PROTECTION<br />

IP 21<br />

DEGREE<br />

Direct Current Soccorgroup<br />

The BEGHELLI SCCSA SoccorGroup is a Maintained<br />

(DC) emergency power supply that in the event of a<br />

mains failure will provide up to 5KW for 3 hours duration<br />

in 24, 48 or 110V DC.<br />

When mains is present and in tolerance, the power<br />

supply will maintain the battery charge via a two rate<br />

constant voltage charger with current limit.<br />

The load is connected in parallel with the battery to<br />

the rectified incoming supply<br />

In the event of a mains failure, the load is fed directly<br />

from the battery without any interruption in supply.<br />

The battery is protected from over discharge by deep<br />

discharge protection isolator. Soccorgroups are<br />

equipped with an AUTOTEST capability where the<br />

built-in microprocessor will periodically perform functional<br />

and duration tests. An RS232 serial port also<br />

allows the central system to be connected to a PC for<br />

remote control and monitoring.<br />

MAIN APPLICATIONS<br />

- halogen lights<br />

- signalling systems<br />

- various alarm systems (fire alarms,<br />

gas detection systems, burglar alarms, etc.)<br />

- generally for any direct current load that does<br />

not allow for interruptions in the power supply<br />

TRANSFORMER SCR BRIDGE<br />

D.C. FILTER REMOTE CONTROL SWITCH<br />

POWER MAINS<br />

CONTROL<br />

BATTERY<br />

SA MAINTAINED<br />

LOAD<br />

B<br />

TECHNICAL<br />

SPECIFICATIONS<br />

A<br />

C<br />

Power supply voltage:<br />

- 230V ± 15% / 50Hz Three-phase<br />

- 400V ± 15% / 50Hz Three-phase<br />

Maintained output:<br />

- stabilized DC output ± 1%<br />

Battery branches:<br />

- stabil. voltage ± 1%<br />

Charging system:<br />

- controlled diodes<br />

- IU charging curve<br />

Changeover time:<br />

- not applicable<br />

Protection:<br />

- fuses on power supply<br />

- fuse on load<br />

- battery fuse<br />

- minimum battery voltage cut-off<br />

remote control switch<br />

- (upon request) transf. CEI 14/6<br />

standards<br />

LED indicators<br />

- power mains present/absent<br />

- output present/absent<br />

- complete battery recharge<br />

- maintaining battery charge<br />

- general failure<br />

- emergency<br />

- battery in reserve status<br />

- battery failure<br />

- self-testing<br />

Display indicators and meters<br />

- power supply: V [VAC], I [A], f [Hz]<br />

- Output: V [VDC], I [A]<br />

- Battery: V [VDC], I [A]<br />

- Events: Type, Date<br />

- Status: Failure type<br />

Remote alarms:<br />

- operation from the mains<br />

- operation from battery<br />

- battery in reserve status<br />

- general failure<br />

Storage batteries:<br />

- sealed lead acid batteries<br />

Recharging:<br />

- 80% in 10 hours, approx.<br />

Operative temperature:<br />

-10 to + 40°C<br />

Cubiclest:<br />

- single unit also containing<br />

the storage batteries<br />

- IP21 protection rating<br />

AT<br />

DIRECT CURRENT CENTRAL BATTERY DEVICES<br />

MAINTAINED LIGHTING<br />

Ordering code Description Voltage Power Duration Battery Battery Cubicle Dimensions (AxBxC) Weight kg<br />

a3227 SCCSA 1KW24V 1P-1ELM 24Vdc 1KW 1h 2x(12V 85Ah) NO 80x80x40 140<br />

3228 SCCSA 1KW24V 3P-1ELM 24Vdc 1KW 3h 4x(12V 85Ah) NO 80x80x40 220<br />

3229 SCCSA 1KW48V 1P-1ELM 48Vdc 1KW 1h 4x(12V 38Ah) NO 80x80x40 140<br />

3230 SCCSA 1KW48V 3P-1ELM 48Vdc 1KW 3h 4x(12V 85Ah) NO 80x80x40 220<br />

3231 SCCSA 2KW48V 1P-1ELM 48Vdc 2KW 1h 4x(12V 85Ah) NO 80x80x40 230<br />

3232 SCCSA 2KW48V 3P-1ELM 48Vdc 2KW 3h 8x(12V 85Ah) NO 80x80x40 360<br />

3233 SCCSA 3KW48V 1P-1ELM 48Vdc 3KW 1h 8x(12V 50Ah) NO 80x140x40 280<br />

3234 SCCSA 3KW48V 3P-1ELM 48Vdc 3KW 3h 12x(12V 85Ah) NO 80x140x40 490<br />

3235 SCCSA 3KW110V 1P-1ELM 110Vdc 3KW 1h 9x(12V 50Ah) NO 80x140x40 300<br />

3236 SCCSA 3KW110V 3P-2ELM 110Vdc 3KW 3h 18x(12V 50Ah) 1 MOB-2 80x140x40 320<br />

3237 SCCSA 5KW110V 1P-1ELM 110Vdc 5KW 1h 9x(12V 85Ah) NO 80x140x40 520<br />

3238 SCCSA 5KW110V 3P-2ELM 110Vdc 5KW 3h 18x(12V 85Ah) 1 MOB-2 80x140x40 520<br />