STRUCTURAL NOTES<br />

10/2/2012 12:54:47 PM<br />

1010 GENERAL CONDITIONS AND STATEMENTS:<br />

A. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS<br />

AND MECHANICAL, PLUMBING DRAWINGS. CONSULT THESE DRAWINGS FOR DIMENSIONS,<br />

AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS. THE CONTRACTOR SHALL<br />

COMPARE AND COORDINATE WITH ALL DISCIPLINES AND REPORT ANY DISCREPANCIES TO<br />

ENGINEER PRIOR TO FABRICATION.<br />

B. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY DISCREPANCIES<br />

SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE<br />

AFFECTED PART OF THE WORK.<br />

C. DO NOT SCALE OFF DRAWINGS OR DETAILS. DIMENSIONS PROVIDED ON PLAN OVERIDE<br />

ANY SCALED DIMENSIONS.<br />

D. THE STRUCTURE DEPICTED ON THE DRAWINGS IS DESIGNED TO BE SELF-SUPPORTING,<br />

STABLE AND STRUCTURALLY SOUND AFTER THE BUILDING IS COMPLETE. IT IS THE<br />

CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE<br />

TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS<br />

INCLUDES PROVIDING TEMPORARY SHORING, SHEETING, BRACING, GUYS OR TIEDOWNS TO<br />

RESIST LOADS IMPOSED BY GRAVITY, SOIL, CONSTRUCTION LOADS, WIND AND SEISMIC<br />

(WHERE APPLICABLE).<br />

E. DETAILS, NOTES, KEYNOTES OR ANY INFORMATION SHOWN ON ANY PART OF THE<br />

DRAWINGS SHALL BE APPLIED TO ALL APPLICABLE OR SIMILAR CONDITIONS AND IF NOTED<br />

AS TYPICAL OR SHOWN FOR ONE CONDITION, SHALL BE APPLIED FOR ALL LIKE OR SIMILAR<br />

CONDITIONS UNLESS NOTED OTHERWISE. THE CONTRACTOR MUST USE, IN CONJUNCTION<br />

WITH STRUCTURAL DRAWINGS, MECHANICAL, PLUMBING AND SITE DRAWINGS TO<br />

DETERMINE WHERE CONDITIONS THAT ARE LIKE OR SIMILAR APPLY.<br />

F. WHERE A CONFLICT EXISTS BETWEEN STRUCTURAL DRAWINGS AND STRUCTURAL<br />

SPECIFICATIONS THE DRAWINGS SHALL GOVERN.<br />

1015 EXISTING STRUCTURE:<br />

INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS TAKEN<br />

FROM THE DRAWINGS THAT WERE:<br />

PREPARED FOR: COUNTY WATER-SEWER DISTRICT<br />

COLLIER COUNTY, FL<br />

PREPARED BY: CONSOER, TOWNSEND & ASSOC.<br />

ENTITLED: RAW WATER BOOSTER PUMPING STATION<br />

DATED: 7-20-1990<br />

WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS<br />

PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS<br />

INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES,<br />

MATERIALS, DETAILS, ETC. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO<br />

VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO DETERMINE IF<br />

MODIFICATIONS AS INDICATED ON DRAWINGS ARE FEASIBLE AND PRACTICAL. FIELD<br />

DIMENSIONS AND SURVEY EXISTING STRUCTURE FOR NEW STRUCTURAL ELEMENTS<br />

PRIOR TO FABRICATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES<br />

OR CONFLICTS.<br />

1020 STRUCTURAL DEMOLITION<br />

A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SELECTING METHODS OF<br />

DEMOLITION SO THAT THE REMAINING STRUCTURE WILL NOT BE IMPAIRED OR<br />

DAMAGED.<br />

B. SAWCUTTING AND CORING SHALL BE UTILIZED TO THE FULLEST EXTENT POSSIBLE.<br />

ISOLATE CONSTRUCTION TO BE REMOVED FROM THE STRUCTURE TO REMAIN.<br />

C. ONLY OVERCUT OPENINGS WHERE INDICATED. USE APPROPRIATE SIZE CORES AT<br />

CORNERS SO THAT OVERCUTTING AT CORNERS WILL NOT BE NECESSARY. USE<br />

CHIPPING TOOLS WHERE CORNERS ARE REQUIRED TO BE SQUARE.<br />

D. SELECT METHODS OF TRANSPORTING DEBRIS THROUGH THE BUILDING WHICH WILL<br />

NOT OVERLOAD THE EXISTING OR NEW BUILDING.<br />

E. PROVIDE SHORING REQUIRED TO SUPPORT THE STRUCTURE WHEN NEW WORK TO<br />

STRENGTHEN THE STRUCTURE CANNOT BE INSTALLED PRIOR TO DEMOLITION.<br />

MAINTAIN SHORING UNTIL NEW WORK HAS ATTAINED DESIGN STRENGTH.<br />

1061 DESIGN LOADS:<br />

THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE<br />

WITH THE 2007 EDITION OF THE FLORIDA BUILDING CODE (2007 FBC) WITH FLORIDA<br />

BUILDING CODE 2009 SUPPLEMENT, BY THE SOUTHERN BUILDING CODE CONGRESS<br />

INTERNATIONAL, INC.<br />

1120 SUBMITTAL (SHOP DRAWING) REVIEW:<br />

A. SUBMITTALS (SHOP DRAWINGS) WILL BE REVIEWED FOR GENERAL COMPLIANCE<br />

WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IF ANY DEVIATIONS<br />

FROM CONTRACT DOCUMENTS BECOME APPARENT DURING REVIEW, AS A COURTESY,<br />

ENGINEER/ARCHITECT MAY MARK UP DEVIATIONS ON SHOP DRAWINGS DURING THE<br />

SUBMITTAL PROCESS. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR<br />

TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS INCLUDING BUT NOT<br />

LIMITED TO QUANTITY, LENGTH, ELEVATIONS AND DIMENSIONS. FABRICATION<br />

REQUIREMENTS, CONSTRUCTION MEANS AND METHODS, COORDINATION OF WORK<br />

WITH OTHER TRADES OR CONSTRUCTION SAFETY REQUIREMENTS.<br />

B. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL<br />

TO THE ARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUT REVIEW, OR IF<br />

SUBMITTAL IS INCOMPLETE, WILL BE REJECTED AND WILL NOT BE REVIEWED. TRC<br />

WORLDWIDE ENGINEERING, INC WILL NOT BE RESPONSIBLE FOR DELAYS CAUSED BY<br />

REJECTED DRAWINGS.<br />

C. SHOP DRAWING SUBMITTALS SHALL FOLLOW THE REQUIREMENTS IN CONTRACT<br />

SPECIFICATIONS SECTION 01330<br />

D. THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS UNLESS<br />

OTHERWISE SPECIFIED IN WRITING BY THE ENGINEER.<br />

E. CHANGES AND ADDITIONS MADE ON RE-SUBMITTALS SHALL BE CLEARLY FLAGGED<br />

AND NOTED. THE PURPOSE OF THE RE-SUBMITTALS SHALL BE CLEARLY NOTED ON<br />

THE LETTER OF TRANSMITTAL. ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO<br />

THOSE ITEMS CAUSING THE RE-SUBMITTAL.<br />

1121 DELEGATE ENGINEERING COMPONENTS AND REQUIREMENTS:<br />

A. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUM REQUIRE<br />

FABRICATION AND ERECTION DRAWINGS PREPARED BY A DELEGATED ENGINEER:<br />

STAINLESS STEEL BASE & ANCHOR RODS.<br />

B. SUBMITTALS SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECT AND<br />

APPLICABLE CODES, LIST THE DESIGN CRITERIA, AND SHOW ALL DETAILS AND<br />

PLANS NECESSARY FOR PROPER FABRICATION AND INSTALLATION. CALCULATIONS<br />

AND SHOP DRAWINGS SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED. GENERIC<br />

PRODUCTS WILL NOT BE ACCEPTED.<br />

C. SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDER THE DIRECT<br />

SUPERVISION AND CONTROL OF THE DELEGATED ENGINEER.<br />

D. SHOP DRAWINGS AND CALCULATIONS REQUIRE THE IMPRESSED SEAL, DATE<br />

AND SIGNATURE OF THE DELEGATED ENGINEER. COMPUTER PRINTOUTS ARE AN<br />

ACCEPTABLE SUBSTITUTE FOR MANUAL COMPUTATIONS PROVIDED THEY ARE<br />

ACCOMPANIED BY SUFFICIENT DESCRIPTIVE INFORMATION TO PERMIT THEIR<br />

PROPER EVALUATION. SUCH DESCRIPTIVE INFORMATION SHALL BEAR THE<br />

IMPRESSED SEAL AND SIGNATURE OF THE DELEGATED ENGINEER AS AN<br />

INDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITY FOR THE RESULTS.<br />

SEPIAS DO NOT REQUIRE SIGNATURE AND SEAL. THE STRUCTURAL ENGINEER WILL<br />

RETAIN ONE SIGNED AND SEALED BLUELINE PRINT FOR RECORD.<br />

E. DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FOR FABRICATION AND<br />

INSTALLATION (SUCH AS REINFORCING STEEL SHOP DRAWINGS OR STRUCTURAL<br />

STEEL ERECTION DRAWINGS) AND REQUIRING NO ENGINEERING DO NOT REQUIRE<br />

THE SEAL OF A DELEGATED ENGINEER. HOWEVER, ALL STRUCTURAL STEEL<br />

CONNECTIONS NOT DETAILED ON THESE DRAWINGS SHALL BE DESIGNED AND<br />

DETAILED BY DELEGATE ENGINEER, BASED ON LOADS AND PROJECT<br />

REQUIREMENTS PROVIDED HEREIN.<br />

F. CATALOG INFORMATION ON STANDARD PRODUCTS DOES NOT REQUIRE THE<br />

SEAL OF A DELEGATED ENGINEER.<br />

G. REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OF SUBMITTALS IS LIMITED<br />

TO VERIFYING THE FOLLOWING:<br />

a) THAT THE SPECIFIED STRUCTURAL SUBMITTALS HAVE BEEN FURNISHED.<br />

b) THAT THE STRUCTURAL SUBMITTALS HAVE BEEN SIGNED AND SEALED BY THE<br />

DELEGATED ENGINEER.<br />

c) THAT THE DELEGATED ENGINEER HAS UNDERSTOOD THE DESIGN INTENT AND<br />

HAS USED THE SPECIFIED STRUCTURAL CRITERIA. (NO DETAILED CHECK OF<br />

CALCULATIONS WILL BE MADE).<br />

d) THAT THE CONFIGURATION SET FORTH IN THE STRUCTURAL SUBMITTALS IS<br />

CONSISTENT WITH THE CONTRACT DOCUMENTS. (NO DETAILED CHECK OF<br />

DIMENSIONS OR QUANTITIES WILL BE MADE).<br />

H. SUBMITTALS NOT MEETING THE ABOVE CRITERIA WILL NOT BE REVIEWED.<br />

2011 FOUNDATIONS:<br />

A. GEOTECHNICAL INVESTIGATION, TESTING, STUDIES, FOUNDATION<br />

RECOMMENDATIONS, AND SITE PREPARATION REQUIREMENTS HAS NOT BEEN<br />

PERFORMED BY TRC WORLDWIDE ENGINEERS, INC.<br />

B. FOUNDATION DESIGN IS BASED ON AN SOIL BEARING PRESSURE OF 2,000 PSF.<br />

C. SOIL TO BE COMPACTED TO CONTRACT SPECIFICATIONS OF 98% MODIFIED<br />

PROCTOR OR GREATER.<br />

3101 FORMWORK:<br />

1. NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HAS REACHED AT<br />

LEAST TWO-THIRDS OF THE 28 DAY DESIGN STRENGTH.<br />

a) DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK SHALL MEET<br />

REQUIREMENTS SET FORTH IN ACI STANDARDS 347 AND 301.<br />

2. CONSTRUCT FORMWORK SO CONCRETE SURFACES CONFORM TO THE<br />

TOLERANCE LIMITS OF ACI 117 [STANDARD SPECIFICATIONS FOR TOLERANCES FOR<br />

CONCRETE CONSTRUCTION MATERIALS]. THE CLASS OF SERVICE FOR OFFSET<br />

BETWEEN ADJACENT PIECES OF FORMWORK FACING MATERIAL SHALL BE CLASS B<br />

FOR SURFACES PERMANENTLY EXPOSED TO PUBLIC VIEW AND CLASS D FOR<br />

SURFACES THAT WILL BE PERMANENTLY CONCEALED.<br />

3. PROVIDE 3/4" CHAMFER FOR ALL EXPOSED CONCRETE EDGES.<br />

3201 REINFORCING STEEL:<br />

A. SHALL BE MMFX DEFORMED BARS, FREE FROM OIL, SCALE AND RUST AND<br />

PLACED IN ACCORDANCE WITH THE TYPICAL BENDING DIAGRAM AND PLACING<br />

DETAILS OF ACI STANDARDS AND SPECIFICATIONS. SECURE APPROVAL OF<br />

SHOP DRAWINGS PRIOR TO COMMENCING FABRICATION. REINFORCING BAR<br />

DETAILING SHALL COMPLY WITH ACI 315 "MANUAL OF STANDARD PRACTICE FOR<br />

DETAILING REINFORCED CONCRETE STRUCTURES".<br />

B. UNLESS NOTED OTHERWISE ON SECTIONS AND DETAILS, PROVIDE THE<br />

FOLLOWING CONCRETE COVER FOR REINFORCING STEEL:<br />

REINFORCING STEEL COVER (PRESTRESSED AND NON-PRESTRESSED<br />

CONCRETE) CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH<br />

GROUND<br />

SLABS, WALLS, JOISTS<br />

#14 & #18 BARS.........................................................1 1/2"<br />

#11 BAR & SMALLER................................................3/4"<br />

CONCRETE EXPOSED TO WEATHER OR EARTH*<br />

#6 BAR THRU #18 BARS..........................................2"<br />

#5 BAR, W31 OR D31 WIRE, AND SMALLER....... 1 1/2"<br />

GRADE BEAMS<br />

TIES, STIRRUPS - TOP & FORMED FACES...... 2"<br />

BOTTOM & UNFORMED FACES.......................3"<br />

FOOTINGS & PILECAPS<br />

TOP.............................................................................. 2"<br />

BOTTOM & SIDES...................................................... 3"<br />

COVERAGE TO REINFORCING REQUIREMENTS APPLIES ALSO TO ANY EDGE OF<br />

SLAB OR OPENING.<br />

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DRIPS, CHAMFERS,<br />

REGLETS, SLOTS, SLEEVES, ANCHORS, AND INSERTS. UNLESS SHOWN ON<br />

STRUCTURAL DRAWINGS NO OPENINGS LARGER THAN 12"x12" SHALL BE<br />

PLACED IN SLABS OR WALLS. FOR OPENINGS NOT SHOWN ON STRUCTURAL<br />

DRAWINGS, APPROVALS MUST BE OBTAINED FROM THE ENGINEER PRIOR TO<br />

FABRICATION OF STEEL AND PLACEMENT OF CONCRETE. LOCATION DRAWINGS<br />

FOR ALL SLEEVES AND BLOCKOUTS IN THE CONCRETE SHALL BE SUBMITTED<br />

FOR APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TO PLACEMENT.<br />

D. ALL CONDUIT, SLEEVES, AND PIPES EMBEDDED IN OR PASSING THRU<br />

CONCRETE SHALL CONFORM TO SECTION 6.3 OF ACI 318 AND THE FOLLOWING:<br />

1. SLEEVES AND PIPES SHALL BE PLACED SO THAT REINFORCING STEEL<br />

CAN BE PLACED WITH THE SPECIFIED COVER AND CLEAR DISTANCE<br />

BETWEEN BARS.<br />

2. THE CONCRETE COVERING OF PIPE AND SLEEVES SHALL NOT BE<br />

LESS THAN 11/2 INCHES. CLEAR DISTANCE BETWEEN SUCH PIPES<br />

AND SLEEVES SHALL NOT BE LESS THAN SIX INCHES.<br />

3. CONDUIT AND PIPES PLACED IN SLABS AND TOPPING OVER SLABS<br />

SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN ONE-THIRD THE<br />

THICKNESS OF SLAB OR TOPPING, AND SHALL BE PLACED IN THE<br />

MIDDLE THIRD OF SLAB DEPTH.<br />

4. CONDUITS AND PIPES PLACED IN COLUMNS SHALL NOT DISPLACE<br />

MORE THAN 4% OF THE CROSS SECTIONAL AREA OF COLUMN AND<br />

SHALL BE LOCATED ON THE CENTER LINE OF COLUMN. OUTLET<br />

BOXES TO BE NOT DEEPER THAN REQUIRED CLEARANCE FOR REINF.<br />

5. INSERTS W/ 3/4" MAX. EMBEDMENT SHALL BE USED TO SUPPORT<br />

CONDUITS, PIPES, AND DUCT FROM THE SLAB. 1-3/8" DEEP (MAX.)<br />

UNISTRUT INSERTS (OR APPROVED EQUAL) ME BE USED TO SUPPORT<br />

MECHANICAL AND PLUMBING EQUIPMENT AT CORRIDORS ONLY (AVOID<br />

CONFLICT W/ POST-TENSION TENDONS).<br />

E. ALL CONTINUOUS BARS SHALL HAVE CLASS B FULL TENSION LAPS UNLESS<br />

INDICATED OTHERWISE. PROVIDE CORNER BARS AT ALL WALL, GRADE BEAM<br />

AND STRIP FOOTING CORNERS. BARS SHALL BE THE SAME SIZE AND SPACING<br />

AS THE HORIZONTAL REINFORCING. INTERSECTING WALLS, GRADE BEAMS AND<br />

STRIP FOOTINGS SHALL BE DOWELED TOGETHER IN THE SAME MANNER.<br />

PROVIDE 2 NO. 4 TOP DIAGONAL BARS 4'-0" LONG AT ALL REENTRANT CORNERS<br />

IN ALL SLABS ON GRADE AND ELEVATED SLABS.<br />

G. SHOP DRAWINGS SHALL DETAIL ALL CONCRETE WALLS IN ELEVATION.<br />

950 Encore Way<br />

Naples, FL 34110<br />

Phone: (239) 254-2000<br />

Florida Certificate of<br />

Authorization No. 1772<br />

DESIGN BY:<br />

DRAWN BY:<br />

CHECKED BY:<br />

CAD FILE:<br />

3301 CONCRETE:<br />

A. SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TO ACHIEVE A<br />

STRENGTH AT 28 DAYS AS LISTED BELOW WITH A PLASTIC AND WORKABLE<br />

MIX:<br />

4000 PSI FOR ALL CONCRETE<br />

CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI 301-05<br />

STANDARDS AND SPECIFICATIONS.<br />

B. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR LAB<br />

TESTS FOR REVIEW PRIOR TO USE. ONLY TYPE II CEMENT SHALL BE USED<br />

FOR SLAB-ON-GRADE CONCRETE. MIX SHALL BE UNIQUELY IDENTIFIED BY<br />

MIX NUMBER OR OTHER POSITIVE IDENTIFICATION. MIX SHALL MEET THE<br />

REQUIREMENTS OF ASTM C33 FOR COARSE AGGREGATE. CONCRETE SHALL<br />

COMPLY WITH THE REQUIREMENTS OF ASTM STANDARD C94 FOR<br />

MEASURING, MIXING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE<br />

TIME STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED<br />

FROM THE TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS<br />

FINAL POSITION SHALL NOT EXCEED ONE AND ONE HALF (1-1/2) HOURS. IF<br />

FOR ANY REASON THERE IS A LONGER DELAY THAN THAT STATED ABOVE,<br />

THE CONCRETE SHALL BE DISCARDED. IT SHALL BE THE RESPONSIBILITY OF<br />

THE TESTING LAB TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE<br />

CONTRACTOR OF ANY NONCOMPLIANCE WITH THE ABOVE. SLABS SHALL<br />

BE CURED USING A DISSIPATING CURING COMPOUND MEETING ASTM<br />

STANDARD C309 TYPE 1-D AND SHALL HAVE A FUGITIVE DYE. THE<br />

COMPOUND SHALL BE PLACED AS SOON AS THE FINISHING IS COMPLETED<br />

OR AS SOON AS THE WATER HAS LEFT THE UNFINISHED CONCRETE.<br />

SCUFFED OR BROKEN AREAS IN THE CURING MEMBRANE SHALL BE<br />

RECOATED DAILY. CALCIUM CHLORIDES SHALL NOT BE UTILIZED; OTHER<br />

ADMIXTURES MAY BE USED ONLY WITH THE APPROVAL OF THE ENGINEER.<br />

C. CONCRETE MIX DESIGNS SHALL INCLUDE A WRITTEN DESCRIPTION<br />

INDICATING WHERE EACH PARTICULAR MIX IS TO BE PLACED WITHIN THE<br />

STRUCTURE. FAILURE TO COMPLY MAY RESULT IN REJECTION OF THE MIX. IF<br />

ACCEPTED, PEA ROCK PUMP MIX USE IS LIMITED TO VERTICAL ELEMENT<br />

POURS AND BEAM POURS LESS THAN 60 LINEAL FEET PER POUR.<br />

D. CONCRETE DESIGN MIX SUBMITTALS SHALL INCLUDE TESTED,<br />

STATISTICAL BACK-UP DATA AS PER CHAPTER 5 OF ACI 318.<br />

E. WATER/CEMENTITIONS MATERIAL RATIO FOR CONCRETE SHALL NOT<br />

EXCEED 0.45 BY WEIGHT.<br />

F. CONFORM TO ACI 306R FOR COLD WEATHER CONCRETING AND ACI 305R<br />

FOR HOT WEATHER CONCRETING WHEN ANY COMBINATION OF HIGH<br />

TEMPERATURE, LOW RELATIVE HUMIDITY AND WIND VELOCITY TEND TO<br />

IMPAIR THE QUALITY OF THE CONCRETE. CONCRETE IS TO BE REJECTED IF<br />

ITS TEMPERATURE AT TIME OF PLACEMENT IS 90°F OR ABOVE. PROTECT<br />

SURFACES OF EXPOSED CONCRETE FROM PRECIPITATION DAMAGE UNTIL<br />

ADEQUATE STRENGTH IS GAINED TO PREVENT DAMAGE.<br />

3304 CONCRETE TESTING:<br />

A. AN INDEPENDENT TESTING LABORATORY SHALL PERFORM THE<br />

FOLLOWING TESTS ON CAST IN PLACE CONCRETE:<br />

a)ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF<br />

PORTLAND CEMENT CONCRETE." SLUMP SHALL RANGE FROM 3 TO 5<br />

INCHES.<br />

b)ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE<br />

STRENGTH OF CYLINDRICAL CONCRETE SPECIMENS."<br />

B. A SEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS, FOR<br />

EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), 5,000 S.F. OF<br />

SURFACE AREA OR EACH PLACEMENT OF EACH MIX DESIGN OF<br />

CONCRETE PLACED IN ANY ONE DAY. REQUIRED CYLINDER(S)<br />

QUANTITIES AND TEST AGE AS FOLLOWS:<br />

1 AT 7 DAYS<br />

2 AT 28 DAYS<br />

ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THE<br />

DIRECTION OF THE ENGINEER, IF REQUIRED. IF 28 DAY STRENGTH IS<br />

ACHIEVED, THE ADDITIONAL CYLINDER(s) MAY BE DISCARDED. ANY<br />

ADDITIONAL CYLINDERS REQUESTED BY CONTRACTOR SHALL BE AT<br />

CONTRACTOR'S EXPENSE.<br />

C. CYLINDERS AND TEST REPORTS SHALL BE CLEARLY LABELED WITH<br />

DATE SAMPLED AND WHERE CONCRETE WAS SPECIFICALLY PLACED.<br />

D. TEST REPORTS SHALL BE KEPT AT JOB SITE, WITH COPIES SENT<br />

DIRECLY TO ENGINEER.<br />

PSM<br />

KLI<br />

PSM<br />

11FTM245<br />

PSM<br />

Florida Reg. No.<br />

_____<br />

FOR 22x34 THE SCALE IS AS NOTED.<br />

FOR 11x17 THE SCALE IS 50% OF THE SCALE SHOWN.<br />

COUNTY WATER-SEWER DISTRICT<br />

COLLIER COUNTY, FL<br />

PUMP REPLACEMENTS<br />

RAW BOOSTER PUMP STATION<br />

STRUCTURAL NOTES<br />

PAUL S MOERSCHEL<br />

FL PE #60487<br />

CERTIFICATE OF AUTHORIZATION NO. 27322<br />

12550 Professional Park Drive, Suite 7<br />

FORT MYERS, FL 33913<br />

PHONE: (239) 939-1414<br />

FAX: (239) 278-4289<br />

© 2011 - TRC Worldwide Engineering, <strong>Inc</strong>.<br />

All rights reserved.<br />

www.trcww.com<br />

TO THE BEST OF MY KNOWLEDGE AND<br />

ABILITY, THE COMPLETED STRUCTURE<br />

DEPICTED ON THESE PLANS COMPLIES<br />

WITH THE APPLICABLE<br />

MINIMUM BUILDING CODES.<br />

FILE No.<br />

11FTM245<br />

PROJECT NO. :<br />

DATE :<br />

SHEET NO. :<br />

2011054<br />

10/2012<br />

S1


ITEM<br />

CONCRETE (PLAN)<br />

CONCRETE (SECTION)<br />

EARTH<br />

BRICK<br />

SECTION INDICATOR<br />

DETAIL INDICATOR<br />

TOP REBAR<br />

BOTTOM REBAR<br />

TOP OF FOOTING ELEVATION<br />

SPOT ELEVATION TOP OF CONCRETE<br />

STEP IN FTG., GRADE BM. OR OTHER<br />

STRUCTURAL ELEMENT<br />

CL BEAM SPLICE<br />

AND<br />

PLATE<br />

CENTERLINE<br />

NUMBER (PRECEEDING)<br />

PLUS OR TENSION<br />

MINUS OR COMPRESSION<br />

POUNDS (FOLLOWING)<br />

TOP OF STEEL ELEVATION<br />

COLUMN SYMBOLS<br />

L E G E N D<br />

LOAD BEARING CONCRETE BLOCK (CMU)<br />

STEP IN STRUCTURE OR DEPRESSED SLAB<br />

INDICATES COLUMN BELOW<br />

INDICATES COLUMN THRU<br />

INDICATES COLUMN ABOVE<br />

COLUMN/PILASTER MARK<br />

FOOTING MARK<br />

TOP OF FOOTING<br />

ELEVATION<br />

C1/P1<br />

F1<br />

-1'-4"<br />

SYMBOL<br />

0'-0"<br />

+0'-0"<br />

&<br />

PL<br />

8"<br />

S<br />

S<br />

CL<br />

#, NO.<br />

+<br />

-<br />

#<br />

T/STL. EL. +20'-8" or (+20'-8")<br />

REINF SYMBOLS<br />

BAR SIZE<br />

BAR SPACING<br />

BAR PLACEMENT<br />

1"<br />

4/12T<br />

1<br />

S0.3<br />

1<br />

S0.3<br />

T=TOP<br />

B=BOTTOM<br />

C=`C'<br />

E=`E'<br />

ABBREVIATIONS<br />

AR<br />

- ANCHOR ROD<br />

K<br />

- KIP(s), 1000 POUNDS<br />

ALT - ALTERNATE<br />

KLF - KIPS PER LINEAR FOOT<br />

APPROX - APPROXIMATELY<br />

KJ<br />

- CONSTRUCTION JOINT<br />

ARCH - ARCHITECT<br />

L<br />

- ANGLE<br />

ARCHL - ARCHITECTURAL<br />

LG<br />

- LONG<br />

B/ - BOTTOM OF<br />

LLH - LONG LEG HORIZONTAL<br />

BC<br />

- BOTTOM CHORD<br />

LLV - LONG LEG VERTICAL<br />

BLDG - BUILDING<br />

LP<br />

- LOW POINT<br />

BM - BEAM<br />

LW - LONG WAY<br />

BOTT - BOTTOM<br />

LWT - LIGHTWEIGHT<br />

BRG - BEARING<br />

MFR - MANUFACTURER<br />

C/C - CENTER TO CENTER<br />

MAS - MASONRY<br />

CIP - CAST IN PLACE<br />

MO - MASONRY OPENING<br />

CJ<br />

- CONTRACTION JOINT<br />

MATL - MATERIAL<br />

CL<br />

- CENTERLINE<br />

MAX - MAXIMUM<br />

CLR - CLEAR<br />

MECHL<br />

- MECHANICAL<br />

CMU - CONCRETE MASONRY UNIT MTL - METAL<br />

COL - COLUMN<br />

MIN - MINIMUM<br />

CONC - CONCRETE<br />

MISC - MISCELLANEOUS<br />

CONFIG - CONFIGURATION<br />

NS<br />

- NEAR SIDE<br />

CONT - CONTINUOUS<br />

NIC - NOT IN CONTRACT<br />

CONTR - CONTRACTOR<br />

NTS - NOT TO SCALE<br />

CTR - CENTER<br />

NW - NORMAL WEIGHT<br />

DBL - DOUBLE<br />

OC - ON CENTER<br />

DET - DETAIL<br />

OH - OPPOSITE HAND<br />

DIA - DIAMETER<br />

OPNG - OPENING<br />

DIM - DIMENSION<br />

PAF - POWER ACTUATED FASTENERS<br />

<strong>DN</strong><br />

- DOWN<br />

PART - PARTITION<br />

DR<br />

- DRAIN<br />

PARTL - PARTIAL<br />

DWG - DRAWING<br />

PCJ - PRECAST CONCRETE JOIST<br />

EA<br />

- EACH<br />

PL<br />

- PLATE<br />

EE<br />

- EACH END<br />

PLF - POUNDS PER LINEAR FOOT<br />

EF<br />

- EACH FACE<br />

PSF - POUNDS PER SQUARE FOOT<br />

EJ<br />

- EXPANSION JOINT<br />

PSI - POUNDS PER SQUARE INCH<br />

EL<br />

- ELEVATION<br />

PT<br />

- POST TENSIONED<br />

ELEV - ELEVATOR<br />

PrT - PRESSURE TREATED<br />

ENGR - ENGINEER<br />

R<br />

- RADIUS<br />

EOR - ENGINEER OF RECORD REG - REGULAR<br />

EOS - EDGE OF SLAB<br />

REINF - REINFORCING<br />

EQ<br />

- EQUAL<br />

REM - REMAINDER<br />

EW - EACH WAY<br />

REQD - REQUIRED<br />

EXIST - EXISTING<br />

REV - REVISED/REVISION<br />

EXP - EXPANSION<br />

RM - ROOM<br />

EXT - EXTERIOR<br />

RO - ROUGH OPENING<br />

FD<br />

- FLOOR DRAIN<br />

RQMTS<br />

- REQUIREMENTS<br />

FIN - FINISH<br />

SCHED<br />

- SCHEDULE<br />

FLR - FLOOR<br />

SECT - SECTION<br />

FND - FOUNDATION<br />

SIM - SIMILAR<br />

FOM - FACE OF MASONRY<br />

SL<br />

- SLOPE<br />

FS<br />

- FAR SIDE<br />

SOG - SLAB-ON-GRADE<br />

FT<br />

- FOOT<br />

SP<br />

- SPIRAL<br />

FTG - FOOTING<br />

SQ<br />

- SQUARE<br />

GA<br />

- GAGE<br />

SS<br />

- STAINLESS STEEL<br />

GALV - GALVANIZED<br />

STD - STANDARD<br />

GC - GENERAL CONTRACTOR STL - STEEL<br />

GT<br />

- GIRDER TRUSS<br />

STRUCTL - STRUCTURAL<br />

HC<br />

- HOLLOW CORE<br />

SW# - SHEARWALL<br />

HCP - HOLLOW CORE PLANK SW - SHORT WAY<br />

HDG - HOT DIPPED GALVANIZED T/ - TOP OF<br />

HG - HIP GIRDER<br />

TB<br />

- TIE BEAM<br />

HK<br />

- HOOK<br />

TC<br />

- TIE COLUMN<br />

HORIZ<br />

- HORIZONTAL<br />

TEMP - TEMPERATURE<br />

HP<br />

- HIGH POINT<br />

TJ<br />

- TIE JOIST<br />

HS<br />

- HIGH STRENGTH<br />

TR<br />

- TRUSS<br />

IJ<br />

- ISOLATION JOINT<br />

TYP - TYPICAL<br />

INFO - INFORMATION<br />

UNO - UNLESS NOTED OTHERWISE<br />

INS - INSULATION<br />

VERT - VERTICAL<br />

INT - INTERIOR<br />

W/ - WITH<br />

IRR - IRREGULAR<br />

W/O - WITHOUT<br />

JB<br />

- JOIST BEARING<br />

WD - WOOD<br />

JBE - JOIST BEARING ELEVATION WF -WALL FOOTING<br />

JR<br />

- JAMB REINFORCING<br />

WP - WORK POINT<br />

JT<br />

- JOINT<br />

WWR - WELDED WIRE REINFORCING<br />

PAUL S MOERSCHEL<br />

FL PE #60487<br />

CERTIFICATE OF AUTHORIZATION NO. 27322<br />

12550 Professional Park Drive, Suite 7<br />

FORT MYERS, FL 33913<br />

PHONE: (239) 939-1414<br />

FAX: (239) 278-4289<br />

© 2011 - TRC Worldwide Engineering, <strong>Inc</strong>.<br />

All rights reserved.<br />

www.trcww.com<br />

FOR 22x34 THE SCALE IS AS NOTED.<br />

FOR 11x17 THE SCALE IS 50% OF THE SCALE SHOWN.<br />

TO THE BEST OF MY KNOWLEDGE AND<br />

ABILITY, THE COMPLETED STRUCTURE<br />

DEPICTED ON THESE PLANS COMPLIES<br />

WITH THE APPLICABLE<br />

MINIMUM BUILDING CODES.<br />

FILE No.<br />

11FTM245<br />

10/2/2012 12:54:47 PM<br />

950 Encore Way<br />

Naples, FL 34110<br />

Phone: (239) 254-2000<br />

Florida Certificate of<br />

Authorization No. 1772<br />

DESIGN BY:<br />

DRAWN BY:<br />

CHECKED BY:<br />

CAD FILE:<br />

PSM<br />

KLI<br />

PSM<br />

11FTM245<br />

PSM<br />

Florida Reg. No.<br />

_____<br />

COUNTY WATER-SEWER DISTRICT<br />

COLLIER COUNTY, FL<br />

PUMP REPLACEMENTS<br />

RAW BOOSTER PUMP STATION<br />

ABBREVIATIONS<br />

PROJECT NO. :<br />

DATE :<br />

SHEET NO. :<br />

2011054<br />

10/2012<br />

S2


HORIZ REINF TO HAVE<br />

90° HOOK EA END<br />

3/4" CHAMFER<br />

VERT REINF<br />

(6) 3/4"ø SS (AISI TYPE<br />

316) ANCHOR RODS x1'-0"<br />

EMBED ON EA SIDE OF<br />

PUMP & MOTOR BASE<br />

3/4" CHAMFER<br />

PROVIDE NUT TACK WELDED<br />

OR DAMAGED THREADS<br />

SAW CUT 1" DEEP &<br />

EXCAVATE EXIST SLAB FOR<br />

NEW PUMP FOUNDATION<br />

EXIST 7" SLAB<br />

ON GRADE<br />

1'-4"<br />

4" MIN<br />

1'-4" *<br />

GROUT IN NEW STAINLESS STEEL (AISI<br />

316) PLATE W/ PUMP AND MOTOR<br />

SUBMIT SHOP DRAWINGS FOR REVIEW<br />

PRIOR TO CONSTRUCTION.<br />

SEE SPECIFICATION SECTION 11350<br />

FOR ADDITIONAL INFORMATION &<br />

REQUIREMENTS<br />

#5@8"OC EW TOP<br />

2" CLR<br />

2" CLR<br />

3"<br />

CLR<br />

#4@10"OC HORIZ<br />

#5@6"OC VERT<br />

PROVIDE 1/4" AMPLITUDE<br />

ROUGHENED SURFACE<br />

FOR BOND TO EXIST SOG<br />

8"<br />

8"<br />

NEW 3/16"x6" SS<br />

STRAP (AISI 316)<br />

3/4" CHAMFER<br />

3<br />

S3<br />

4'-6"<br />

NEW PIPE<br />

SUPPORT WALL<br />

4<br />

S3<br />

7'-6"<br />

7'-6"<br />

7'-6"<br />

3'-0"<br />

3'-0"<br />

3'-0"<br />

NEW PUMP<br />

FOUNDATION<br />

(TYP 4 PLACES)<br />

5<br />

S3<br />

3" TYP<br />

ALL SIDES<br />

3"<br />

CLR<br />

#5@8"OC EW BOTT<br />

1 1/2"<br />

6"<br />

EXIST PIPE RADIUS<br />

MATCH EXIST<br />

3'-0"<br />

5<br />

S3<br />

ENLARGED PLAN SECTION OF<br />

FOUNDATION REINF<br />

3/4" = 1'-0"<br />

COMPACT SOIL BENEATH FTG<br />

GEOTECH ENG TO VERIFY 2,000 PSF<br />

MIN ALLOWABLE BEARING PRESSURE<br />

EXIST REINF. DO NOT DAMAGE<br />

#4@12"OC EW, FIELD VERIFY<br />

NOTE:<br />

ALL REINFORCING STEEL IN PUMP BASE SHALL BE CORROSION<br />

RESISTANT ALLOY STEEL, TYPE MMFX-2 GRADE 100 AS<br />

MANUFACTURED BY MMFX TECHNOLOGIES CORP, MEETING<br />

THE REQUIREMENTS OF ASTMA 1035 - "STANDARD<br />

SPECIFICATION FOR DEFORMED AND PLAIN; LOW-CARBON,<br />

CHROMIUM, STEEL BARS FOR CONCRETE PLACEMENT".<br />

* COORDINATE W/ EXIST & NEW, HEIGHT OF CURB W/ EXIST<br />

PIPE & NEW/RECONDITIONED EQUIPMENT & SS PL.<br />

4 PUMP FOUNDATION SECTION<br />

S3<br />

3/4" = 1'-0"<br />

MATCH<br />

EXIST<br />

MATCH EXIST<br />

PIPE RADIUS<br />

EXIST 7" REINF SOG<br />

(2)#4 FULL HT EA END<br />

OF WALL, EPOXY EMBED<br />

4" INTO EXIST SLAB<br />

3"<br />

3 SECTION - NEW PIPE SUPPORT WALL<br />

S3<br />

3/4" = 1'-0"<br />

NEW 8" WIDE<br />

CONCRETE WALL<br />

NEW 1/2"ø SS RODS<br />

(AISI 316)<br />

REMOVE EXIST<br />

CONCRETE PIPE<br />

SUPPORT. DO NOT<br />

DAMAGE EXISTING<br />

REINF<br />

PROVIDE NUT. TACK WELD<br />

OR DAMAGE THREADS<br />

(2)#4 HORIZ CENTER W/<br />

HK EA END BELOW PIPE<br />

2" CLR<br />

2" CLR<br />

2<br />

S3<br />

2" CLR<br />

NEW #4 VERT EA END<br />

EXIST<br />

REINF<br />

3/4" CHAMFER<br />

NEW PIPE SUPPORT<br />

WALL ENLARGED PLAN<br />

3/4" = 1'-0"<br />

NEW #4 HORIZ<br />

8"<br />

2<br />

S3<br />

7'-6"<br />

NEW PIPE<br />

SUPPORT WALL<br />

1 PUMP FOUNDATION SUPPORT PLANS<br />

S3<br />

1/8" = 1'-0"<br />

PLAN NOTE:<br />

1. EXISTING PIPE SUPPORT AND PUMP SUPPORT PADS TO BE<br />

REMOVED AND REPLACED W/ NEW PIPE SUPPORT WALLS AND<br />

PUMP FOUNDATION SUPPORTS.<br />

2. ALL EARTHWORK AND DEMOLITION WORK SHALL BE<br />

EXECUTED WITH CARE TO AVOID POSSIBLE DAMAGE TO<br />

EXISTING CONDUIT AND WIRING. LOCATE ALL CONDUITS AND<br />

WIRING IN VICINITY OF WORK DEPICTED ON THESE DRAWINGS<br />

PRIOR TO CONSTRUCTION.<br />

SEE GENERAL NOTES, SHEET 2,<br />

AND SPECIFICATION SECTION<br />

02220, 3.02<br />

PAUL S MOERSCHEL<br />

FL PE #60487<br />

CERTIFICATE OF AUTHORIZATION NO. 27322<br />

12550 Professional Park Drive, Suite 7<br />

FORT MYERS, FL 33913<br />

PHONE: (239) 939-1414<br />

FAX: (239) 278-4289<br />

© 2011 - TRC Worldwide Engineering, <strong>Inc</strong>.<br />

All rights reserved.<br />

www.trcww.com<br />

FOR 22x34 THE SCALE IS AS NOTED.<br />

FOR 11x17 THE SCALE IS 50% OF THE SCALE SHOWN.<br />

TO THE BEST OF MY KNOWLEDGE AND<br />

ABILITY, THE COMPLETED STRUCTURE<br />

DEPICTED ON THESE PLANS COMPLIES<br />

WITH THE APPLICABLE<br />

MINIMUM BUILDING CODES.<br />

FILE No.<br />

11FTM245<br />

10/2/2012 12:54:48 PM<br />

950 Encore Way<br />

Naples, FL 34110<br />

Phone: (239) 254-2000<br />

Florida Certificate of<br />

Authorization No. 1772<br />

DESIGN BY:<br />

DRAWN BY:<br />

CHECKED BY:<br />

CAD FILE:<br />

PSM<br />

KLI<br />

PSM<br />

11FTM245<br />

PSM<br />

Florida Reg. No.<br />

_____<br />

COUNTY WATER-SEWER DISTRICT<br />

COLLIER COUNTY, FL<br />

PUMP REPLACEMENTS<br />

RAW BOOSTER PUMP STATION<br />

PLANS & SECTIONS<br />

PROJECT NO. :<br />

DATE :<br />

SHEET NO. :<br />

2011054<br />

10/2012<br />

S3