STRUCTURAL NOTES<br />
10/2/2012 12:54:47 PM<br />
1010 GENERAL CONDITIONS AND STATEMENTS:<br />
A. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS<br />
AND MECHANICAL, PLUMBING DRAWINGS. CONSULT THESE DRAWINGS FOR DIMENSIONS,<br />
AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS. THE CONTRACTOR SHALL<br />
COMPARE AND COORDINATE WITH ALL DISCIPLINES AND REPORT ANY DISCREPANCIES TO<br />
ENGINEER PRIOR TO FABRICATION.<br />
B. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANY DISCREPANCIES<br />
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH THE<br />
AFFECTED PART OF THE WORK.<br />
C. DO NOT SCALE OFF DRAWINGS OR DETAILS. DIMENSIONS PROVIDED ON PLAN OVERIDE<br />
ANY SCALED DIMENSIONS.<br />
D. THE STRUCTURE DEPICTED ON THE DRAWINGS IS DESIGNED TO BE SELF-SUPPORTING,<br />
STABLE AND STRUCTURALLY SOUND AFTER THE BUILDING IS COMPLETE. IT IS THE<br />
CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE<br />
TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS<br />
INCLUDES PROVIDING TEMPORARY SHORING, SHEETING, BRACING, GUYS OR TIEDOWNS TO<br />
RESIST LOADS IMPOSED BY GRAVITY, SOIL, CONSTRUCTION LOADS, WIND AND SEISMIC<br />
(WHERE APPLICABLE).<br />
E. DETAILS, NOTES, KEYNOTES OR ANY INFORMATION SHOWN ON ANY PART OF THE<br />
DRAWINGS SHALL BE APPLIED TO ALL APPLICABLE OR SIMILAR CONDITIONS AND IF NOTED<br />
AS TYPICAL OR SHOWN FOR ONE CONDITION, SHALL BE APPLIED FOR ALL LIKE OR SIMILAR<br />
CONDITIONS UNLESS NOTED OTHERWISE. THE CONTRACTOR MUST USE, IN CONJUNCTION<br />
WITH STRUCTURAL DRAWINGS, MECHANICAL, PLUMBING AND SITE DRAWINGS TO<br />
DETERMINE WHERE CONDITIONS THAT ARE LIKE OR SIMILAR APPLY.<br />
F. WHERE A CONFLICT EXISTS BETWEEN STRUCTURAL DRAWINGS AND STRUCTURAL<br />
SPECIFICATIONS THE DRAWINGS SHALL GOVERN.<br />
1015 EXISTING STRUCTURE:<br />
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS TAKEN<br />
FROM THE DRAWINGS THAT WERE:<br />
PREPARED FOR: COUNTY WATER-SEWER DISTRICT<br />
COLLIER COUNTY, FL<br />
PREPARED BY: CONSOER, TOWNSEND & ASSOC.<br />
ENTITLED: RAW WATER BOOSTER PUMPING STATION<br />
DATED: 7-20-1990<br />
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS<br />
PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS<br />
INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES,<br />
MATERIALS, DETAILS, ETC. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO<br />
VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO DETERMINE IF<br />
MODIFICATIONS AS INDICATED ON DRAWINGS ARE FEASIBLE AND PRACTICAL. FIELD<br />
DIMENSIONS AND SURVEY EXISTING STRUCTURE FOR NEW STRUCTURAL ELEMENTS<br />
PRIOR TO FABRICATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES<br />
OR CONFLICTS.<br />
1020 STRUCTURAL DEMOLITION<br />
A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SELECTING METHODS OF<br />
DEMOLITION SO THAT THE REMAINING STRUCTURE WILL NOT BE IMPAIRED OR<br />
DAMAGED.<br />
B. SAWCUTTING AND CORING SHALL BE UTILIZED TO THE FULLEST EXTENT POSSIBLE.<br />
ISOLATE CONSTRUCTION TO BE REMOVED FROM THE STRUCTURE TO REMAIN.<br />
C. ONLY OVERCUT OPENINGS WHERE INDICATED. USE APPROPRIATE SIZE CORES AT<br />
CORNERS SO THAT OVERCUTTING AT CORNERS WILL NOT BE NECESSARY. USE<br />
CHIPPING TOOLS WHERE CORNERS ARE REQUIRED TO BE SQUARE.<br />
D. SELECT METHODS OF TRANSPORTING DEBRIS THROUGH THE BUILDING WHICH WILL<br />
NOT OVERLOAD THE EXISTING OR NEW BUILDING.<br />
E. PROVIDE SHORING REQUIRED TO SUPPORT THE STRUCTURE WHEN NEW WORK TO<br />
STRENGTHEN THE STRUCTURE CANNOT BE INSTALLED PRIOR TO DEMOLITION.<br />
MAINTAIN SHORING UNTIL NEW WORK HAS ATTAINED DESIGN STRENGTH.<br />
1061 DESIGN LOADS:<br />
THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED IN ACCORDANCE<br />
WITH THE 2007 EDITION OF THE FLORIDA BUILDING CODE (2007 FBC) WITH FLORIDA<br />
BUILDING CODE 2009 SUPPLEMENT, BY THE SOUTHERN BUILDING CODE CONGRESS<br />
INTERNATIONAL, INC.<br />
1120 SUBMITTAL (SHOP DRAWING) REVIEW:<br />
A. SUBMITTALS (SHOP DRAWINGS) WILL BE REVIEWED FOR GENERAL COMPLIANCE<br />
WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IF ANY DEVIATIONS<br />
FROM CONTRACT DOCUMENTS BECOME APPARENT DURING REVIEW, AS A COURTESY,<br />
ENGINEER/ARCHITECT MAY MARK UP DEVIATIONS ON SHOP DRAWINGS DURING THE<br />
SUBMITTAL PROCESS. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR<br />
TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS INCLUDING BUT NOT<br />
LIMITED TO QUANTITY, LENGTH, ELEVATIONS AND DIMENSIONS. FABRICATION<br />
REQUIREMENTS, CONSTRUCTION MEANS AND METHODS, COORDINATION OF WORK<br />
WITH OTHER TRADES OR CONSTRUCTION SAFETY REQUIREMENTS.<br />
B. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL<br />
TO THE ARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUT REVIEW, OR IF<br />
SUBMITTAL IS INCOMPLETE, WILL BE REJECTED AND WILL NOT BE REVIEWED. TRC<br />
WORLDWIDE ENGINEERING, INC WILL NOT BE RESPONSIBLE FOR DELAYS CAUSED BY<br />
REJECTED DRAWINGS.<br />
C. SHOP DRAWING SUBMITTALS SHALL FOLLOW THE REQUIREMENTS IN CONTRACT<br />
SPECIFICATIONS SECTION 01330<br />
D. THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS UNLESS<br />
OTHERWISE SPECIFIED IN WRITING BY THE ENGINEER.<br />
E. CHANGES AND ADDITIONS MADE ON RE-SUBMITTALS SHALL BE CLEARLY FLAGGED<br />
AND NOTED. THE PURPOSE OF THE RE-SUBMITTALS SHALL BE CLEARLY NOTED ON<br />
THE LETTER OF TRANSMITTAL. ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO<br />
THOSE ITEMS CAUSING THE RE-SUBMITTAL.<br />
1121 DELEGATE ENGINEERING COMPONENTS AND REQUIREMENTS:<br />
A. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUM REQUIRE<br />
FABRICATION AND ERECTION DRAWINGS PREPARED BY A DELEGATED ENGINEER:<br />
STAINLESS STEEL BASE & ANCHOR RODS.<br />
B. SUBMITTALS SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECT AND<br />
APPLICABLE CODES, LIST THE DESIGN CRITERIA, AND SHOW ALL DETAILS AND<br />
PLANS NECESSARY FOR PROPER FABRICATION AND INSTALLATION. CALCULATIONS<br />
AND SHOP DRAWINGS SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED. GENERIC<br />
PRODUCTS WILL NOT BE ACCEPTED.<br />
C. SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDER THE DIRECT<br />
SUPERVISION AND CONTROL OF THE DELEGATED ENGINEER.<br />
D. SHOP DRAWINGS AND CALCULATIONS REQUIRE THE IMPRESSED SEAL, DATE<br />
AND SIGNATURE OF THE DELEGATED ENGINEER. COMPUTER PRINTOUTS ARE AN<br />
ACCEPTABLE SUBSTITUTE FOR MANUAL COMPUTATIONS PROVIDED THEY ARE<br />
ACCOMPANIED BY SUFFICIENT DESCRIPTIVE INFORMATION TO PERMIT THEIR<br />
PROPER EVALUATION. SUCH DESCRIPTIVE INFORMATION SHALL BEAR THE<br />
IMPRESSED SEAL AND SIGNATURE OF THE DELEGATED ENGINEER AS AN<br />
INDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITY FOR THE RESULTS.<br />
SEPIAS DO NOT REQUIRE SIGNATURE AND SEAL. THE STRUCTURAL ENGINEER WILL<br />
RETAIN ONE SIGNED AND SEALED BLUELINE PRINT FOR RECORD.<br />
E. DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FOR FABRICATION AND<br />
INSTALLATION (SUCH AS REINFORCING STEEL SHOP DRAWINGS OR STRUCTURAL<br />
STEEL ERECTION DRAWINGS) AND REQUIRING NO ENGINEERING DO NOT REQUIRE<br />
THE SEAL OF A DELEGATED ENGINEER. HOWEVER, ALL STRUCTURAL STEEL<br />
CONNECTIONS NOT DETAILED ON THESE DRAWINGS SHALL BE DESIGNED AND<br />
DETAILED BY DELEGATE ENGINEER, BASED ON LOADS AND PROJECT<br />
REQUIREMENTS PROVIDED HEREIN.<br />
F. CATALOG INFORMATION ON STANDARD PRODUCTS DOES NOT REQUIRE THE<br />
SEAL OF A DELEGATED ENGINEER.<br />
G. REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OF SUBMITTALS IS LIMITED<br />
TO VERIFYING THE FOLLOWING:<br />
a) THAT THE SPECIFIED STRUCTURAL SUBMITTALS HAVE BEEN FURNISHED.<br />
b) THAT THE STRUCTURAL SUBMITTALS HAVE BEEN SIGNED AND SEALED BY THE<br />
DELEGATED ENGINEER.<br />
c) THAT THE DELEGATED ENGINEER HAS UNDERSTOOD THE DESIGN INTENT AND<br />
HAS USED THE SPECIFIED STRUCTURAL CRITERIA. (NO DETAILED CHECK OF<br />
CALCULATIONS WILL BE MADE).<br />
d) THAT THE CONFIGURATION SET FORTH IN THE STRUCTURAL SUBMITTALS IS<br />
CONSISTENT WITH THE CONTRACT DOCUMENTS. (NO DETAILED CHECK OF<br />
DIMENSIONS OR QUANTITIES WILL BE MADE).<br />
H. SUBMITTALS NOT MEETING THE ABOVE CRITERIA WILL NOT BE REVIEWED.<br />
2011 FOUNDATIONS:<br />
A. GEOTECHNICAL INVESTIGATION, TESTING, STUDIES, FOUNDATION<br />
RECOMMENDATIONS, AND SITE PREPARATION REQUIREMENTS HAS NOT BEEN<br />
PERFORMED BY TRC WORLDWIDE ENGINEERS, INC.<br />
B. FOUNDATION DESIGN IS BASED ON AN SOIL BEARING PRESSURE OF 2,000 PSF.<br />
C. SOIL TO BE COMPACTED TO CONTRACT SPECIFICATIONS OF 98% MODIFIED<br />
PROCTOR OR GREATER.<br />
3101 FORMWORK:<br />
1. NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HAS REACHED AT<br />
LEAST TWO-THIRDS OF THE 28 DAY DESIGN STRENGTH.<br />
a) DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK SHALL MEET<br />
REQUIREMENTS SET FORTH IN ACI STANDARDS 347 AND 301.<br />
2. CONSTRUCT FORMWORK SO CONCRETE SURFACES CONFORM TO THE<br />
TOLERANCE LIMITS OF ACI 117 [STANDARD SPECIFICATIONS FOR TOLERANCES FOR<br />
CONCRETE CONSTRUCTION MATERIALS]. THE CLASS OF SERVICE FOR OFFSET<br />
BETWEEN ADJACENT PIECES OF FORMWORK FACING MATERIAL SHALL BE CLASS B<br />
FOR SURFACES PERMANENTLY EXPOSED TO PUBLIC VIEW AND CLASS D FOR<br />
SURFACES THAT WILL BE PERMANENTLY CONCEALED.<br />
3. PROVIDE 3/4" CHAMFER FOR ALL EXPOSED CONCRETE EDGES.<br />
3201 REINFORCING STEEL:<br />
A. SHALL BE MMFX DEFORMED BARS, FREE FROM OIL, SCALE AND RUST AND<br />
PLACED IN ACCORDANCE WITH THE TYPICAL BENDING DIAGRAM AND PLACING<br />
DETAILS OF ACI STANDARDS AND SPECIFICATIONS. SECURE APPROVAL OF<br />
SHOP DRAWINGS PRIOR TO COMMENCING FABRICATION. REINFORCING BAR<br />
DETAILING SHALL COMPLY WITH ACI 315 "MANUAL OF STANDARD PRACTICE FOR<br />
DETAILING REINFORCED CONCRETE STRUCTURES".<br />
B. UNLESS NOTED OTHERWISE ON SECTIONS AND DETAILS, PROVIDE THE<br />
FOLLOWING CONCRETE COVER FOR REINFORCING STEEL:<br />
REINFORCING STEEL COVER (PRESTRESSED AND NON-PRESTRESSED<br />
CONCRETE) CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH<br />
GROUND<br />
SLABS, WALLS, JOISTS<br />
#14 & #18 BARS.........................................................1 1/2"<br />
#11 BAR & SMALLER................................................3/4"<br />
CONCRETE EXPOSED TO WEATHER OR EARTH*<br />
#6 BAR THRU #18 BARS..........................................2"<br />
#5 BAR, W31 OR D31 WIRE, AND SMALLER....... 1 1/2"<br />
GRADE BEAMS<br />
TIES, STIRRUPS - TOP & FORMED FACES...... 2"<br />
BOTTOM & UNFORMED FACES.......................3"<br />
FOOTINGS & PILECAPS<br />
TOP.............................................................................. 2"<br />
BOTTOM & SIDES...................................................... 3"<br />
COVERAGE TO REINFORCING REQUIREMENTS APPLIES ALSO TO ANY EDGE OF<br />
SLAB OR OPENING.<br />
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DRIPS, CHAMFERS,<br />
REGLETS, SLOTS, SLEEVES, ANCHORS, AND INSERTS. UNLESS SHOWN ON<br />
STRUCTURAL DRAWINGS NO OPENINGS LARGER THAN 12"x12" SHALL BE<br />
PLACED IN SLABS OR WALLS. FOR OPENINGS NOT SHOWN ON STRUCTURAL<br />
DRAWINGS, APPROVALS MUST BE OBTAINED FROM THE ENGINEER PRIOR TO<br />
FABRICATION OF STEEL AND PLACEMENT OF CONCRETE. LOCATION DRAWINGS<br />
FOR ALL SLEEVES AND BLOCKOUTS IN THE CONCRETE SHALL BE SUBMITTED<br />
FOR APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TO PLACEMENT.<br />
D. ALL CONDUIT, SLEEVES, AND PIPES EMBEDDED IN OR PASSING THRU<br />
CONCRETE SHALL CONFORM TO SECTION 6.3 OF ACI 318 AND THE FOLLOWING:<br />
1. SLEEVES AND PIPES SHALL BE PLACED SO THAT REINFORCING STEEL<br />
CAN BE PLACED WITH THE SPECIFIED COVER AND CLEAR DISTANCE<br />
BETWEEN BARS.<br />
2. THE CONCRETE COVERING OF PIPE AND SLEEVES SHALL NOT BE<br />
LESS THAN 11/2 INCHES. CLEAR DISTANCE BETWEEN SUCH PIPES<br />
AND SLEEVES SHALL NOT BE LESS THAN SIX INCHES.<br />
3. CONDUIT AND PIPES PLACED IN SLABS AND TOPPING OVER SLABS<br />
SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN ONE-THIRD THE<br />
THICKNESS OF SLAB OR TOPPING, AND SHALL BE PLACED IN THE<br />
MIDDLE THIRD OF SLAB DEPTH.<br />
4. CONDUITS AND PIPES PLACED IN COLUMNS SHALL NOT DISPLACE<br />
MORE THAN 4% OF THE CROSS SECTIONAL AREA OF COLUMN AND<br />
SHALL BE LOCATED ON THE CENTER LINE OF COLUMN. OUTLET<br />
BOXES TO BE NOT DEEPER THAN REQUIRED CLEARANCE FOR REINF.<br />
5. INSERTS W/ 3/4" MAX. EMBEDMENT SHALL BE USED TO SUPPORT<br />
CONDUITS, PIPES, AND DUCT FROM THE SLAB. 1-3/8" DEEP (MAX.)<br />
UNISTRUT INSERTS (OR APPROVED EQUAL) ME BE USED TO SUPPORT<br />
MECHANICAL AND PLUMBING EQUIPMENT AT CORRIDORS ONLY (AVOID<br />
CONFLICT W/ POST-TENSION TENDONS).<br />
E. ALL CONTINUOUS BARS SHALL HAVE CLASS B FULL TENSION LAPS UNLESS<br />
INDICATED OTHERWISE. PROVIDE CORNER BARS AT ALL WALL, GRADE BEAM<br />
AND STRIP FOOTING CORNERS. BARS SHALL BE THE SAME SIZE AND SPACING<br />
AS THE HORIZONTAL REINFORCING. INTERSECTING WALLS, GRADE BEAMS AND<br />
STRIP FOOTINGS SHALL BE DOWELED TOGETHER IN THE SAME MANNER.<br />
PROVIDE 2 NO. 4 TOP DIAGONAL BARS 4'-0" LONG AT ALL REENTRANT CORNERS<br />
IN ALL SLABS ON GRADE AND ELEVATED SLABS.<br />
G. SHOP DRAWINGS SHALL DETAIL ALL CONCRETE WALLS IN ELEVATION.<br />
950 Encore Way<br />
Naples, FL 34110<br />
Phone: (239) 254-2000<br />
Florida Certificate of<br />
Authorization No. 1772<br />
DESIGN BY:<br />
DRAWN BY:<br />
CHECKED BY:<br />
CAD FILE:<br />
3301 CONCRETE:<br />
A. SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TO ACHIEVE A<br />
STRENGTH AT 28 DAYS AS LISTED BELOW WITH A PLASTIC AND WORKABLE<br />
MIX:<br />
4000 PSI FOR ALL CONCRETE<br />
CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI 301-05<br />
STANDARDS AND SPECIFICATIONS.<br />
B. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDER OR LAB<br />
TESTS FOR REVIEW PRIOR TO USE. ONLY TYPE II CEMENT SHALL BE USED<br />
FOR SLAB-ON-GRADE CONCRETE. MIX SHALL BE UNIQUELY IDENTIFIED BY<br />
MIX NUMBER OR OTHER POSITIVE IDENTIFICATION. MIX SHALL MEET THE<br />
REQUIREMENTS OF ASTM C33 FOR COARSE AGGREGATE. CONCRETE SHALL<br />
COMPLY WITH THE REQUIREMENTS OF ASTM STANDARD C94 FOR<br />
MEASURING, MIXING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE<br />
TIME STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED<br />
FROM THE TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITS<br />
FINAL POSITION SHALL NOT EXCEED ONE AND ONE HALF (1-1/2) HOURS. IF<br />
FOR ANY REASON THERE IS A LONGER DELAY THAN THAT STATED ABOVE,<br />
THE CONCRETE SHALL BE DISCARDED. IT SHALL BE THE RESPONSIBILITY OF<br />
THE TESTING LAB TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE<br />
CONTRACTOR OF ANY NONCOMPLIANCE WITH THE ABOVE. SLABS SHALL<br />
BE CURED USING A DISSIPATING CURING COMPOUND MEETING ASTM<br />
STANDARD C309 TYPE 1-D AND SHALL HAVE A FUGITIVE DYE. THE<br />
COMPOUND SHALL BE PLACED AS SOON AS THE FINISHING IS COMPLETED<br />
OR AS SOON AS THE WATER HAS LEFT THE UNFINISHED CONCRETE.<br />
SCUFFED OR BROKEN AREAS IN THE CURING MEMBRANE SHALL BE<br />
RECOATED DAILY. CALCIUM CHLORIDES SHALL NOT BE UTILIZED; OTHER<br />
ADMIXTURES MAY BE USED ONLY WITH THE APPROVAL OF THE ENGINEER.<br />
C. CONCRETE MIX DESIGNS SHALL INCLUDE A WRITTEN DESCRIPTION<br />
INDICATING WHERE EACH PARTICULAR MIX IS TO BE PLACED WITHIN THE<br />
STRUCTURE. FAILURE TO COMPLY MAY RESULT IN REJECTION OF THE MIX. IF<br />
ACCEPTED, PEA ROCK PUMP MIX USE IS LIMITED TO VERTICAL ELEMENT<br />
POURS AND BEAM POURS LESS THAN 60 LINEAL FEET PER POUR.<br />
D. CONCRETE DESIGN MIX SUBMITTALS SHALL INCLUDE TESTED,<br />
STATISTICAL BACK-UP DATA AS PER CHAPTER 5 OF ACI 318.<br />
E. WATER/CEMENTITIONS MATERIAL RATIO FOR CONCRETE SHALL NOT<br />
EXCEED 0.45 BY WEIGHT.<br />
F. CONFORM TO ACI 306R FOR COLD WEATHER CONCRETING AND ACI 305R<br />
FOR HOT WEATHER CONCRETING WHEN ANY COMBINATION OF HIGH<br />
TEMPERATURE, LOW RELATIVE HUMIDITY AND WIND VELOCITY TEND TO<br />
IMPAIR THE QUALITY OF THE CONCRETE. CONCRETE IS TO BE REJECTED IF<br />
ITS TEMPERATURE AT TIME OF PLACEMENT IS 90°F OR ABOVE. PROTECT<br />
SURFACES OF EXPOSED CONCRETE FROM PRECIPITATION DAMAGE UNTIL<br />
ADEQUATE STRENGTH IS GAINED TO PREVENT DAMAGE.<br />
3304 CONCRETE TESTING:<br />
A. AN INDEPENDENT TESTING LABORATORY SHALL PERFORM THE<br />
FOLLOWING TESTS ON CAST IN PLACE CONCRETE:<br />
a)ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF<br />
PORTLAND CEMENT CONCRETE." SLUMP SHALL RANGE FROM 3 TO 5<br />
INCHES.<br />
b)ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVE<br />
STRENGTH OF CYLINDRICAL CONCRETE SPECIMENS."<br />
B. A SEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS, FOR<br />
EVERY 50 CUBIC YARDS (OR FRACTION THEREOF), 5,000 S.F. OF<br />
SURFACE AREA OR EACH PLACEMENT OF EACH MIX DESIGN OF<br />
CONCRETE PLACED IN ANY ONE DAY. REQUIRED CYLINDER(S)<br />
QUANTITIES AND TEST AGE AS FOLLOWS:<br />
1 AT 7 DAYS<br />
2 AT 28 DAYS<br />
ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THE<br />
DIRECTION OF THE ENGINEER, IF REQUIRED. IF 28 DAY STRENGTH IS<br />
ACHIEVED, THE ADDITIONAL CYLINDER(s) MAY BE DISCARDED. ANY<br />
ADDITIONAL CYLINDERS REQUESTED BY CONTRACTOR SHALL BE AT<br />
CONTRACTOR'S EXPENSE.<br />
C. CYLINDERS AND TEST REPORTS SHALL BE CLEARLY LABELED WITH<br />
DATE SAMPLED AND WHERE CONCRETE WAS SPECIFICALLY PLACED.<br />
D. TEST REPORTS SHALL BE KEPT AT JOB SITE, WITH COPIES SENT<br />
DIRECLY TO ENGINEER.<br />
PSM<br />
KLI<br />
PSM<br />
11FTM245<br />
PSM<br />
Florida Reg. No.<br />
_____<br />
FOR 22x34 THE SCALE IS AS NOTED.<br />
FOR 11x17 THE SCALE IS 50% OF THE SCALE SHOWN.<br />
COUNTY WATER-SEWER DISTRICT<br />
COLLIER COUNTY, FL<br />
PUMP REPLACEMENTS<br />
RAW BOOSTER PUMP STATION<br />
STRUCTURAL NOTES<br />
PAUL S MOERSCHEL<br />
FL PE #60487<br />
CERTIFICATE OF AUTHORIZATION NO. 27322<br />
12550 Professional Park Drive, Suite 7<br />
FORT MYERS, FL 33913<br />
PHONE: (239) 939-1414<br />
FAX: (239) 278-4289<br />
© 2011 - TRC Worldwide Engineering, <strong>Inc</strong>.<br />
All rights reserved.<br />
www.trcww.com<br />
TO THE BEST OF MY KNOWLEDGE AND<br />
ABILITY, THE COMPLETED STRUCTURE<br />
DEPICTED ON THESE PLANS COMPLIES<br />
WITH THE APPLICABLE<br />
MINIMUM BUILDING CODES.<br />
FILE No.<br />
11FTM245<br />
PROJECT NO. :<br />
DATE :<br />
SHEET NO. :<br />
2011054<br />
10/2012<br />
S1
ITEM<br />
CONCRETE (PLAN)<br />
CONCRETE (SECTION)<br />
EARTH<br />
BRICK<br />
SECTION INDICATOR<br />
DETAIL INDICATOR<br />
TOP REBAR<br />
BOTTOM REBAR<br />
TOP OF FOOTING ELEVATION<br />
SPOT ELEVATION TOP OF CONCRETE<br />
STEP IN FTG., GRADE BM. OR OTHER<br />
STRUCTURAL ELEMENT<br />
CL BEAM SPLICE<br />
AND<br />
PLATE<br />
CENTERLINE<br />
NUMBER (PRECEEDING)<br />
PLUS OR TENSION<br />
MINUS OR COMPRESSION<br />
POUNDS (FOLLOWING)<br />
TOP OF STEEL ELEVATION<br />
COLUMN SYMBOLS<br />
L E G E N D<br />
LOAD BEARING CONCRETE BLOCK (CMU)<br />
STEP IN STRUCTURE OR DEPRESSED SLAB<br />
INDICATES COLUMN BELOW<br />
INDICATES COLUMN THRU<br />
INDICATES COLUMN ABOVE<br />
COLUMN/PILASTER MARK<br />
FOOTING MARK<br />
TOP OF FOOTING<br />
ELEVATION<br />
C1/P1<br />
F1<br />
-1'-4"<br />
SYMBOL<br />
0'-0"<br />
+0'-0"<br />
&<br />
PL<br />
8"<br />
S<br />
S<br />
CL<br />
#, NO.<br />
+<br />
-<br />
#<br />
T/STL. EL. +20'-8" or (+20'-8")<br />
REINF SYMBOLS<br />
BAR SIZE<br />
BAR SPACING<br />
BAR PLACEMENT<br />
1"<br />
4/12T<br />
1<br />
S0.3<br />
1<br />
S0.3<br />
T=TOP<br />
B=BOTTOM<br />
C=`C'<br />
E=`E'<br />
ABBREVIATIONS<br />
AR<br />
- ANCHOR ROD<br />
K<br />
- KIP(s), 1000 POUNDS<br />
ALT - ALTERNATE<br />
KLF - KIPS PER LINEAR FOOT<br />
APPROX - APPROXIMATELY<br />
KJ<br />
- CONSTRUCTION JOINT<br />
ARCH - ARCHITECT<br />
L<br />
- ANGLE<br />
ARCHL - ARCHITECTURAL<br />
LG<br />
- LONG<br />
B/ - BOTTOM OF<br />
LLH - LONG LEG HORIZONTAL<br />
BC<br />
- BOTTOM CHORD<br />
LLV - LONG LEG VERTICAL<br />
BLDG - BUILDING<br />
LP<br />
- LOW POINT<br />
BM - BEAM<br />
LW - LONG WAY<br />
BOTT - BOTTOM<br />
LWT - LIGHTWEIGHT<br />
BRG - BEARING<br />
MFR - MANUFACTURER<br />
C/C - CENTER TO CENTER<br />
MAS - MASONRY<br />
CIP - CAST IN PLACE<br />
MO - MASONRY OPENING<br />
CJ<br />
- CONTRACTION JOINT<br />
MATL - MATERIAL<br />
CL<br />
- CENTERLINE<br />
MAX - MAXIMUM<br />
CLR - CLEAR<br />
MECHL<br />
- MECHANICAL<br />
CMU - CONCRETE MASONRY UNIT MTL - METAL<br />
COL - COLUMN<br />
MIN - MINIMUM<br />
CONC - CONCRETE<br />
MISC - MISCELLANEOUS<br />
CONFIG - CONFIGURATION<br />
NS<br />
- NEAR SIDE<br />
CONT - CONTINUOUS<br />
NIC - NOT IN CONTRACT<br />
CONTR - CONTRACTOR<br />
NTS - NOT TO SCALE<br />
CTR - CENTER<br />
NW - NORMAL WEIGHT<br />
DBL - DOUBLE<br />
OC - ON CENTER<br />
DET - DETAIL<br />
OH - OPPOSITE HAND<br />
DIA - DIAMETER<br />
OPNG - OPENING<br />
DIM - DIMENSION<br />
PAF - POWER ACTUATED FASTENERS<br />
<strong>DN</strong><br />
- DOWN<br />
PART - PARTITION<br />
DR<br />
- DRAIN<br />
PARTL - PARTIAL<br />
DWG - DRAWING<br />
PCJ - PRECAST CONCRETE JOIST<br />
EA<br />
- EACH<br />
PL<br />
- PLATE<br />
EE<br />
- EACH END<br />
PLF - POUNDS PER LINEAR FOOT<br />
EF<br />
- EACH FACE<br />
PSF - POUNDS PER SQUARE FOOT<br />
EJ<br />
- EXPANSION JOINT<br />
PSI - POUNDS PER SQUARE INCH<br />
EL<br />
- ELEVATION<br />
PT<br />
- POST TENSIONED<br />
ELEV - ELEVATOR<br />
PrT - PRESSURE TREATED<br />
ENGR - ENGINEER<br />
R<br />
- RADIUS<br />
EOR - ENGINEER OF RECORD REG - REGULAR<br />
EOS - EDGE OF SLAB<br />
REINF - REINFORCING<br />
EQ<br />
- EQUAL<br />
REM - REMAINDER<br />
EW - EACH WAY<br />
REQD - REQUIRED<br />
EXIST - EXISTING<br />
REV - REVISED/REVISION<br />
EXP - EXPANSION<br />
RM - ROOM<br />
EXT - EXTERIOR<br />
RO - ROUGH OPENING<br />
FD<br />
- FLOOR DRAIN<br />
RQMTS<br />
- REQUIREMENTS<br />
FIN - FINISH<br />
SCHED<br />
- SCHEDULE<br />
FLR - FLOOR<br />
SECT - SECTION<br />
FND - FOUNDATION<br />
SIM - SIMILAR<br />
FOM - FACE OF MASONRY<br />
SL<br />
- SLOPE<br />
FS<br />
- FAR SIDE<br />
SOG - SLAB-ON-GRADE<br />
FT<br />
- FOOT<br />
SP<br />
- SPIRAL<br />
FTG - FOOTING<br />
SQ<br />
- SQUARE<br />
GA<br />
- GAGE<br />
SS<br />
- STAINLESS STEEL<br />
GALV - GALVANIZED<br />
STD - STANDARD<br />
GC - GENERAL CONTRACTOR STL - STEEL<br />
GT<br />
- GIRDER TRUSS<br />
STRUCTL - STRUCTURAL<br />
HC<br />
- HOLLOW CORE<br />
SW# - SHEARWALL<br />
HCP - HOLLOW CORE PLANK SW - SHORT WAY<br />
HDG - HOT DIPPED GALVANIZED T/ - TOP OF<br />
HG - HIP GIRDER<br />
TB<br />
- TIE BEAM<br />
HK<br />
- HOOK<br />
TC<br />
- TIE COLUMN<br />
HORIZ<br />
- HORIZONTAL<br />
TEMP - TEMPERATURE<br />
HP<br />
- HIGH POINT<br />
TJ<br />
- TIE JOIST<br />
HS<br />
- HIGH STRENGTH<br />
TR<br />
- TRUSS<br />
IJ<br />
- ISOLATION JOINT<br />
TYP - TYPICAL<br />
INFO - INFORMATION<br />
UNO - UNLESS NOTED OTHERWISE<br />
INS - INSULATION<br />
VERT - VERTICAL<br />
INT - INTERIOR<br />
W/ - WITH<br />
IRR - IRREGULAR<br />
W/O - WITHOUT<br />
JB<br />
- JOIST BEARING<br />
WD - WOOD<br />
JBE - JOIST BEARING ELEVATION WF -WALL FOOTING<br />
JR<br />
- JAMB REINFORCING<br />
WP - WORK POINT<br />
JT<br />
- JOINT<br />
WWR - WELDED WIRE REINFORCING<br />
PAUL S MOERSCHEL<br />
FL PE #60487<br />
CERTIFICATE OF AUTHORIZATION NO. 27322<br />
12550 Professional Park Drive, Suite 7<br />
FORT MYERS, FL 33913<br />
PHONE: (239) 939-1414<br />
FAX: (239) 278-4289<br />
© 2011 - TRC Worldwide Engineering, <strong>Inc</strong>.<br />
All rights reserved.<br />
www.trcww.com<br />
FOR 22x34 THE SCALE IS AS NOTED.<br />
FOR 11x17 THE SCALE IS 50% OF THE SCALE SHOWN.<br />
TO THE BEST OF MY KNOWLEDGE AND<br />
ABILITY, THE COMPLETED STRUCTURE<br />
DEPICTED ON THESE PLANS COMPLIES<br />
WITH THE APPLICABLE<br />
MINIMUM BUILDING CODES.<br />
FILE No.<br />
11FTM245<br />
10/2/2012 12:54:47 PM<br />
950 Encore Way<br />
Naples, FL 34110<br />
Phone: (239) 254-2000<br />
Florida Certificate of<br />
Authorization No. 1772<br />
DESIGN BY:<br />
DRAWN BY:<br />
CHECKED BY:<br />
CAD FILE:<br />
PSM<br />
KLI<br />
PSM<br />
11FTM245<br />
PSM<br />
Florida Reg. No.<br />
_____<br />
COUNTY WATER-SEWER DISTRICT<br />
COLLIER COUNTY, FL<br />
PUMP REPLACEMENTS<br />
RAW BOOSTER PUMP STATION<br />
ABBREVIATIONS<br />
PROJECT NO. :<br />
DATE :<br />
SHEET NO. :<br />
2011054<br />
10/2012<br />
S2
HORIZ REINF TO HAVE<br />
90° HOOK EA END<br />
3/4" CHAMFER<br />
VERT REINF<br />
(6) 3/4"ø SS (AISI TYPE<br />
316) ANCHOR RODS x1'-0"<br />
EMBED ON EA SIDE OF<br />
PUMP & MOTOR BASE<br />
3/4" CHAMFER<br />
PROVIDE NUT TACK WELDED<br />
OR DAMAGED THREADS<br />
SAW CUT 1" DEEP &<br />
EXCAVATE EXIST SLAB FOR<br />
NEW PUMP FOUNDATION<br />
EXIST 7" SLAB<br />
ON GRADE<br />
1'-4"<br />
4" MIN<br />
1'-4" *<br />
GROUT IN NEW STAINLESS STEEL (AISI<br />
316) PLATE W/ PUMP AND MOTOR<br />
SUBMIT SHOP DRAWINGS FOR REVIEW<br />
PRIOR TO CONSTRUCTION.<br />
SEE SPECIFICATION SECTION 11350<br />
FOR ADDITIONAL INFORMATION &<br />
REQUIREMENTS<br />
#5@8"OC EW TOP<br />
2" CLR<br />
2" CLR<br />
3"<br />
CLR<br />
#4@10"OC HORIZ<br />
#5@6"OC VERT<br />
PROVIDE 1/4" AMPLITUDE<br />
ROUGHENED SURFACE<br />
FOR BOND TO EXIST SOG<br />
8"<br />
8"<br />
NEW 3/16"x6" SS<br />
STRAP (AISI 316)<br />
3/4" CHAMFER<br />
3<br />
S3<br />
4'-6"<br />
NEW PIPE<br />
SUPPORT WALL<br />
4<br />
S3<br />
7'-6"<br />
7'-6"<br />
7'-6"<br />
3'-0"<br />
3'-0"<br />
3'-0"<br />
NEW PUMP<br />
FOUNDATION<br />
(TYP 4 PLACES)<br />
5<br />
S3<br />
3" TYP<br />
ALL SIDES<br />
3"<br />
CLR<br />
#5@8"OC EW BOTT<br />
1 1/2"<br />
6"<br />
EXIST PIPE RADIUS<br />
MATCH EXIST<br />
3'-0"<br />
5<br />
S3<br />
ENLARGED PLAN SECTION OF<br />
FOUNDATION REINF<br />
3/4" = 1'-0"<br />
COMPACT SOIL BENEATH FTG<br />
GEOTECH ENG TO VERIFY 2,000 PSF<br />
MIN ALLOWABLE BEARING PRESSURE<br />
EXIST REINF. DO NOT DAMAGE<br />
#4@12"OC EW, FIELD VERIFY<br />
NOTE:<br />
ALL REINFORCING STEEL IN PUMP BASE SHALL BE CORROSION<br />
RESISTANT ALLOY STEEL, TYPE MMFX-2 GRADE 100 AS<br />
MANUFACTURED BY MMFX TECHNOLOGIES CORP, MEETING<br />
THE REQUIREMENTS OF ASTMA 1035 - "STANDARD<br />
SPECIFICATION FOR DEFORMED AND PLAIN; LOW-CARBON,<br />
CHROMIUM, STEEL BARS FOR CONCRETE PLACEMENT".<br />
* COORDINATE W/ EXIST & NEW, HEIGHT OF CURB W/ EXIST<br />
PIPE & NEW/RECONDITIONED EQUIPMENT & SS PL.<br />
4 PUMP FOUNDATION SECTION<br />
S3<br />
3/4" = 1'-0"<br />
MATCH<br />
EXIST<br />
MATCH EXIST<br />
PIPE RADIUS<br />
EXIST 7" REINF SOG<br />
(2)#4 FULL HT EA END<br />
OF WALL, EPOXY EMBED<br />
4" INTO EXIST SLAB<br />
3"<br />
3 SECTION - NEW PIPE SUPPORT WALL<br />
S3<br />
3/4" = 1'-0"<br />
NEW 8" WIDE<br />
CONCRETE WALL<br />
NEW 1/2"ø SS RODS<br />
(AISI 316)<br />
REMOVE EXIST<br />
CONCRETE PIPE<br />
SUPPORT. DO NOT<br />
DAMAGE EXISTING<br />
REINF<br />
PROVIDE NUT. TACK WELD<br />
OR DAMAGE THREADS<br />
(2)#4 HORIZ CENTER W/<br />
HK EA END BELOW PIPE<br />
2" CLR<br />
2" CLR<br />
2<br />
S3<br />
2" CLR<br />
NEW #4 VERT EA END<br />
EXIST<br />
REINF<br />
3/4" CHAMFER<br />
NEW PIPE SUPPORT<br />
WALL ENLARGED PLAN<br />
3/4" = 1'-0"<br />
NEW #4 HORIZ<br />
8"<br />
2<br />
S3<br />
7'-6"<br />
NEW PIPE<br />
SUPPORT WALL<br />
1 PUMP FOUNDATION SUPPORT PLANS<br />
S3<br />
1/8" = 1'-0"<br />
PLAN NOTE:<br />
1. EXISTING PIPE SUPPORT AND PUMP SUPPORT PADS TO BE<br />
REMOVED AND REPLACED W/ NEW PIPE SUPPORT WALLS AND<br />
PUMP FOUNDATION SUPPORTS.<br />
2. ALL EARTHWORK AND DEMOLITION WORK SHALL BE<br />
EXECUTED WITH CARE TO AVOID POSSIBLE DAMAGE TO<br />
EXISTING CONDUIT AND WIRING. LOCATE ALL CONDUITS AND<br />
WIRING IN VICINITY OF WORK DEPICTED ON THESE DRAWINGS<br />
PRIOR TO CONSTRUCTION.<br />
SEE GENERAL NOTES, SHEET 2,<br />
AND SPECIFICATION SECTION<br />
02220, 3.02<br />
PAUL S MOERSCHEL<br />
FL PE #60487<br />
CERTIFICATE OF AUTHORIZATION NO. 27322<br />
12550 Professional Park Drive, Suite 7<br />
FORT MYERS, FL 33913<br />
PHONE: (239) 939-1414<br />
FAX: (239) 278-4289<br />
© 2011 - TRC Worldwide Engineering, <strong>Inc</strong>.<br />
All rights reserved.<br />
www.trcww.com<br />
FOR 22x34 THE SCALE IS AS NOTED.<br />
FOR 11x17 THE SCALE IS 50% OF THE SCALE SHOWN.<br />
TO THE BEST OF MY KNOWLEDGE AND<br />
ABILITY, THE COMPLETED STRUCTURE<br />
DEPICTED ON THESE PLANS COMPLIES<br />
WITH THE APPLICABLE<br />
MINIMUM BUILDING CODES.<br />
FILE No.<br />
11FTM245<br />
10/2/2012 12:54:48 PM<br />
950 Encore Way<br />
Naples, FL 34110<br />
Phone: (239) 254-2000<br />
Florida Certificate of<br />
Authorization No. 1772<br />
DESIGN BY:<br />
DRAWN BY:<br />
CHECKED BY:<br />
CAD FILE:<br />
PSM<br />
KLI<br />
PSM<br />
11FTM245<br />
PSM<br />
Florida Reg. No.<br />
_____<br />
COUNTY WATER-SEWER DISTRICT<br />
COLLIER COUNTY, FL<br />
PUMP REPLACEMENTS<br />
RAW BOOSTER PUMP STATION<br />
PLANS & SECTIONS<br />
PROJECT NO. :<br />
DATE :<br />
SHEET NO. :<br />
2011054<br />
10/2012<br />
S3