br />
through the network node with M-bus primary address 02 on the M-<br />
bus.<br />
This data point shows the remaining capacity of the exchangeable<br />
main battery in percent. Since this consumption cannot be presented<br />
as a normal M-bus data point, the unit of this value is shown with a<br />
variable VIF. The unit is ASCII-coded and rendered in inverse order<br />
according to the M-bus. It shows "% Batt." A 255 consumption value<br />
signals that the network node concerned is fed externally and not fed<br />
through a battery. There is no data point for the capacity of the<br />
backup battery.<br />