Manufacturer ID<br />

The manufacturer ID shows the manufacturer's globally unique<br />

code. The manufacturer ID may be computed from the three letters<br />

of the manufacturer identifier. The following formula is used for this<br />

purpose:<br />

Manufacturer ID = [ASCII(1st letter) – 64] x 32 x 32<br />

+ [ASCII(2nd letter) – 64] x 32<br />

+ [ASCII(3rd letter) – 64]<br />

Siemens Building Technologies electronic (formerly known as Landis<br />

und Staefa electronic) with the "LSE" identifier thus carries the<br />

manufacturer ID "12901."<br />

Version<br />

Medium<br />

The version provides the current software version of the device.<br />

Since the software version is part of the address, a network node will<br />

change its address following a software update. In other words,<br />

should a node be given a software update after it had been<br />

connected to an M-bus master, a new search run needs to be<br />

performed, so that the master can address this network node again.<br />

The medium indicates the physical measurand of the device.<br />

Medium 14 has been set aside for the network node which is not a<br />

meter.<br />

Medium<br />

(decimal)<br />

Medium<br />

(hex) Meaning<br />

00 00 Other<br />

01 01 Oil<br />

02 02 Electricity<br />

03 03 Gas<br />

04 04 Heat (volume measurement in return pipe )<br />

05 05 Steam<br />

06 06 Hot water (30°C to 90°C)<br />

07 07 Cold water<br />

08 08 Heat cost allocator<br />

09 09 Compressed air<br />

10 0A Cold (volume measurement in return pipe)<br />

11 0B Cold (volume measurement in flow pipe)<br />

12 0C Heat (volume measurement in flow pipe)<br />

13 0D Heat / cold<br />

14 0E <strong>Network</strong> node / system device<br />

15 0F Unknown<br />

Table 3: List Showing all the Media Supported in Accordance with [3]<br />

For intra-company use only 19/56<br />

Siemens<br />

Netzwerkknoten <strong>WTT16</strong>/<strong>WTX16</strong><br />

Building Technologies The <strong>Network</strong> <strong>Node</strong> 09.03.2007