AC Output Soccorgroup<br />

AC output Soccorgroup In the event of a power failure,<br />

the loads connected to the Maintained and<br />

non-maintained outputs are connected to the inverter<br />

via a high speed changeover device.<br />

The PWM (Pulse With Modulation) inverter operating<br />

at high frequency, converts the DC battery voltage<br />

into a stabilised, low-distortion sinusoidal AC<br />

voltage.<br />

The inverter is protected against overload and short<br />

circuit by means of an electronic current limiter that<br />

is capable of ensuring safe operation under all<br />

conditions.<br />

Soccorgroups are equipped with an AUTOTEST<br />

function where the built-in microprocessor will periodically<br />

perform functional and duration tests.<br />

An RS232 serial port also allows the central system<br />

to be connected to a PC for remote control and<br />

monitoring.<br />

MAIN APPLICATIONS<br />

- <strong>Emergency</strong> lighting and other safety systems.<br />

- Mixed mainatained and non-maintained AC loads.<br />

B<br />

TECHNICAL<br />

SPECIFICATIONS<br />

A<br />

C<br />

Power supply voltage:<br />

230V ± 15% / 50Hz<br />

Single phase<br />

Non-Maintained output:<br />

- absent when mains is present<br />

- derived from the inverter in the<br />

absence of in tolerance mains<br />

supply (± 2%)<br />

Maintained output:<br />

- from the mains when<br />

mains is present<br />

- derived from the inverter in the<br />

absence of in tolerance mains<br />

supply (± 2%)<br />

Battery output:<br />

- stabil. voltage ± 1%<br />

Charging system:<br />

- switch mode<br />

- IU charging curve<br />

Changeover time:<br />

- equal to or less than 500ms<br />

Protection:<br />

- fuses on power supply<br />

- fuse on NM-M load<br />

- battery fuse<br />

- minimum battery voltage cut-off<br />

remote control switch<br />

- electronic current limiter<br />

on inverter<br />

LED Indicators:<br />

- power mains present/absent<br />

- output present/absent<br />

- complete battery recharge<br />

- maintaining battery charge<br />

- general failure<br />

- emergency<br />

- battery in reserve status<br />

- battery failure<br />

- self-testing<br />

Display signals and measures<br />

- Power supply: V [VAC],<br />

I [A], f [Hz]<br />

- Output: V [VAC], I [A], f [Hz]<br />

- Battery: V [VDC], I [A]<br />

- Events: Type, Date<br />

- Status: Failure type<br />

Remote Signals:<br />

- operation from the mains<br />

- operation from the inverter<br />

- battery in reserve status<br />

- general failure<br />

Storage batteries:<br />

- sealed lead acid batteries<br />

Recharging:<br />

- 80% in 10 hours, approx.<br />

Recharging in 6 hours:<br />

- on request<br />

Operative temperature:<br />

- 10 to + 40°C<br />

Cubicle:<br />

- single unit also containing<br />

the storage batteries<br />

- IP21 protection rating<br />

AT<br />

ALTERNATING- CURRENT CENTRAL BATTERY DEVICES<br />

NON MAINTAINED / MAINTAINED LIGHTING<br />

Ordering code Article Apparent power VA Active power W Duration Battery Battery Cubicles Dimensions (AxBxC) Weight kg<br />

3249 SCASE/SA 1KVA 1P-1ELM 1000 700 1 2x(12V 65Ah) NO 80x80x40 140<br />

3250 SCASE/SA 1KVA 3P-1ELM 1000 700 3 4x(12V 65Ah) NO 80x80x40 200<br />

3251 SCASE/SA 1.5KVA 1P-1ELM 1500 1000 1 2x(12V 85Ah) NO 80x80x40 170<br />

3252 SCASE/SA 1.5KVA 3P-1ELM 1500 1000 3 4x(12V 85Ah) NO 80x80x40 230<br />

3253 SCASE/SA 2KVA 1P-1ELM 2000 1400 1 4x(12V 65Ah) NO 80x80x40 210<br />

3254 SCASE/SA 2KVA 3P-1ELM 2000 1400 3 8x(12V 65Ah) NO 80x140x40 300<br />

3255 SCASE/SA 3KVA 1P-1ELM 3000 2100 1 8x(12V 50Ah) NO 80x140x40 300<br />

3256 SCASE/SA 3KVA 3P-1ELM 3000 2100 3 8x(12V 85Ah) NO 80x140x40 400<br />

3257 SCASE/SA 4KVA 1P-1ELM 4000 2800 1 8x(12V 65Ah) NO 80x140x40 360<br />

3258 SCASE/SA 4KVA 3P-2ELM 4000 2800 3 16x(12V 65Ah) 1 MOB-2 80x140x40 360<br />

3259 SCASE/SA 5KVA 1P-1ELM 5000 3500 1 8x(12V 85Ah) NO 80x140x40 390<br />

3260 SCASE/SA 5KVA 3P-2ELM 5000 3500 3 16x(12V 85Ah) 1 MOB-2 80x140x40 420<br />

3261 SCASE/SA 6KVA 1P-1ELM 6000 4200 1 8x(12V 85Ah) NO 80x140x40 450<br />

3262 SCASE/SA 6KVA 3P-2ELM 6000 4200 3 16x(12V 85Ah) 1 MOB-2 80x140x40 450<br />

3263 SCASE/SA 7KVA 1P-2ELM 7000 4900 1 24x(12V 38Ah) 1 MOB-2 80x140x40 320<br />

3264 SCASE/SA 7KVA 3P-2ELM 7000 4900 3 24x(12V 85Ah) 1 MOB-2 80x140x40 450<br />

3265 SCASE/SA 8.5KVA 1P-2ELM 8500 6000 1 16x(12V 65Ah) 1 MOB-2 80x140x40 400<br />

3266 SCASE/SA 8.5KVA 3P-3ELM 8500 6000 3 32x(12V 85Ah) 2 MOB-2 80x140x40 270<br />

3267 SCASE/SA 10KVA 1P-2ELM 10000 7000 1 24x(12V 65Ah) 1 MOB-2 80x140x40 290<br />

3268 SCASE/SA 10KVA 3P-4ELM 10000 7000 3 48x(12V 65Ah) 3 MOB-2 80x140x40 310<br />