14.11.2012 Views

Automation platform Modicon Premium - Schneider Electric

Automation platform Modicon Premium - Schneider Electric

Automation platform Modicon Premium - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Characteristics (continued)<br />

<strong>Premium</strong> PLCs have been developed to comply with major national and international standards on electronic industrial automation equipment.<br />

See pages 9/8 to 9/19 "Standards, certification and environmental conditions".<br />

Characteristics and performance (continued)<br />

Types of processor TSX P57<br />

304M<br />

TSX P57<br />

3634M<br />

TSX P57<br />

354M<br />

TSX P57<br />

454M<br />

TSX P57<br />

4634M (1)<br />

Maximum No. of racks 4/6/8 slots 16 16 16<br />

configuration<br />

12 slots 8 8 8<br />

Max. no. of slots for modules 128 128 128<br />

Functions Max. no in-rack<br />

(3)<br />

TSX P57<br />

554M<br />

Discrete I/O 1024 2040 2040<br />

Analog I/O 128 256 512<br />

Process control<br />

channels<br />

<strong>Modicon</strong> <strong>Premium</strong> automation<br />

<strong>platform</strong><br />

Unity processors<br />

15 (up to 45 parameterizable simple<br />

loops)<br />

20 (up to 60 parameterizable<br />

simple loops)<br />

TSX P57<br />

5634M<br />

6634M<br />

30 (up to 90 parameterizable<br />

simple loops)<br />

Programmable loops via EFB control blocks (with Unity Pro Large and Extra Large)<br />

Application-specific<br />

channels, number<br />

32 64 64<br />

Application-specific<br />

channels, type<br />

Counter, axis control, weighing and serial links (Modbus, Uni-Telway and asynchronous)<br />

Integrated Ethernet – 1 – 1 – 1<br />

connections Fipio manager – 1 (127 agents) – 1<br />

(127 agents)<br />

–<br />

Serial link 1 link with 2 connectors (TER and 1 x 12 Mbit/s USB link (TER),<br />

AUX) 19.2 or 115 Kbit/s<br />

1 x 19.2 Kbit/s (AUX) link<br />

Max. no. of Network (Ethernet,<br />

3 3 including 1 3 4 4 including 1 4 4 including 1<br />

connections Fipway, Ethway,<br />

integrated<br />

integrated<br />

integrated<br />

Modbus Plus)<br />

Ethernet port<br />

Ethernet port (4)<br />

Ethernet port (4)<br />

AS-Interface bus 8 8 8<br />

CANopen or<br />

Modbus Plus bus<br />

1<br />

InterBus or<br />

Profibus DP bus<br />

3 4 5<br />

Memories Maximum Without PCMCIA card Kb 192 prog. + data 208 prog. 440<br />

1024/2048 (5)<br />

capacity<br />

+ data prog. + data<br />

prog. + data<br />

With PCMCIA card Kb 1792 prog.<br />

1792 prog. 2048 prog.<br />

7168 prog.<br />

192 data<br />

208 data 440 data<br />

1024/2048 data (5)<br />

Data storage Kb 16,384 (limited to 8192 with current PCMCIA cards)<br />

Maximum size Located internal bits bits 16,384 32,768 32,768<br />

of object zones (%Mi)<br />

Located internal data Kb 64 for internal words %Mpi<br />

128 for int. words %Mpi<br />

64 for constant words %Kpi<br />

64 for const. words %Kpi<br />

Unlocated internal Kb Elementary EDT and derived DDT Elementary EDT and derived DDT data: Unlimited (6)<br />

data<br />

data: 64 Kb<br />

DFB and EFB function blocks: DFB and EFB function blocks:<br />

- Size per instance: 64 Kb<br />

- Size per instance: unlimited (6),<br />

- Unlimited number of instances (6) - Unlimited number of instances (6)<br />

Application Tasks Master 1 1 1<br />

structure<br />

Fast 1 1 1<br />

Auxiliary – – 4<br />

Event-triggered 64 (1 of which has priority) 64 (1 of which has priority) 128 (1 of which has priority)<br />

32 (timers)<br />

Execution Without Boolean ms 0.12 0.039…0.057 (7) 0.0375...0.045 (7)<br />

time for one<br />

instruction<br />

PCMCIA card On word or fixed-point<br />

arithmetic<br />

ms 0.17 0.054…0.073 (7) 0.045...0.060 (7)<br />

On floating points ms 1.75...3.00 (7) 0.55…0.63 (7) 0.48...0.56 (7)<br />

With PCMCIA Boolean ms 0.17 0.048…0.057 (7) 0.0375...0.045 (7)<br />

card<br />

On word or fixed-point<br />

arithmetic<br />

ms 0.32 0.054…0.073 (7) 0.045...0.060 (7)<br />

On floating points ms 1.75...3.00 (7) 0.55…0.63 (7) 0.48...0.56 (7)<br />

Typical Without 100% Boolean Kinst/ 6.72 15.75 20.26<br />

program PCMCIA card<br />

ms<br />

code<br />

execution<br />

time for 1<br />

Kinstruction<br />

With PCMCIA<br />

card<br />

65% Boolean and<br />

35% fixed arithmetic<br />

100% Boolean<br />

Kinst/<br />

ms<br />

Kinst/<br />

ms<br />

5.11<br />

4.59<br />

11.40<br />

15.75<br />

14.00<br />

20.26<br />

65% Boolean and Kinst/ 3.11 11.40 14.00<br />

35% fixed arithmetic ms<br />

System overhead Master task ms 1.00 1.00 1.00<br />

Fast task ms 0.35 0.08 0.07<br />

(4) TSX FPP 20 PCMCIA Fipway card not supported.<br />

(5) The first value applies to TSX P57 554M/5634M processors and the second to the TSX P57 6634M processor .<br />

(6) Within the limits of the processor's data memory capacity<br />

(7) Values limited according to type of instruction .<br />

1/11<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10

Hooray! Your file is uploaded and ready to be published.