Automation platform Modicon Premium - Schneider Electric
Automation platform Modicon Premium - Schneider Electric
Automation platform Modicon Premium - Schneider Electric
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
References,<br />
dimensions,<br />
mounting<br />
TSX PSY 2600M<br />
TSX PSY 5500M<br />
TSX FAN ppP<br />
<strong>Modicon</strong> <strong>Premium</strong><br />
automation <strong>platform</strong><br />
Power supply and fan modules<br />
References<br />
Each TSX RKY p/pEX rack must be equipped with a single or double format power supply<br />
module (slot marked PS)��<br />
The power required to supply each TSX RKY rack depends on the type and number of modules<br />
installed in the rack�� It is therefore necessary to establish a power consumption table rack by rack<br />
in order to determine the TSX PSY power supply module most suitable for each rack (see pages<br />
9/6 and 9/7)��<br />
Power supply module<br />
Power Available power (1) Format Reference Weight<br />
supply c 5 V c 24 VR c 24 VC Total<br />
(2)<br />
kg<br />
c 24 V non 15 W 15 W – 30 W Standard TSX PSY 1610M 0��540<br />
isolated (3) 35 W 19 W – 50 W Double TSX PSY 3610M 0��780<br />
c 24...48 V<br />
isolated<br />
35 W 19 W – 50 W Double TSX PSY 5520M 0��890<br />
a 100…240 V25<br />
W 15 W 12 W 26 W Standard TSX PSY 2600M 0��510<br />
a 100…120 V 35 W 19 W 19 W 50 W Double TSX PSY 5500M 0��620<br />
a 200…240 V75<br />
W – 38 W<br />
(SELV)<br />
77 W Double TSX PSY 8500M 0��740<br />
Accessories<br />
Description Use Quantity Reference Weight<br />
kg<br />
Battery Internal RAM memory backup (position<br />
in power supply modules)<br />
1 battery TSX PLP 01 0��010<br />
10<br />
batteries<br />
TSX PLP 101 0��100<br />
Fan modules<br />
Description Use Power supply Reference Weight<br />
kg<br />
Fan modules<br />
(4)<br />
Dimensions/mounting TSX FAN pP<br />
Side view Front view Fan module mounting<br />
58<br />
110 146<br />
Description:<br />
page 2/2<br />
Characteristics:<br />
page 2/3<br />
For TSX RKY p or<br />
TSX RKY pEX racks<br />
c 24 V TSX FAN D2P 0��500<br />
a 100…120 V TSX FAN A4P 0��500<br />
a 200…240 V TSX FAN A5P 0��500<br />
(1) Voltages c 5 V and c 24 VR for power supply to <strong>Premium</strong> modules, voltage c 24 VC for<br />
supplying power to input sensors. The sum of absorbed power on each voltage (c 5 V,<br />
c 24 VR and c 24 VC) should not exceed the total power of the module. See power<br />
consumption table on page 9/6.<br />
(2) Product supplied with a processor RAM memory backup battery.<br />
(3) The internal 0 V of the module is connected to the PLC earth.<br />
(4) One fan module for rack with 4 or 6 positions, two fan modules for rack with 8 positions and<br />
three fan modules for rack with 12 positions. Product supplied with bilingual Quick Reference<br />
Guide: English and French.<br />
138<br />
Functions:<br />
page 2/4<br />
54<br />
88,9 58,3<br />
2/5<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10