Standard Emergency Lighting - Beta Industries
Standard Emergency Lighting - Beta Industries
Standard Emergency Lighting - Beta Industries
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
AC Output Soccorgroup<br />
AC output Soccorgroup In the event of a power failure,<br />
the loads connected to the Maintained and<br />
non-maintained outputs are connected to the inverter<br />
via a high speed changeover device.<br />
The PWM (Pulse With Modulation) inverter operating<br />
at high frequency, converts the DC battery voltage<br />
into a stabilised, low-distortion sinusoidal AC<br />
voltage.<br />
The inverter is protected against overload and short<br />
circuit by means of an electronic current limiter that<br />
is capable of ensuring safe operation under all<br />
conditions.<br />
Soccorgroups are equipped with an AUTOTEST<br />
function where the built-in microprocessor will periodically<br />
perform functional and duration tests.<br />
An RS232 serial port also allows the central system<br />
to be connected to a PC for remote control and<br />
monitoring.<br />
MAIN APPLICATIONS<br />
- <strong>Emergency</strong> lighting and other safety systems.<br />
- Mixed mainatained and non-maintained AC loads.<br />
B<br />
TECHNICAL<br />
SPECIFICATIONS<br />
A<br />
C<br />
Power supply voltage:<br />
230V ± 15% / 50Hz<br />
Single phase<br />
Non-Maintained output:<br />
- absent when mains is present<br />
- derived from the inverter in the<br />
absence of in tolerance mains<br />
supply (± 2%)<br />
Maintained output:<br />
- from the mains when<br />
mains is present<br />
- derived from the inverter in the<br />
absence of in tolerance mains<br />
supply (± 2%)<br />
Battery output:<br />
- stabil. voltage ± 1%<br />
Charging system:<br />
- switch mode<br />
- IU charging curve<br />
Changeover time:<br />
- equal to or less than 500ms<br />
Protection:<br />
- fuses on power supply<br />
- fuse on NM-M load<br />
- battery fuse<br />
- minimum battery voltage cut-off<br />
remote control switch<br />
- electronic current limiter<br />
on inverter<br />
LED Indicators:<br />
- power mains present/absent<br />
- output present/absent<br />
- complete battery recharge<br />
- maintaining battery charge<br />
- general failure<br />
- emergency<br />
- battery in reserve status<br />
- battery failure<br />
- self-testing<br />
Display signals and measures<br />
- Power supply: V [VAC],<br />
I [A], f [Hz]<br />
- Output: V [VAC], I [A], f [Hz]<br />
- Battery: V [VDC], I [A]<br />
- Events: Type, Date<br />
- Status: Failure type<br />
Remote Signals:<br />
- operation from the mains<br />
- operation from the inverter<br />
- battery in reserve status<br />
- general failure<br />
Storage batteries:<br />
- sealed lead acid batteries<br />
Recharging:<br />
- 80% in 10 hours, approx.<br />
Recharging in 6 hours:<br />
- on request<br />
Operative temperature:<br />
- 10 to + 40°C<br />
Cubicle:<br />
- single unit also containing<br />
the storage batteries<br />
- IP21 protection rating<br />
AT<br />
ALTERNATING- CURRENT CENTRAL BATTERY DEVICES<br />
NON MAINTAINED / MAINTAINED LIGHTING<br />
Ordering code Article Apparent power VA Active power W Duration Battery Battery Cubicles Dimensions (AxBxC) Weight kg<br />
3249 SCASE/SA 1KVA 1P-1ELM 1000 700 1 2x(12V 65Ah) NO 80x80x40 140<br />
3250 SCASE/SA 1KVA 3P-1ELM 1000 700 3 4x(12V 65Ah) NO 80x80x40 200<br />
3251 SCASE/SA 1.5KVA 1P-1ELM 1500 1000 1 2x(12V 85Ah) NO 80x80x40 170<br />
3252 SCASE/SA 1.5KVA 3P-1ELM 1500 1000 3 4x(12V 85Ah) NO 80x80x40 230<br />
3253 SCASE/SA 2KVA 1P-1ELM 2000 1400 1 4x(12V 65Ah) NO 80x80x40 210<br />
3254 SCASE/SA 2KVA 3P-1ELM 2000 1400 3 8x(12V 65Ah) NO 80x140x40 300<br />
3255 SCASE/SA 3KVA 1P-1ELM 3000 2100 1 8x(12V 50Ah) NO 80x140x40 300<br />
3256 SCASE/SA 3KVA 3P-1ELM 3000 2100 3 8x(12V 85Ah) NO 80x140x40 400<br />
3257 SCASE/SA 4KVA 1P-1ELM 4000 2800 1 8x(12V 65Ah) NO 80x140x40 360<br />
3258 SCASE/SA 4KVA 3P-2ELM 4000 2800 3 16x(12V 65Ah) 1 MOB-2 80x140x40 360<br />
3259 SCASE/SA 5KVA 1P-1ELM 5000 3500 1 8x(12V 85Ah) NO 80x140x40 390<br />
3260 SCASE/SA 5KVA 3P-2ELM 5000 3500 3 16x(12V 85Ah) 1 MOB-2 80x140x40 420<br />
3261 SCASE/SA 6KVA 1P-1ELM 6000 4200 1 8x(12V 85Ah) NO 80x140x40 450<br />
3262 SCASE/SA 6KVA 3P-2ELM 6000 4200 3 16x(12V 85Ah) 1 MOB-2 80x140x40 450<br />
3263 SCASE/SA 7KVA 1P-2ELM 7000 4900 1 24x(12V 38Ah) 1 MOB-2 80x140x40 320<br />
3264 SCASE/SA 7KVA 3P-2ELM 7000 4900 3 24x(12V 85Ah) 1 MOB-2 80x140x40 450<br />
3265 SCASE/SA 8.5KVA 1P-2ELM 8500 6000 1 16x(12V 65Ah) 1 MOB-2 80x140x40 400<br />
3266 SCASE/SA 8.5KVA 3P-3ELM 8500 6000 3 32x(12V 85Ah) 2 MOB-2 80x140x40 270<br />
3267 SCASE/SA 10KVA 1P-2ELM 10000 7000 1 24x(12V 65Ah) 1 MOB-2 80x140x40 290<br />
3268 SCASE/SA 10KVA 3P-4ELM 10000 7000 3 48x(12V 65Ah) 3 MOB-2 80x140x40 310<br />