14.11.2012 Views

Automation platform Modicon Premium - Schneider Electric

Automation platform Modicon Premium - Schneider Electric

Automation platform Modicon Premium - Schneider Electric

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Characteristics<br />

<strong>Modicon</strong> <strong>Premium</strong><br />

automation <strong>platform</strong><br />

Power supply and fan modules<br />

Caracteristics<br />

Type of power supply module TSX PSY 1610M TSX PSY 3610M TSX PSY 5520M<br />

Primary Voltage Nominal V c 24 c 24 c 24������48<br />

Limit (ripple included) V c 19��2������30 (1)<br />

c 19��2������60<br />

(possible up to 34 V for 1 h in evry 24 h)<br />

Frequency Nominal/limit Hz – – –<br />

Currency Nominal input A rms ≤ 1��5 at c 24 V ≤ 2��7 at c 24 V ≤ 3 at c 24 V<br />

≤ 1��5 at c 48 V<br />

Initial start up<br />

at 25 °C (2)<br />

1 inrush A 100 at c 24 V 150 at c 24 V 15 at c 24 V<br />

15 at c 48 V<br />

I²t on activation A ² s 12��5 20 50 at c 24 V<br />

55 at c 48 V<br />

It on activation As 0��2 0��5 7 at c 24 V<br />

6 at c 48 V<br />

Duration of<br />

micro breaks<br />

Main supply (accepted) ms ≤ 1 ≤ 1 ≤ 1<br />

Integrated protection By fuse 5 x 20,<br />

time-delayed 3��5 A<br />

No By fuse 5 x 20,<br />

time-delayed 5 A<br />

Secondary Power Total useful (typical) W 30 50 50<br />

Output c 5 V Nominal voltage V 5 5 5<br />

Nominal current A 3 7 7<br />

Power (typical) W 15 35 35<br />

Output<br />

c 24 VR (3)<br />

Nominal voltage V U mains - 0��6 U mains - 0��6 24<br />

Nominal current A 0��6 0��6 0��8<br />

Power (typical) W 15 19 19<br />

Output c 24 V sensors – – –<br />

Integrated protection on outputs (4) Yes, against overloads, short-circuits and overvoltages<br />

Conformity to standards IEC 61131-2<br />

Isolation Dielectric<br />

withstand<br />

Insulation<br />

resistance<br />

Primary/secondary and<br />

primary/earth<br />

Primary/secondary and<br />

primary/earth<br />

V eff Non isolated, internal 0 V connected to PLC earth 2000 - 50/60 Hz - 1 min<br />

MW – ≥ 10<br />

Type od power supply module TSX PSY 2600M TSX PSY 5500M TSX PSY 8500M<br />

Primary Voltage Nominal V a 100������240 a 100������120/200������240<br />

Limit (ripple included) V a 85������264 a 85������140/190������264 a 85������140/170������264<br />

Frequencys Nominal/limit Hz 50…60/47…63<br />

Current Nominal input A rms 0��5 at a 100 V<br />

0��3 at a 240 V<br />

Initial start up<br />

at 25 °C<br />

(2)<br />

I inrush current A 37 at a 100 V<br />

75 at a 240 V<br />

I²t on activation A²s 0��63 at a 100 V<br />

2��6 at a 240 V<br />

It on activation As 0��034 at a 100 V<br />

0��067 at a 240 V<br />

1��7 at a 100 V<br />

0��5 at a 240 V<br />

38 at a 100 V<br />

38 at a 240 V<br />

4 at a 100 V<br />

2 at a 240 V<br />

0��11 at a 100 V<br />

0��11 at a 240 V<br />

Duration of<br />

micro breaks<br />

Mains supply (accepted) ms ≤ 10 ≤ 10 ≤ 10<br />

Integrated protection By fuse 5 x 20, time-delayed, 4 A<br />

Secondary Power Total useful (typical) W 26 50 77 (5)<br />

Output c 5 V Nominal voltage V 5 5 5<br />

Nominal current A 5 7 15<br />

Power (typical) W 25 35 75<br />

Output<br />

c 24 VR (3)<br />

Nominal voltage V 24 24 –<br />

Nominal current A 0��6 0��8 –<br />

Power (typical) W 15 19 –<br />

1��7 at a 100 V<br />

0��5 at a 240 V<br />

30 at a 100 V<br />

60 at a 240 V<br />

15 at a 100 V<br />

8 at a 240 V<br />

0��15 at a 100 V<br />

0��15 at a 240 V<br />

Output<br />

c 24 VC<br />

Sensors A 0��5 0��8 1��6 (TBTS)<br />

Integrated protection on outputs (4) Yes, against overloads, short-circuits and overvoltages<br />

Conformity to standards IEC 61131-2<br />

Isolation Dielectric<br />

withstand<br />

Insulation<br />

resistance<br />

Description:<br />

page 2/2<br />

Primary/secondary and<br />

primary/earth<br />

Primary/secondary and<br />

primary/earth<br />

Functions:<br />

page 2/4<br />

V eff 2000 - 50/60 Hz - 1 min 3000 - 50/60 Hz - 1 min<br />

MW ≥ 100<br />

(1) When supplying modules with relay outputs, the range is reduced to 21.6…26.4 V.<br />

(2) These values should be taken into account when starting several devices simultaneously and<br />

for sizing protection devices.<br />

(3) Output c 24 V for supplying relays of modules with relay outputs.<br />

(4) Output c 24 VR, cannot be accessed by the user and is protected by a fuse located beneath<br />

the module (5 x 20, 4 A, type Medium)<br />

(5) 77 W at 60 °C, 85 W at 55 °C, or 100 W at 55 °C using TSX FANppP fan modules.<br />

References:<br />

page 2/5<br />

2/3<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!