THERMAL MANAGEMENT SYSTEMS - Schneider Electric
THERMAL MANAGEMENT SYSTEMS - Schneider Electric
THERMAL MANAGEMENT SYSTEMS - Schneider Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>THERMAL</strong> <strong>MANAGEMENT</strong><br />
<strong>SYSTEMS</strong><br />
Concept 6/2<br />
Selection guide 6/6<br />
VF<br />
Ventilation systems 6/8<br />
ICL-AI/ICT-AI<br />
Air/air exchangers 6/30<br />
ICL-AG/ICT-AG<br />
Air/water exchangers 6/36<br />
CLL/CLT<br />
CLLMP/CLTMP<br />
Cooling units 6/40<br />
- Mechanical control<br />
- Electronic control<br />
RC<br />
Resistance heaters 6/64<br />
- Insulated<br />
- Standard<br />
TS<br />
Control devices 6/80<br />
Thermal management<br />
for electrical panels 6/95<br />
Support service for<br />
the PROclima 4.0 software<br />
calculation 6/100
6/2<br />
Thermal management for electrical and<br />
electronic switchboards: a need
What is temperature control?<br />
Technological evolution<br />
The miniaturisation of components, the generalisation of electronics,<br />
the appearance of new products based on power electronics mean<br />
that temperature management is a need that must increasingly<br />
be taken into account in the design of electrical and/or electronic<br />
switchboards.<br />
What are the advantages of good temperature<br />
control?<br />
Temperature control in electrical switchboards is one of the important<br />
factors of good industrial maintenance.<br />
The risks involved through failure to have a suitable thermal solution<br />
are multiple, affecting the life of components and the performance of<br />
installations to such an extent that they may halt production.<br />
The service life of the components themselves is a function of the<br />
temperature and humidity conditions in the enclosure. Ideal are<br />
values from +15…+35 ºC for temperature and from 30 to 90% relative<br />
humidity (RH).<br />
Cooling, Heating, controlling<br />
Just like the degrees of IP/IK protection suited to each installation,<br />
the equipment installed inside an enclosure needs suitable thermal<br />
protection.<br />
There are different solutions to these problems, depending on<br />
environmental conditions, the nature of the components of the<br />
electrical switchboard, etc.<br />
In some cases it is suffi cient to oversize the enclosure, use fans or<br />
air-air exchangers. In other, more extreme cases, in which the<br />
ambient temperature is higher, air-water heat exchangers or cooling<br />
units must be used.<br />
A solution for every need<br />
With this objective in mind, Himel proposes a comprehensive<br />
Thermal Offer to secure your installation.<br />
Cooling<br />
Heating<br />
Control<br />
Calculation<br />
1. Forced ventilation system<br />
2 . Air/air exchangers<br />
3 . Air/water exchangers<br />
4. Cooling units<br />
5. Resistance heaters<br />
6. Thermal control systems<br />
7. PROclima 4.0 software<br />
6/3
System Natural ventilation Forced ventilation Air-air exchangers<br />
Natural convection helps to reduce the<br />
temperature inside the enclosure, whereby<br />
installing (without filter) outlet grilles or raising<br />
the enclosure tops may be a suitable solution.<br />
Fans with a Himel filter have been designed to<br />
evacuate a large amount of heat economically.<br />
They have an aluminium exchange battery that<br />
separates the two air circuits (inside and outside)<br />
and stops dust from getting inside.<br />
When to use them<br />
This solution is only feasible in cases where the<br />
power that has to be dissipated is weak, and in<br />
atmospheres with low dust levels.<br />
When you need to evacuate greater dissipated<br />
power, and when the outside environment is<br />
polluted.<br />
In highly polluted atmospheres or when large<br />
amounts of heat must be evacuated without<br />
bringing the outside and inside atmospheres<br />
into contact.<br />
Ta: ambient temperature<br />
Td: temperature required<br />
Ta < Td Ta < Td Ta < Td<br />
The inside and outside air circuits are<br />
independent.<br />
NO NO YES<br />
Advantages<br />
c Economic solution.<br />
c Maintenance-free.<br />
c Easy and quick to install.<br />
c Economic solution.<br />
c Easy maintenance.<br />
c Easy and quick to install.<br />
c Even temperature inside the enclosure.<br />
c High protection degree (IP54 or IP55).<br />
c They do not bring the atmospheres inside and<br />
outside the enclosure into contact.<br />
c Easy maintenance.<br />
c High protection degree (IP54).<br />
c The temperature inside the enclosure is always<br />
Drawbacks<br />
c The amount of heat evacuated is weak.<br />
c Reduction in protection degree.<br />
c Dust penetration.<br />
higher than the outside.<br />
c They bring the atmospheres inside and outside<br />
the enclosure into contact.<br />
c Maintenance is required: filter change.<br />
c The temperature inside the enclosure is<br />
always higher than the outside.<br />
Solutions<br />
Outlet grilles<br />
Fans and outlet grills<br />
Air-air exchangers<br />
6/4
Air-water exchangers Cooling Heating<br />
They cool the enclosure by means of a water-cooled exchange<br />
battery.<br />
The regulation of the temperature in the enclosure is performed<br />
by means of a thermostat that closes or opens an<br />
electro-valve.<br />
They are cooling unit devices that guarantee effective and<br />
independent cooling from the outside environment, and avoid<br />
the appearance of heat sources.<br />
Resistance heaters avoid problems of condensation inside the<br />
enclosure and guarantee maintenance of the ideal temperature<br />
for the correct operation of the electronic components.<br />
c When a large amount of heat has to be evacuated and a<br />
water cooling installation stable in temperature and flow is<br />
available.<br />
c Particularly suitable for difficult and highly polluted<br />
atmosphere, since there is no outside air circuit.<br />
c Our cooling units can be used in the severest atmospheres,<br />
where the temperature can reach up to 55 ºC.<br />
c Our cooling units feature the temperature adjustment<br />
function, as well as an indication of any anomalies by<br />
means of an alarm.<br />
Resistance heaters are used to heat the electrical switchboard<br />
when the ambient temperature is too low, or to prevent the<br />
formation of condensation water.<br />
Ta > Td Ta > Td Ta < Td<br />
YES<br />
YES<br />
c The inside temperature of the enclosure does not depend on<br />
the outside.<br />
c They do not bring the atmospheres inside and outside the<br />
enclosure into contact.<br />
c It has a leak detection device.<br />
c Even temperature inside the enclosure.<br />
c High protection degree (IP54).<br />
c They use ecological gas.<br />
c Small size.<br />
c Fitted with a PTC-type heating element that stabilises the<br />
surface temperature of the aluminium section.<br />
c In two versions: insulated, with low surface temperature<br />
and in aluminium with a surface temperature below<br />
< 75 ºC.<br />
c The fan-equipped resistance heaters guarantee the<br />
temperature inside the enclosure and prevent hot spots.<br />
c They need cold water.<br />
c They need a specific plumbing installation.<br />
c The installation of a drain is recommended.<br />
c Maintenance is required: filter change.<br />
Air-water exchangers Cooling units Resistance heaters<br />
6/5
<strong>THERMAL</strong> <strong>MANAGEMENT</strong><br />
Selection guide<br />
A thermal solution for every environment<br />
Ventilation systems with filter<br />
Particularly suited for installations in which:<br />
c The temperature expected outside the enclosure may be lower than the<br />
maximum required inside it.<br />
c A high degree of protection must be maintained (IP54/IP55).<br />
c The outside environment is not too dusty.<br />
Broad range of solutions:<br />
c 42 models.<br />
c In RAL-7032 and RAL-7035.<br />
c From 38 to 850 m 3 /h.<br />
c In 5 voltages:<br />
AC: 400/440 V, 230 V, 115 V (50/60 Hz).<br />
DC: 48 V and 24 V.<br />
Air-air exchangers<br />
Particularly suited for installations in which:<br />
c The temperature expected outside the enclosure may be lower than the<br />
maximum required inside it.<br />
c Maintaining good watertightness is important (IP54/IP55).<br />
c The outside environment is highly polluted.<br />
Broad range of solutions:<br />
c 4 models.<br />
c Top- and side-mounting versions.<br />
c Performance from 15 to 70 W.<br />
c Voltage: 230 V (50/60 Hz).<br />
Air-water exchangers<br />
Particularly suited for installations in which:<br />
c The temperature required inside the enclosure must be lower than the<br />
maximum expected outside.<br />
c In corrosive atmospheres, the outside and inside air circuit never come into<br />
contact.<br />
c Very polluted atmospheres, since they are water-cooled and there is no<br />
outside air circuit.<br />
c When the heat needs to be extracted from the confines of the building.<br />
Broad range of solutions:<br />
c 3 models.<br />
c Top- and side-mounting versions.<br />
c Cooling power from 2100 W and 3000 W.<br />
c Voltage: 230 V (50/60 Hz).<br />
6/6
<strong>THERMAL</strong> <strong>MANAGEMENT</strong><br />
Selection guide<br />
Cooling units<br />
They give the equipment installed in the enclosure the temperature it needs<br />
to operate correctly:<br />
Regardless of the outside temperature.<br />
They do not bring the inside and outside air circuit into contact.<br />
They reduce humidity in the enclosure.<br />
Range of solutions:<br />
c 19 models.<br />
c Top- and side-mounting versions.<br />
c Cooling power from 240 up to 3.100 W.<br />
c Tension: 230 V (50/60 Hz); 3 400/440 V (50/60 Hz).<br />
Resistance heaters<br />
With a twofold objective:<br />
c They avoid condensation problems inside the enclosure.<br />
c They guarantee maintenance of the ideal temperature for the correct<br />
operation of the electronic components.<br />
Range of solutions:<br />
c 30 models.<br />
c Insulated or aluminium versions.<br />
c Convection or circulation fan versions.<br />
c Heating power from 10 up to 550 W.<br />
c Tension: from 12 to 450 V AC/DC.<br />
Control devices<br />
Thermostats: they maintain the temperature inside the enclosure and send a<br />
signal when certain defi ned values are exceeded:<br />
c Maximum value (cooling action).<br />
c Minimum value (heating action).<br />
Range of solutions:<br />
c 16 models.<br />
c Two versions: adjustable or preset temperature.<br />
c Hygrostat: relative humidity regulators. They are used together with<br />
resistance heaters or fans.<br />
c Hygrometer: relative humidity control with a double-function device: hygrostat-thermostat.<br />
Calculation assistance software: PROclima<br />
We provide our clients and users with this software to help them select their<br />
temperature control equipment.<br />
The program calculates the thermal balance in the enclosure and suggests<br />
the best ventilation or cooling solution.<br />
6/7
Ventilation systems VF<br />
Wide range of ventilation products<br />
1<br />
2<br />
7<br />
5<br />
9<br />
6<br />
8<br />
4<br />
3<br />
6/8
0.8 mm<br />
2.2<br />
2.3<br />
2.1<br />
4.5 mm<br />
1 Minimum pressure<br />
loss. Better air flow.<br />
The angles of walls, the<br />
tilting of slats, the fixing<br />
distance of the motor<br />
and the sizing of the<br />
unit have been studied<br />
to guarantee the best<br />
possible air conduction<br />
and minimise pressure<br />
loss.<br />
2 Fixing guide (2.1). Exclusive device (patented) that<br />
centres the fan body with the machining carried out<br />
on the enclosure wall. This system corrects possible<br />
defects in sizing and in the precision of machining.<br />
It also facilitates the operation of the “multiple fixing<br />
clips”.<br />
Multiple thickness fixing clips system (2.2). This<br />
exclusive patented device guarantees easy and<br />
reliable fixing of the ventilation system on 0.8 mm<br />
to 4.5 mm thick walls without the need for any other<br />
screws.<br />
It also guarantees a perfect joint compression on the<br />
cut outline. Protection between the grille and the wall<br />
is guaranteed for all materials: steel, stainless steel,<br />
polyester, aluminium, etc.<br />
Tilted profile of the grill (2.3). This innovating profile<br />
increases the protection of the filter against vertical<br />
exposure:<br />
c Each slat is protected by the slat above it.<br />
c The external size remains small.<br />
3 IP54-55.<br />
Designed (patented)<br />
especially to evacuate<br />
any water that might<br />
be retained by the filter<br />
blanket for applications<br />
that may be splashed<br />
under pressure.<br />
4 Wide offer of filters.<br />
c For application in<br />
greasy atmospheres<br />
(OEMs).<br />
c Anti-insect filters.<br />
c Small fine filter (when<br />
greater dust protection<br />
is required).<br />
ENVIRONMENTALLY<br />
friendly<br />
5 Environment.<br />
c Recyclable plastic<br />
materials and filters.<br />
c Motors compliant with<br />
the ROHS legislation.<br />
c Lower electrical<br />
consumption for<br />
greater air flow.<br />
6 Selection of plastic materials.<br />
The materials (ASA/PC) selected give the system:<br />
c Good behaviour (long service life) with regard to<br />
UV rays.<br />
c Excellent mechanical behaviour.<br />
c The colours of the grills in the standard supply are<br />
RAL-7032 and 7035.<br />
c Grill colour can be changed by mould injection<br />
(check with the sales network).<br />
7 Strong, reliable and effortless fixing that is<br />
evident upon installation, made possible by the set of<br />
“guide devices” and the “multiple fixing clips”.<br />
It also allows traditional enclosures to be fixed with<br />
fasteners.<br />
8 Fast replacement of<br />
the filter blanket.<br />
Fast, easy and secure<br />
replacement of the filter<br />
blanket, even with the<br />
fan operating.<br />
Reversibility.<br />
The rotation of the fan<br />
motor can be easily<br />
changed on all models<br />
(extraction/discharge).<br />
9 Motor selection. State-of-the-art motors have been<br />
selected from leading manufacturers in the sector, with<br />
a view to achieving:<br />
c Higher flow rate.<br />
c Longer useful life.<br />
The largest range of voltages is available in the<br />
standard motor selection, both in alternating (50/60 Hz)<br />
and direct current.<br />
Self-extinguishing. Self-extinguishing according to<br />
the UL94 VO regulation.<br />
6/9
<strong>SYSTEMS</strong><br />
Selection guide<br />
VENTILATION <strong>SYSTEMS</strong> WITH FILTER<br />
Free flow<br />
(fan with filter)<br />
Fan + 1 outlet grill<br />
Flow rate (m 3 /h)<br />
Fan + 2 outlet grills<br />
50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz<br />
Voltage<br />
Type of<br />
connection<br />
(*)<br />
Total<br />
(external) (mm)<br />
Dimensions<br />
(mm)<br />
Cut-out<br />
(mm)<br />
38 39 25 26 33 34 230 V C<br />
38 39 27 28 35 36 115 V C<br />
58 39 47 24 DC C<br />
137 117 92 92<br />
44 34 41 48 DC C<br />
85 98 63 72 71 83 230 V F<br />
79 92 65 74 73 79 115 V F<br />
80 57 77 24 DC F<br />
170 150 125 125<br />
79 59 68 48 DC F<br />
165 193 153 171 161 175 230 V F<br />
164 192 153 171 161 174 115 V F<br />
188 171 179 24 DC F<br />
193 171 179 48 DC F<br />
302 350 260 307 268 311 230 V F<br />
268 248 223 223<br />
302 348 263 305 271 314 115 V F<br />
262 221 229 24 DC F<br />
247 210 218 48 DC F<br />
562 586 473 477 481 485 230 V B<br />
582 583 485 475 494 477 115 V B<br />
838 803 718 568 728 585 230 V B<br />
336 316 291 291<br />
983 944 843 642 854 667 115 V B<br />
931 803 798 568 809 585 400/440 V B<br />
(*) C = by cable, F = by connector, B = by terminal block.<br />
NEW Fans with type of connection F include a fan connection cable (L = 2 m)<br />
6/10
Reference<br />
Fan with filter Outlet grille Fan with filter Outlet grille<br />
IP<br />
RAL-7032 RAL-7032 RAL-7035 RAL-7035<br />
VF38<br />
VF38R35<br />
VF38/115<br />
VF38/115R35<br />
FS38<br />
FS38R35 54<br />
VF38/24DC<br />
VF38/24DCR35<br />
VF38/48DC<br />
VF38/48DCR35<br />
VF85<br />
VF85R35<br />
VF85/115<br />
VF85/115R35<br />
FS85<br />
FS85R35 54<br />
VF85/24DC<br />
VF85/24DCR35<br />
VF85/48DC<br />
VF85/48DCR35<br />
VF165<br />
VF165R35<br />
VF165/115<br />
VF165/115R35<br />
VF165/24DC<br />
VF165/24DCR35<br />
VF165/48DC<br />
VF165/48DCR35<br />
FS165<br />
FS165R35 54<br />
VF300<br />
VF300R35<br />
VF300/115<br />
VF300/115R35<br />
VF300/24DC<br />
VF300/24DCR35<br />
VF300/48DC<br />
VF300/48DCR35<br />
VF560<br />
VF560R35<br />
VF560/115<br />
VF560/115R35<br />
VF850<br />
FS560<br />
VF850R35<br />
FS560R35 54<br />
VF850/115<br />
VF850/115R35<br />
VF850/400<br />
VF850/400R35<br />
6/11
VENTILATION <strong>SYSTEMS</strong><br />
Selection guide<br />
OUTLET GRILLES<br />
Reference<br />
Dimensions<br />
(mm)<br />
IP<br />
RAL-7032 RAL-7035 Total (outside) Cut-out<br />
FS38 FS38R35 137 117 92 92 54<br />
FS85 FS85R35 170 150 125 125 54<br />
FS165 FS165R35 268 248 223 223 54<br />
FS560 FS560R35 336 316 291 291 54<br />
VANDAL PROOF SYSTEM<br />
Reference<br />
Dimensions<br />
(mm)<br />
Set of<br />
RAL-7011<br />
ANVF 137 177 2<br />
ANVF 170 150 2<br />
ANVF 268 248 2<br />
ANVF 336 316 2<br />
POWER CONNECTION CABLE FOR FANS<br />
Reference<br />
Length (mm)<br />
CBMV100 1000<br />
CBMV200 2000<br />
FILTERS<br />
Reference Concept For fans and grilles with dimensions (mm)<br />
F38<br />
137 117<br />
F85 Standard filter (G2 class<br />
170 150<br />
F165 conforming to EN 779)<br />
268 248<br />
F560 336 316<br />
F85OEM<br />
170 150<br />
F165OEM “Greasy environments” OEM filter<br />
268 248<br />
F560OEM 336 316<br />
FF85<br />
170 150<br />
FF165<br />
Fine filter (G3 class conforming<br />
to EN 779)<br />
268 248<br />
FF560 336 316<br />
FAIN38<br />
137 117<br />
FAIN85 170 150<br />
“Anti-insect” filters<br />
FAIN165 268 248<br />
FAIN560 336 316<br />
6/12
VENTILATION <strong>SYSTEMS</strong><br />
Selection guide<br />
EMC EXTERNAL KIT IP55<br />
Reference<br />
For fans and grilles with dimensions (mm)<br />
VF85/KITIPCEM 170 150<br />
VF165/KITIPCEM 268 248<br />
VF560/KITIPCEM 336 316<br />
PROTECTION KIT IP55<br />
For grilles and fans<br />
(mm)<br />
Aluzinc<br />
RAL-7032<br />
Aluzinc<br />
RAL-7035<br />
Stainless steel<br />
Replacement<br />
filters<br />
170 150 VF85/KITIPALZ32 VF85/KITIPALZ35 VF85/KITIP F85/KITIP<br />
268 248 VF165/KITIPALZ32 VF165/KITIPALZ35 VF165/KITIP F165/KITIP<br />
336 316 VF560/KITIPALZ32 VF560/KITIPALZ35 VF560/KITIP F560/KITIP<br />
Forced ventilation<br />
The movement of air inside the enclosure with the aid of a fan makes it<br />
possible to:<br />
1<br />
Increase thermal dissipation through the enclosure walls and, as a result,<br />
reduce the inside temperature.<br />
2<br />
Avoid hot spots in the enclosure (even temperature) harmful to some<br />
components.<br />
Natural ventilation<br />
Solution 1<br />
Solution 2<br />
The provision of fresh air from the outside by means of ventilation grills<br />
improves the dissipation of heat by natural convection. However, this<br />
solution is feasible in cases where the power to be dissipated is weak and<br />
in atmospheres with low dust levels. There are 4 ways of ventilating, with a<br />
common principle: entry of cold air through the bottom of the enclosure by<br />
means of an accessory and the exit of hot air through the top of the enclosure<br />
by means of an accessory:<br />
1<br />
By elevating the ceiling of the enclosures (only in Spacial 6000 models) and<br />
adding a fi lterless bottom air inlet (solution 1).<br />
2<br />
By means of a ceiling ventilation device, adding a fi lterless air inlet at the<br />
bottom (solution 1).<br />
3<br />
By means of inlet and outlet grills (fi lterless) (solution 2).<br />
4<br />
By means of ventilation lugs (Solution for insulating enclosures).<br />
6/13
VF<br />
Forced ventilation system<br />
IP54 (EN 60529)<br />
VF38 Fans…<br />
General features:<br />
c The Himel fans are comprised of an axial motor, a protection housing for<br />
the front and rear sides, and a filter for retaining dust particles.<br />
c The filter can even be replaced during operation, without any risk of contact<br />
with the blades or other rotating elements.<br />
c The cut-out template included with the standard supply avoids drawing and<br />
protects the enclosure surface from the risk of scratches during handling.<br />
Conditions of use:<br />
c The outside temperature Te should be 5 °C below the temperature required<br />
Ts in the enclosure.<br />
c The filters the fans are equipped with must be cleaned or replaced<br />
periodically.<br />
c The environment should be relatively “clean” and over-frequent filter<br />
replacement should be avoided.<br />
c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />
or single opening) must be taken into consideration to determine ventilation<br />
flow.<br />
Characteristics<br />
Reference<br />
Colour RAL-7032 VF38 VF38/115 VF38/24DC VF38/48DC<br />
Colour RAL-7035 VF38R35 VF38/115R35 VF38/24DCR35 VF38/48DCR35<br />
Flow rate with filter (m 3 /h) (50/60 Hz) 38/39 38/39 58 44<br />
Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 25/26 27/28 39 34<br />
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />
Voltage range 150...250 V 75...125 V 10...27.6 V 24...55 V<br />
Absorbed power (50/60 Hz) 4.5/4.8 W 3.3/3.5 W 3.6 W 4.6 W<br />
Intensity max. (50/60 Hz) 0.16/0.17 A 0.16/0.16 A 0.18 A 0.074 A<br />
Noise level<br />
40/41 dB (A)<br />
Bearing<br />
Balls<br />
IP Degree of protection (with standard filter) 54<br />
External dimensions (mm) 137 117 49<br />
Cut-out dimensions (mm) 92 92<br />
Weight 0.220 kg 0.230 kg<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –10 a +70 °C –10 a +70 °C<br />
Storage temperature –40 a +70 °C<br />
100% operating factor 100%<br />
Maximum static pressure (0 m 3 /h airflow)<br />
20 Pa<br />
Outlet grilles<br />
Characteristics<br />
Reference<br />
Colour RAL-7032<br />
FS38<br />
Colour RAL-7035<br />
FS38R35<br />
Degree of protection IP54 54<br />
External dimensions (mm)<br />
137 117 18<br />
(height length depth)<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Operating temperature –20 a +70 °C<br />
Replacement filter<br />
Characteristics<br />
Standard filter (G2 class conforming to EN 779)<br />
Reference<br />
F38<br />
6/14
VF<br />
Forced ventilation system<br />
IP54 (EN 60529)<br />
Dimensions (mm)<br />
FIG. 1<br />
Fans VF38-VF38/115<br />
13<br />
137<br />
91.85<br />
80<br />
92 92<br />
117 49 9<br />
FIG. 2<br />
“Pressure/Flow” Diagram<br />
Pa<br />
VF38<br />
Difference in static pressure (SP)<br />
Flow rate m 3 /h<br />
6/15
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
VF85 Fans…<br />
General features:<br />
c The Himel fans are comprised of an axial motor, a protection housing for<br />
the front and rear sides, and a filter for retaining powder particles.<br />
c The filter can even be replaced during operation, without any risk of contact<br />
with the blades or other rotating elements.<br />
c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />
protection for dust-sensitive installations.<br />
c The cut-out template included with the standard supply avoids drawing and<br />
protects the enclosure surface from the risk of scratches during handling.<br />
Conditions of use:<br />
c The outside temperature Te should be 5 °C below the temperature required<br />
Ts in the enclosure.<br />
c The filters the fans are equipped with must be cleaned or replaced<br />
periodically.<br />
c The environment should be relatively “clean” and over-frequent filter<br />
replacement should be avoided.<br />
c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />
or single opening) must be taken into consideration to determine ventilation<br />
flow.<br />
Characteristics<br />
Reference<br />
Colour RAL-7032 VF85 VF85/115 VF85/24DC VF85/48DC<br />
Colour RAL-7035 VF85R35 VF85/115R35 VF85/24DCR35 VF85/48DCR35<br />
Flow rate with filter (m 3 /h) (50/60 Hz) 85/98 79/92 80<br />
Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 63/72 65/74 60<br />
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />
Voltage range 175...253 V 75...126 V 10...27.6 V 25...55.2 V<br />
Absorbed power (50/60 Hz) 17/15 W 16/15 W 7.6 W 8 W<br />
Intensity max. (50/60 Hz) 0.12/0.097 A 0.21/0.179 A 0.30 A 0.173 A<br />
Noise level<br />
46/49 dB (A)<br />
Bearing<br />
Balls<br />
IP Degree of protection (with standard filter) 54<br />
External dimensions (mm) 170 150 62<br />
Cut-out dimensions (mm) 125 125<br />
Weight 0.780 kg 0.480 kg<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –20 a +60 °C –10 a +70 °C<br />
Storage temperature –40 a +70 °C<br />
100% operating factor 100%<br />
Maximum static pressure (0 m 3 /h airflow)<br />
50 Pa<br />
Outlet grills<br />
Characteristics<br />
Reference<br />
Colour RAL-7032<br />
FS85<br />
Colour RAL-7035<br />
FS85R35<br />
IP 54<br />
Outside dimensions (mm)<br />
170 150 18<br />
(height width depth)<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –20 a +70 °C<br />
Replacement filter<br />
Characteristics<br />
Standard filter (filtration capacity: G2 conforming to EN 779)<br />
OEM filter (oily environment)<br />
Fine filter<br />
Anti-insect filter<br />
Reference<br />
F85<br />
F85OEM<br />
FF85<br />
FAIN85<br />
6/16
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
Dimensions (mm)<br />
FIG. 1<br />
Fans<br />
15<br />
170<br />
124.85<br />
119<br />
125 x 125<br />
150<br />
62<br />
9<br />
FIG. 2<br />
“Pressure/Flow” Diagram<br />
Pa<br />
VF85<br />
Difference in static pressure (SP)<br />
Flow rate m 3 /h<br />
6/17
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
VF165 Fans…<br />
General features:<br />
c The Himel fans are comprised of an axial motor, a protection housing for<br />
the front and rear sides, and a filter for retaining powder particles.<br />
c The filter can even be replaced during operation, without any risk of contact<br />
with the blades or other rotating elements.<br />
c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />
protection for dust-sensitive installations.<br />
c The cut-out template included with the standard supply avoids drawing and<br />
protects the enclosure surface from the risk of scratches during handling.<br />
Conditions of use:<br />
c The outside temperature Te should be 5 °C below the temperature required<br />
Ts in the enclosure.<br />
c The filters the fans are equipped with must be cleaned or replaced<br />
periodically.<br />
c The environment should be relatively “clean” and over-frequent filter<br />
replacement should be avoided.<br />
c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />
or single opening) must be taken into consideration to determine ventilation<br />
flow.<br />
Characteristics<br />
Reference<br />
Colour RAL-7032 VF165 VF165/115 VF165/24DC VF165/48DC<br />
Colour RAL-7035 VF165R35 VF165/115R35 VF165/24DCR35 VF165/48DCR35<br />
Flow rate with filter (m 3 /h) (50/60 Hz) 165/193 190<br />
Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 153/171 171<br />
Flow rate with 2 outlet grills (m 3 /h) (50/60 Hz) 161/175 179<br />
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />
Voltage range 175...253 V 75...126 V 10...27.6 V 25...55.2 V<br />
Absorbed power (50/60 Hz) 16.3/14.3 W 15.5/14.4 W 8 W 8.7 W<br />
Intensity max. (50/60 Hz) 0.12 A/0.94 A 0.20 A/0.18 A 0.3 A 0.18 A<br />
Noise level<br />
50/51 dB (A)<br />
Bearing<br />
Balls<br />
IP Degree of protection (with standard filter) 54<br />
External dimensions (mm) 268 248 104<br />
Cut-out dimensions (mm) 223 223<br />
Weight 1.140 kg 0.810 kg<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –20 a +60 °C –10 a +70 °C<br />
Storage temperature –40 a +70 °C<br />
100% operating factor 100%<br />
Maximum static pressure (0 m 3 /h airflow)<br />
50 Pa<br />
Outlet grills<br />
Characteristics<br />
Reference<br />
Colour RAL-7032<br />
FS165<br />
Colour RAL-7035<br />
FS165R35<br />
IP 54<br />
Outside dimensions (mm)<br />
268 248 18<br />
(height width depth)<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –20 a +70 °C<br />
Replacement filter<br />
Characteristics<br />
Standard filter (filtration capacity: G2 conforming to EN 779)<br />
OEM filter (oily environment)<br />
Fine filter<br />
Anti-insect filter<br />
Reference<br />
F165<br />
F165OEM<br />
FF165<br />
FAIN165<br />
6/18
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
Dimensions (mm)<br />
FIG. 1<br />
Fans VF165-VF165/115<br />
18<br />
268<br />
222.7<br />
119<br />
223 x 223<br />
248<br />
104<br />
9.5<br />
FIG. 2<br />
“Pressure/Flow” Diagram<br />
Pa<br />
VF165<br />
Difference in static pressure (SP)<br />
Flow rate<br />
(m 3 /h)<br />
6/19
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
VF300 Fans…<br />
General features:<br />
c The Himel fans are comprised of an axial motor, a protection housing for<br />
the front and rear sides, and a filter for retaining powder particles.<br />
c The filter can even be replaced during operation, without any risk of contact<br />
with the blades or other rotating elements.<br />
c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />
protection for dust-sensitive installations.<br />
c The cut-out template included with the standard supply avoids drawing and<br />
protects the enclosure surface from the risk of scratches during handling.<br />
Conditions of use:<br />
c The outside temperature Te should be 5 °C below the temperature required<br />
Ts in the enclosure.<br />
c The filters the fans are equipped with must be cleaned or replaced<br />
periodically.<br />
c The environment should be relatively “clean” and over-frequent filter<br />
replacement should be avoided.<br />
c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />
or single opening) must be taken into consideration to determine ventilation<br />
flow.<br />
Characteristics<br />
Reference<br />
Colour RAL-7032 VF300 VF300/115 VF300/24DC VF300/48DC<br />
Colour RAL-7035 VF300R35 VF300/115R35 VF300/24DCR35 VF300/48DCR35<br />
Flow rate with filter (m 3 /h) (50/60 Hz) 300/350 262<br />
Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 260/307 221<br />
Flow rate with 2 outlet grills (m 3 /h) (50/60 Hz) 268/311 229<br />
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />
Voltage range 145...253 V 75...126 V 12...30 V 25...60 V<br />
Absorbed power (50/60 Hz) 36/37 W 36/36 W 13 W 11 W<br />
Intensity max. (50/60 Hz) 0.17/0.16 A 0.35/0.32 A 0.53 A 0.24 A<br />
Noise level<br />
55/56 dB (A)<br />
Bearing<br />
Balls<br />
IP Degree of protection (with standard filter) 54<br />
External dimensions (mm) 268 248 116 268 248 103,4<br />
Cut-out dimensions (mm) 223 223<br />
Weight 1.3 kg 1.1 kg<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –10 a +70 °C –10 a +70 °C<br />
Storage temperature –40 a +70 °C<br />
100% operating factor 100%<br />
Maximum static pressure (0 m 3 /h airflow)<br />
158 Pa<br />
Outlet grills<br />
Characteristics<br />
Reference<br />
Colour RAL-7032<br />
FS165<br />
Colour RAL-7035<br />
FS165R35<br />
IP 54<br />
Outside dimensions (mm)<br />
268 248 18<br />
(height width depth)<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –20 a +70 °C<br />
Replacement filter<br />
Characteristics<br />
Standard filter (filtration capacity: G2 conforming to EN 779)<br />
OEM filter (oily environment)<br />
Fine filter<br />
Anti-insect filter<br />
Reference<br />
F165<br />
F165OEM<br />
FF165<br />
FAIN165<br />
6/20
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
Dimensions (mm)<br />
FIG. 1<br />
Fans VF300-VF300/115<br />
18<br />
268<br />
222.7<br />
172<br />
223 x 223<br />
248<br />
116<br />
9.5<br />
FIG. 2<br />
“Pressure/Flow” Diagram<br />
Pa<br />
VF300<br />
Difference in static pressure (SP)<br />
Flow rate m 3 /h<br />
6/21
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
VF560... and VF850... Fans<br />
General features:<br />
c The Himel fans are comprised of an axial motor, a protection housing for<br />
the front and rear sides, and a filter for retaining powder particles.<br />
c The filter can even be replaced during operation, without any risk of contact<br />
with the blades or other rotating elements.<br />
c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />
protection for dust-sensitive installations.<br />
c The cut-out template included with the standard supply avoids drawing and<br />
protects the enclosure surface from the risk of scratches during handling.<br />
Conditions of use:<br />
c The outside temperature Te should be 5 °C below the temperature required<br />
Ts in the enclosure.<br />
c The filters the fans are equipped with must be cleaned or replaced<br />
periodically.<br />
c The environment should be relatively “clean” and over-frequent filter<br />
replacement should be avoided.<br />
c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />
or single opening) must be taken into consideration to determine ventilation<br />
flow.<br />
Characteristics<br />
Reference<br />
Colour RAL-7032 VF560 VF560/115 VF850 VF850/115 VF850/400<br />
Colour RAL-7035 VF560R35 VF560/115R35 VF850R35 VF850/115R35 VF850/400R35<br />
Flow rate with filter (m 3 /h) (50/60 Hz) 562/586<br />
838 (50 Hz)<br />
983 (50 Hz)<br />
931 (50 Hz)<br />
803 (60 Hz)<br />
944 (60 Hz)<br />
803 (60 Hz)<br />
Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 473/477<br />
718 (50 Hz)<br />
843 (50 Hz)<br />
798 (50 Hz)<br />
568 (60 Hz)<br />
642 (60 Hz)<br />
568 (60 Hz)<br />
Flow rate with 2 outlet grills (m 3 /h) (50/60 Hz) 481/485<br />
728 (50 Hz)<br />
854 (50 Hz)<br />
809 (50 Hz)<br />
585 (60 Hz)<br />
667 (60 Hz)<br />
585 (60 Hz)<br />
Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 230 V (50/60 Hz) 115 V (50/60 Hz) 400 V (50/60 Hz)<br />
Voltage range 207...244 V 103...122 V 207...244 V 103...122 V 396...466 V<br />
Absorbed power (50/60 Hz) 68/85 W 65/83 W 150/195 W 145/182 W 40/40 W<br />
Intensity max. (50/60 Hz) 0.52/0.37 A 0.60/0.72 A 0.65/0.85 A 0.13/1.6 A 0.22/0.23 A<br />
Noise level 59/59 dB (A) 76/75 dB (A) 78/77 dB (A) 77/75 dB (A)<br />
Bearing<br />
Balls<br />
IP Degree of protection (with standard filter) 54<br />
External dimensions (mm) 336 316 161 336 316 162<br />
Cut-out dimensions (mm) 291 291<br />
Weight 3.2 kg 4.1 kg<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –15 a +60 °C<br />
Storage temperature –40 a +50 °C<br />
100% operating factor 100%<br />
Maximum static pressure (0 m 3 /h airflow) 140 Pa 170 Pa<br />
Outlet grills<br />
Characteristics<br />
Reference<br />
Colour RAL-7032<br />
FS560<br />
Colour RAL-7035<br />
FS560R35<br />
IP 54<br />
Outside dimensions (mm) (height width depth) 336 316 18<br />
Material<br />
Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />
Service temperature –20 a +70 °C<br />
Replacement filter<br />
Characteristics<br />
Standard filter (filtration capacity: G2 conforming to EN 779)<br />
OEM filter (oily environment)<br />
Fine filter<br />
Anti-insect filter<br />
Reference<br />
F560<br />
F560OEM<br />
FF560<br />
FAIN560<br />
6/22
VF<br />
Forced ventilation system<br />
IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />
Dimensions (mm)<br />
FIG. 1<br />
VF560-VF560/115 Fans<br />
18<br />
336<br />
290.7<br />
225<br />
291 x 291<br />
291 291<br />
316<br />
160.5<br />
9.5<br />
FIG. 2<br />
VF650-VF650/115 Fans<br />
18<br />
336<br />
290.7<br />
280<br />
291 x 291<br />
316<br />
162<br />
9.5<br />
FIG. 3<br />
FIG. 4<br />
“Pressure/Flow” Diagram<br />
Pa<br />
VF560<br />
Pa<br />
VF850<br />
Difference in static pressure (Pa)<br />
Difference in static pressure (Pa)<br />
Flow rate m 3 /h<br />
Flow rate m 3 /h<br />
6/23
VF<br />
Accessories for forced and natural ventilation systems<br />
Circulation fan<br />
c To circulate the air inside the enclosures.<br />
c Fixing with screws.<br />
c User protection according to DIN 31001.<br />
Reference<br />
Flow rate<br />
(m 3 /h)<br />
Tension<br />
<strong>Electric</strong>al<br />
power (W)<br />
Weight<br />
(kg)<br />
VC150 150 230 V 50 Hz 17 0.82<br />
IP20 Fans<br />
c For uses where a high degree of protection is not required (IP20).<br />
c Self-extinguishing thermoplastic grille with a black fi nish.<br />
c Fixing to the enclosure with four M4 screws.<br />
Reference<br />
Flow rate<br />
(m 3 /h)<br />
Tension<br />
<strong>Electric</strong>al power (W)<br />
Weight<br />
(kg)<br />
Dimensions<br />
(mm)<br />
Outlet grilles<br />
Standard filter<br />
V65 65 230 V - 50 Hz 17 0.69 124 124 55 FS65 F65<br />
V65/115 65 115 V - 50 Hz 17 0.69 124 124 55 FS65 F65<br />
EMC external kit IP55<br />
c They are directly mounted onto the fans and grilles to protect the<br />
equipment from electromagnetic interference.<br />
Reference<br />
For fans and grilles with dimensions (mm)<br />
VF85/KITIPCEM 170 150<br />
VF165/KITIPCEM 268 248<br />
VF560/KITIPCEM 336 316<br />
6/24
VF<br />
Accessories for forced and natural ventilation systems<br />
Fans for 19” racks<br />
c Height: 1 U.<br />
c Connection cable.<br />
References:<br />
CBMV100 (L = 1 m).<br />
CBMV200 (L = 2 m).<br />
Reference<br />
Specifications<br />
Flow rate*<br />
(m 3 /h)<br />
Noise dB (A)<br />
Tension<br />
(V/Hz)<br />
<strong>Electric</strong>al power<br />
(W)<br />
VR312<br />
With 3 fans with a depth of 180 mm<br />
With thermostat and indicator light<br />
312 50 230/50-60 34<br />
VR400 With 3 fans with a depth of 180 mm 400 50 230/50-60 36<br />
VR624<br />
With 3 fans with a depth of 180 mm<br />
With thermostat and indicator light<br />
624 50 230/50-60 68<br />
VR800 With 6 fans with a depth of 310 mm 800 52 230/50-61 72<br />
VR1200 With 9 fans with a depth of 445 mm 1200 55 230/50-62 108<br />
*Flow measured without counter-pressure.<br />
19” 2 U tangential fan<br />
c Fan with air drawn in from the front and vertically channelled through the<br />
19” rack.<br />
c Height: 2 U.<br />
Reference<br />
Flow rate (m 3 /h)<br />
Noise<br />
dB (A)<br />
Tension (V/Hz)<br />
<strong>Electric</strong>al power<br />
(W)<br />
VTR300 300 53 230/50-60 37<br />
6/25
VF<br />
Accessories for forced and natural ventilation systems<br />
Fans<br />
c Turbine-type fan motor for ventilation/extraction.<br />
Ventilation filters<br />
c Outlet fi lter unit for enclosure ventilation. For fi tting to MV fans.<br />
Protective grille<br />
c Protective grille for enclosure fan motors. For fi tting to MV fans.<br />
Power connection cable for fans<br />
c For fi tting to the connection terminal of the fan motors.<br />
References:<br />
CBMV100 (L = 1 m).<br />
CBMV200 (L = 2 m).<br />
Reference<br />
Flow<br />
(m 3 /h)<br />
Tension<br />
(V/Hz)<br />
Power absorbed<br />
(W)<br />
Noise<br />
(dB) (A)<br />
External dimensions<br />
(mm)<br />
MV156 156 230/50-60 17/15 42 120 120 38 FS156 RV156<br />
MV156/115 156 120/50-60 17/15 42 120 120 38 FS156 RV156<br />
MV35 35 230/50-60 16/14 32 80 80 25 FS35 RV35<br />
MV35/115 35 120/50-60 16/14 32 80 80 25 FS35 RV35<br />
Filter<br />
Grille<br />
6/26
VF<br />
Accessories for forced and natural ventilation systems<br />
Ceiling ventilation<br />
c Ventilation accessories to be mounted on the top of OLN enclosures..<br />
VMT340<br />
VFT400<br />
340 90 6<br />
270<br />
68 22<br />
340<br />
270<br />
90 6<br />
68 22<br />
190<br />
ø7<br />
270<br />
340<br />
290.5<br />
270<br />
270<br />
340<br />
290.5<br />
6<br />
270<br />
228<br />
6<br />
228<br />
External dimensions (mm)<br />
Reference Description Height Width Depth Flow rate (m 3 /h) Tension (V/Hz) <strong>Electric</strong>al power (W)<br />
VMT340 Natural airing device 93 340 340 - - -<br />
VFT400<br />
Forced ventilation device<br />
(supplied with electric fan)<br />
90 340 340 400 230/50-60 85<br />
6/27
VF<br />
Accessories for forced and natural ventilation systems<br />
Outlet grilles with filter IP54<br />
c Injected thermoplastic, self-extinguishing, conforming to UL94 V0.<br />
c Operating temperature from –10 to +60 °C.<br />
c IP55 with IP55 watertightness protection kit.<br />
Reference<br />
Dimensions<br />
(mm)<br />
RAL-7032 RAL-7035 Total (exterior) Machined<br />
FS38 FS38R35 137 117 92 92<br />
FS85 FS85R35 170 150 125 125<br />
FS165 FS165R35 268 248 223 223<br />
FS560 FS560R35 336 316 291 291<br />
VANDAL PROOF SYSTEM<br />
Reference<br />
Dimensions<br />
(mm)<br />
Set of<br />
RAL-7011<br />
ANVF 137 177 2<br />
ANVF 170 150 2<br />
ANVF 268 248 2<br />
ANVF 336 316 2<br />
POWER CONNECTION CABLE FOR FANS<br />
Reference<br />
Length (mm)<br />
CBMV100 1000<br />
CBMV200 2000<br />
Filters<br />
Reference Concept For fans and grilles with dimensions (mm)<br />
F38<br />
137 117<br />
F85 Standard filter (G2 class<br />
170 150<br />
F165 conforming to EN 779)<br />
268 248<br />
F560 336 316<br />
F85OEM<br />
170 150<br />
F165OEM “Greasy environments” OEM filter<br />
268 248<br />
F560OEM 336 316<br />
FF85<br />
170 150<br />
Fine filter (G3 class conforming<br />
FF165 268 248<br />
to EN 779)<br />
FF560 336 316<br />
FAIN38<br />
137 117<br />
FAIN85 170 150<br />
“Anti-insect” filters<br />
FAIN165 268 248<br />
FAIN560 336 316<br />
Protection kit IP55<br />
For grilles and fans<br />
(mm)<br />
Aluzinc<br />
RAL-7032<br />
Aluzinc<br />
RAL-7035<br />
Stainless steel<br />
Replacement<br />
filter<br />
170 150 VF85/KITIPALZ32 VF85/KITIPALZ35 VF85/KITIP F85/KITIP<br />
268 248 VF165/KITIPALZ32 VF165/KITIPALZ35 VF165/KITIP F165/KITIP<br />
336 316 VF560/KITIPALZ32 VF560/KITIPALZ35 VF560/KITIP F560/KITIP<br />
6/28
VF<br />
Accessories for forced and natural ventilation systems<br />
Lifting screws<br />
c Lifting screws for the top of the OLN enclosures<br />
to improve ventilation<br />
c Reference: VET12.<br />
Ventilation devices<br />
c To connect the inside of the enclosure with the exterior atmosphere and<br />
prevent condensation. Can be fixed onto the outside (references VM25<br />
and VN27) or onto the internal sides connected with the rear self-ventilating<br />
windows of the POLYMEL enclosures (reference VM35).<br />
Reference<br />
Specifications<br />
VM25 For coupling to the exterior of all polyester enclosures<br />
VM25<br />
VM27<br />
VM27 For coupling to the exterior of all polyester enclosures<br />
VM35 For coupling to the interior of POLYMEL enclosures<br />
VM35<br />
Ventilation slots<br />
c Natural ventilation. Guarantee air circulation inside the enclosure.<br />
Texturised RAL-7032 colour<br />
F<br />
A<br />
F<br />
C<br />
= =<br />
B<br />
Ø5.3<br />
D<br />
E<br />
Reference A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)<br />
TR1 144 62 36 110 - -<br />
TR2 208 90 72 94 190 -<br />
TR3 244 90 72 130 226 -<br />
TR4 345 118 100 231 237 115.5<br />
TR5 345 148 130 231 327 115.5<br />
TR6 445 148 130 297 427 148.5<br />
6/29
Air/air exchangers<br />
In details<br />
1<br />
2<br />
5<br />
4<br />
3<br />
AIR/AIR EXCHANGERS<br />
Reference Performance Voltage Mounting<br />
Dimensions (mm)<br />
Height Width Depth<br />
Integrated<br />
thermostat<br />
ICL15AI 15 W/°K 230 V 50/60 Hz Side 700 270 144 Yes<br />
ICL35AI 35 W/°K 230 V 50/60 Hz Side 780 325 144 Yes<br />
ICL35AILC 35 W/°K 230 V 50/60 Hz Side 780 325 144 No<br />
ICL35AIN 35 W/°K 230 V 50/60 Hz Side 780 325 144 Yes<br />
ICL60AI 70 W/°K 230 V 50/60 Hz Side 1480 450 144 Yes<br />
ICT50AI 50 W/°K 230 V 50/60 Hz Top 340 600 360 Yes<br />
See the accessories on pages 6/33 and 6/35.<br />
6/30
1 Available in two<br />
versions:<br />
c Side-mounting.<br />
c Top-mounting.<br />
Performance from 15 to<br />
70 W/°K that allows you<br />
to install the equipment<br />
best suited to your needs<br />
in each case.<br />
2 The exchangers<br />
come equipped with an<br />
adjustable thermostat<br />
that controls the interior<br />
temperature of the<br />
enclosure:<br />
c An auxiliary control<br />
thermostat does not<br />
need to be installed.<br />
c It guarantees the<br />
correct reading of the<br />
interior temperature of<br />
the enclosure.<br />
Temperature control range<br />
from +20 to +50 ºC.<br />
3 The air-air exchangers<br />
do not need inlet filters,<br />
thus reducing periodic<br />
maintenance.<br />
4 The interior and<br />
exterior air circuits are<br />
perfectly separated<br />
and maintain the IP54<br />
watertightness of the<br />
enclosure.<br />
Two fans guarantee air<br />
circulation in each of the<br />
circuits:<br />
c Circulation fan for air<br />
inside the enclosure.<br />
The internal circuit fan<br />
is always on, thereby<br />
maintaining a uniform<br />
temperature inside<br />
the enclosure and<br />
preventing hot spots.<br />
c Circulation fan<br />
for air outside the<br />
enclosure.<br />
The interior thermostat<br />
controls the fan and<br />
starts it when the<br />
temperature of the air<br />
inside the enclosure<br />
is above the required<br />
temperature.<br />
5<br />
c Fast access to<br />
the interior makes<br />
unit cleaning and<br />
maintenance easy.<br />
c The special<br />
configuration of the<br />
exchange battery<br />
makes it easy to clean.<br />
The spaces between<br />
the slats make it<br />
possible to access<br />
the inside aluminium<br />
walls for easy and fast<br />
cleaning.<br />
6/31
ICT / ICL / AI<br />
Air/air exchangers<br />
Side-mounting<br />
General features:<br />
c Main components: thermostatic adjustment system, exchange battery,<br />
circulation<br />
c The temperature required in the enclosure may be adjusted from +25 ºC to<br />
+50 ºC.<br />
c The interior and exterior air circuits are perfectly separated (IP54). Two fans<br />
guarantee air circulation in each one of the circuits; the inside circuit (that<br />
moves the enclosure air) is permanently on, which makes it possible to<br />
avoid hot spots in the electric circuits or the components.<br />
c The equipment is delivered with a drilling template, an installation guide,<br />
and a water and air-tightness gasket to be inserted between the exchanger<br />
and the enclosure.<br />
Conditions of use:<br />
c The exchangers can only be used when the outside temperature is 5 °C<br />
below the temperature required inside the enclosure.<br />
c The enclosure should be airtight to avoid the penetration of outside air<br />
(IP54 minimum).<br />
Reference<br />
ICL15AI ICL35AI ICL35AILC<br />
ICL35AIN<br />
(internal mounting)<br />
ICL60AI<br />
Cooling specifications<br />
Specific power (1) 15 W/°K 35 W/°K 35 W/°K 35 W/°K 70 W/°K<br />
Exterior circuit airflow 200 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h<br />
Inside circuit airflow 200 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h<br />
Exchange surface 1.23 m 2 1.5 m 2 1.5 m 2 1.5 m 2 6.6 m 2<br />
Adjustment Yes Yes No Yes Yes<br />
Type Thermostatic Thermostatic - Thermostatic Thermostatic<br />
Temperature control range 25-50 °C 25-50 °C - 25-50 °C 25-50 °C<br />
Nature of the fluid Air Air Thermostatic Air Air<br />
<strong>Electric</strong>al specifications<br />
Power supply voltage 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz<br />
Start-up/rated intensity 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A<br />
<strong>Electric</strong>al power absorbed 150 W 150 W 150 W 150 W 150 W<br />
Physical features<br />
External dimensions<br />
A B C (mm)<br />
700 270 144 780 325 144 780 325 144 780 325 144 1480 450 144<br />
Internal IP circuit IP54 IP54 IP54 IP54 IP54<br />
External IP circuit IP22 IP22 IP22 IP22 IP22<br />
Weight 12 kg 15 kg 15 kg 15 kg 35 kg<br />
Noise level 64 dB (A) 64 dB (A) 64 dB (A) 64 dB (A) 64 dB (A)<br />
(1) Power in W is obtained by formula: specifi c power temperature difference between interior and exterior of enclosure.<br />
Example: for exchanger ref. ICL35AI for a difference of 10 °C, the system power is 35 10 = 350 W.<br />
6/32
ICT / ICL / AI<br />
Air/air exchangers<br />
Dimensions (mm)<br />
FIG. 1<br />
External mounting<br />
FIG. 2<br />
Internal mounting<br />
I<br />
=<br />
J<br />
=<br />
I<br />
B<br />
E<br />
F<br />
K<br />
G<br />
E<br />
A<br />
80<br />
136<br />
D<br />
G<br />
H<br />
= =<br />
(1)<br />
A<br />
80<br />
D<br />
136<br />
H<br />
= =<br />
26<br />
144<br />
(C)<br />
K<br />
ø 30<br />
B<br />
25<br />
25<br />
(1)<br />
144<br />
28 (C) 26<br />
J<br />
F<br />
(1) Filter grilles.<br />
Ref.: RPF (not included in the standard supply).<br />
ICL15AI<br />
ICL35AI<br />
ICL35AILC<br />
ICL35AIN<br />
ICL60AI<br />
A 700 780 1480<br />
B 270 325 450<br />
C 144 144 144<br />
D 220 294 420<br />
E 167 183.5 183.5<br />
F 82 77.5 77.5<br />
G 13 35.5 35.5<br />
H 366 413 1113<br />
I 226 266 393<br />
J 40 52 115<br />
K 4 8 Ø 4 8 Ø 6 8 Ø<br />
Accessories (side mounting)<br />
c Optional grille to mount the exchangers inside the enclosure.<br />
Reference<br />
For mounting with the exchanger<br />
RPF15AI ICL15AI<br />
RPF35AI ICL35AI/ICL35AILC<br />
RPF70AI ICL60AI<br />
Installation (internal mounting)<br />
6/33
ICT / ICL / AI<br />
Air/air exchangers<br />
Top mounting<br />
General features:<br />
c Main components: thermostatic adjustment system, exchange battery,<br />
circulation fans for air from the inside and outside circuits.<br />
c The temperature required in the enclosure may be adjusted from +25 ºC to<br />
+50 ºC.<br />
c The interior and exterior air circuits are perfectly separated (IP54). Two fans<br />
guarantee air circulation in each one of the circuits; the inside circuit (that<br />
moves the enclosure air) is permanently on, which makes it possible to<br />
avoid hot spots in the electric circuits or the components.<br />
ICT50AI<br />
c The equipment is delivered with a drilling template, an installation guide,<br />
and a water and air-tightness gasket to be inserted between the exchanger<br />
and the enclosure.<br />
Conditions of use:<br />
c The exchangers can only be used when the outside temperature is 5 °C<br />
below the temperature required inside the enclosure.<br />
c The enclosure should be airtight to avoid the penetration of outside air.<br />
Reference<br />
ICT50AI<br />
Cooling specifications<br />
Specific power (1)<br />
50 W/°K<br />
Exterior circuit airflow 450 m 3 /h<br />
Interior circuit airflow 450 m 3 /h<br />
Exchange surface 3.3 m 2<br />
Adjustment<br />
Yes<br />
Type<br />
Thermostatic<br />
Temperature control range 20-50 °C<br />
Nature of the fluid Air<br />
<strong>Electric</strong>al specifications<br />
Power supply voltage<br />
230 V 50/60 Hz<br />
Start-up/rated intensity 2.1/0.7 A<br />
<strong>Electric</strong>al power absorbed<br />
150 W<br />
Physical features<br />
External dimensions A B C (mm) 390 600 365<br />
Internal IP circuit<br />
IP54<br />
External IP circuit<br />
IP22<br />
Weight<br />
19 kg<br />
Noise level<br />
64 dB (A)<br />
(1) Power in W is obtained by formula: specifi c power temperature difference between inferior and exterior of enclosure.<br />
6/34
ICT / ICL / AI<br />
Air/air exchangers<br />
Dimensions (mm)<br />
FIG. 1<br />
Top mounting: dimensions<br />
600 26<br />
360<br />
340<br />
115 370<br />
300<br />
ø 8<br />
290<br />
360<br />
20<br />
70 310 70<br />
600<br />
Accessories (top mounting)<br />
c Intermediate frame for coupling the MMI64 exchanger to the 600 mm wide<br />
and 400 mm deep enclosures.<br />
c Ref. MMI64.<br />
26<br />
360<br />
Frame MMI64<br />
6/35
Air/water exchangers<br />
In details<br />
1<br />
2<br />
5<br />
3<br />
4<br />
AIR/WATER EXCHANGERS<br />
References<br />
Cooling power L35/W<br />
10/200 l/h<br />
Voltage<br />
Dimensions (mm)<br />
Height Width Depth<br />
Mounting<br />
ICL1800AG 1800 W 230 V 50/60 Hz 830 360 113 Side<br />
ICT1800AG 1800 W 230 V 50/60 Hz 310 600 365 Top<br />
6/36
Maximum Safety<br />
1 Available in two<br />
versions: Top and side<br />
mounting.<br />
2 The exchangers<br />
come with an adjustable<br />
thermostat that controls<br />
the inside temperature of<br />
the enclosure:<br />
c It avoids the installation<br />
of an auxiliary control<br />
thermostat.<br />
c It guarantees the<br />
correct reading of the<br />
inside temperature of the<br />
enclosure.<br />
Temperature adjustment<br />
range: +20 to +50 ºC.<br />
ANTI-LEAK<br />
detection system<br />
3 It has an electricallyoperated<br />
valve in the<br />
water inlet which,<br />
controlled by the<br />
thermostat, adjusts<br />
temperature and avoids<br />
possible condensation.<br />
It has an anti-leak<br />
detection system that<br />
cuts off the water supply<br />
if it detects a loss in the<br />
circuit.<br />
4 The IP54<br />
watertightness is<br />
guaranteed.<br />
The recirculation fan<br />
of the enclosure inside<br />
air is on permanently,<br />
which maintains an<br />
even temperature inside<br />
the enclosure and thus<br />
avoids the appearance of<br />
hot spots.<br />
5 Comfortable and easy to assemble and<br />
disassemble. Fast access to the inside makes for easy<br />
cleaning and maintenance of the unit.<br />
Because it is water cooled, there is no outside air<br />
circuit, and no filters are needed, thus reducing<br />
periodical maintenance.<br />
6/37
ICT / ICL / AG<br />
Air/water exchangers<br />
Top and side mounting<br />
General features:<br />
c Main components: control system, exchange cassette, circulation fans for<br />
internal circuit.<br />
c The temperature required in the enclosure can be controlled within a range of<br />
+25 to +50 ºC.<br />
c The alarm which detects an interruption in the water circuit triggers closing<br />
of an N/O contact. This contact can be used to actuate a pilot light or<br />
siren, or it can be connected to a PLC input. In the event of the alarm being<br />
triggered, the water supply is automatically cut off.<br />
c System to evacuate condensation water to the outside.<br />
Conditions of use:<br />
c The air-water exchangers can be used even if the external temperature is<br />
superior to the temperature required within the enclosure.<br />
c The enclosure should be airtight in order to prevent entry of external air,<br />
IP54 minimum.<br />
Reference<br />
ICT1800AG<br />
ICL1800AG<br />
Cooling specifications<br />
Specific power A 35 W 10-200 l/h 1800 W 1800 W<br />
Max. water pressure 1 MPa 1 MPa<br />
Exterior circuit airflow 250 m 3 /h 350 m 3 /h<br />
Adjustment Yes Yes<br />
Type Thermostatic Thermostatic<br />
Temperature control range 25-50 °C 25-50 °C<br />
Nature of the fluid Water Water<br />
<strong>Electric</strong>al specifications<br />
Power supply voltage 230 V 50/60 Hz 230 V 50/60 Hz<br />
Start-up/rated intensity 1/0.5 A 1/0.5 A<br />
<strong>Electric</strong>al power absorbed 90 W 90 W<br />
Type of alarm Dry contact Dry contact<br />
Physical features<br />
External dimensions A B C (mm) 310 600 365 830 355 110<br />
IP (EN 60529) IP54 IP54<br />
Weight 26 kg 19 kg<br />
Noise level 64 dB (A) 62 dB (A)<br />
Mounting Top Side<br />
6/38
=<br />
=<br />
ICT / ICL / AG<br />
Air/water exchangers<br />
Dimensions<br />
FIG. 1<br />
Top mounting exchanger<br />
Top mounting Ref.: ICT1800AG<br />
Included with unit:<br />
=<br />
=<br />
497<br />
430<br />
c Drilling template.<br />
40.5 61.5<br />
c Installation accessories.<br />
c Installation and operating<br />
instructions.<br />
268 236 236<br />
280<br />
332<br />
Front of the enclosure<br />
600<br />
310<br />
Water inlet-outlet<br />
Condensation water outlet<br />
FIG. 2<br />
Side mounting Ref.: ICL1800AG<br />
Included with unit:<br />
Side mounting exchanger<br />
300<br />
20<br />
c Drilling template.<br />
105<br />
c Installation accessories.<br />
c Installation and operating<br />
instructions.<br />
c For internal or external mounting.<br />
830<br />
180<br />
300<br />
410<br />
750<br />
150<br />
ø 8<br />
113<br />
360<br />
FIG. 3<br />
Curves<br />
Power absorbed at a water fl ow rate for 100 l/h Power absorbed at a water fl ow rate for 200 l/h Power absorbed at a water fl ow rate for 300 l/h<br />
Power Potencia exchanged disipada por by el the intercambiador exchangers (W)<br />
3500<br />
Td = Temperatura deseada en el interior del armario<br />
3000<br />
Td=50°C<br />
2500 Td=45°C<br />
Td=40°C<br />
2000 Td=35°C<br />
1500 Td=30°C<br />
Td=25°C<br />
1000 Td=20°C<br />
500<br />
0<br />
5 10 15 20 25 30<br />
Water Temperatura temperature del agua ºC °C<br />
Potencia Power exchanged disipada por by el the intercambiador exchangers (W) (W)<br />
4000<br />
4000<br />
3500<br />
3500 Td=50°C<br />
Td=50°C<br />
3000<br />
3000 Td=45°C<br />
Td=45°C<br />
Td=40°C<br />
2500 Td=40°C<br />
2500<br />
Td=35°C<br />
Td=35°C<br />
2000<br />
2000 Td=30°C<br />
Td=30°C<br />
1500<br />
1500 Td=25°C<br />
Td=25°C<br />
1000 Td=20°C<br />
500<br />
Td=20°C<br />
1000<br />
500<br />
0<br />
5 10 15 20 25 30<br />
0 5 10 15 20 25 30<br />
Water temperature ºC<br />
Temperatura del agua °C<br />
Water Temperatura temperature del agua ºC°C<br />
Power Potencia exchanged disipada por by el the intercambiador exchangers (W)<br />
Example: for water at 100 l/h at 15 ºC with a preferred temperature of 35 ºC<br />
Power = 1400 W<br />
6/39
6/40<br />
Cooling units<br />
CLL/CLT standard control
The inside and outside air circuits are perfectly<br />
separated and maintain IP54 watertightness of the<br />
enclosure.<br />
Two fans guarantee air circulation in each one of the<br />
circuits:<br />
c Internal circuit fan. It is on permanently, which<br />
maintains an even temperature inside the enclosure,<br />
avoids the appearance of hot spots and guarantees<br />
a correct reading of the inside temperature of the<br />
enclosure by the set-point thermostat.<br />
c External circuit fan.<br />
The inside thermostat controls the fan and starts<br />
it up when the temperature of the air inside the<br />
enclosure is above the maximum value displayed.<br />
Easy access to the condenser allows simplified<br />
cleaning through blowing.<br />
Disassemble of the cooling units is not necessary for<br />
the high temperature compressor and external fan<br />
maintenances.<br />
The air conditioning units<br />
come with an adjustable<br />
thermostat that controls<br />
the inside temperature of<br />
the enclosure:<br />
c It avoids the installation<br />
of an auxiliary control<br />
thermostat.<br />
c It guarantees the<br />
correct reading of the<br />
inside temperature of<br />
the enclosure.<br />
Temperature adjustment<br />
range: +20 ºC to +50 ºC<br />
(supplied factory-adjusted<br />
to 35 ºC).<br />
ENVIRONMENTALLY<br />
friendly<br />
c The top mounting models feature a condensation<br />
water automatic evaporation system with an<br />
exclusive safety system that switches off the<br />
apparatus or issues an alarm if the condensation<br />
water level is exceeded.<br />
c They also feature an exclusive voluntary unloading<br />
system that makes it possible to empty the water<br />
from the condensation tray.<br />
c Available in two<br />
versions: top and side<br />
mounting versions.<br />
c The power of<br />
mechanically regulated<br />
cooling units ranges<br />
from 240 to 3100 W.<br />
There is always<br />
equipment which is<br />
suited to your needs.<br />
c Comfortable and<br />
easy to assemble and<br />
disassemble.<br />
c The side installation<br />
models can be semirecessed<br />
with the<br />
use of the specific<br />
accessory.<br />
They are equipped with an<br />
automatic reset pressostat<br />
and a contact thermostat that<br />
detects the overpressure in<br />
the compressor circuit and<br />
interrupts it and the outside<br />
circuit fan, thus avoiding<br />
possible faults.<br />
Fitted with a fault warning<br />
relay, it provides the possibility<br />
of operating an alarm indicator,<br />
shutting down the apparatus.<br />
Fitted with high pressure<br />
compressors that allow<br />
them to work at outside<br />
temperatures of up to +55 ºC.<br />
Environmentally friendly.<br />
Use of R134a ecological gas.<br />
6/41
COOLING UNITS<br />
Selection guide<br />
SIDE-MOUNTING<br />
References<br />
Power EN 14511<br />
L35 - L35<br />
Voltage in V-Hz Dimensions (mm) Adjustment<br />
CLL240 240 W (819 Btu/h) 230-50/60 450 350 140 Thermostat<br />
CLL370 370 W (1260 Btu/h) 230-50/60 620 300 170 Thermostat<br />
CLL760 760 W (2594 Btu/h) 230-50/60 800 350 195 Thermostat<br />
CLL1050 1050 W (3584 Btu/h) 230-50/60 900 400 195 Thermostat<br />
CLLMP1100 1100 W (3755 Btu/h) 230-50/60 1010 400 240 Microprocessor<br />
CLLMP1400 1400 W (4780 Btu/h) 230-50/60 1010 400 240 Microprocessor<br />
CLLMP1400T<br />
1400 W (4780 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
1010 400 240 Microprocessor<br />
CLL1650 1650 W (5631 Btu/h) 230-50/60 1000 400 220 Thermostat<br />
CLL1650T<br />
1800 W (6143 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
1000 400 220 Thermostat<br />
CLLMP1800T<br />
1800 W (6145 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
1010 400 240 Microprocessor<br />
6/42
COOLING UNITS<br />
Selection guide<br />
TOP-MOUNTING<br />
References<br />
Power EN 14511<br />
L35 - L35<br />
Voltage in V-Hz Dimensions (mm) Adjustment<br />
CLT760 760 W (2.594 Btu/h) 230-50/60 340 600 350 Thermostat<br />
CLT1050 1050 W (3.584 Btu/h) 230-50/60 400 700 400 Thermostat<br />
CLTMP1400 1400 W (4.780 Btu/h) 230-50/60 415 750 412 Microprocessor<br />
CLT1460 1460 W (4.984 Btu/h) 230-50/60 400 700 400 Thermostat<br />
CLT1650 1650 W (5.631 Btu/h) 230-50/60 430 700 400 Thermostat<br />
CLTMP1800T<br />
1800 W (6.145 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
415 750 412 Microprocessor<br />
CLT1650T<br />
2000 W (6.826 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
430 700 400 Thermostat<br />
CLT2450T<br />
2450 W (8.368 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
470 800 450 Thermostat<br />
CLT3100T<br />
3100 W (10.583 Btu/h)<br />
3 400 V 50 Hz/<br />
3 440 V 60 Hz<br />
470 800 450 Thermostat<br />
6/43
CLL<br />
Cooling units<br />
Mechanical control<br />
Side mounting<br />
Cooling units for electronic switchboards:<br />
c Respect for the environment by using the ecological gas R134a.<br />
c Cooling power of 240 W to 3100 W.<br />
c Possibility of partial flush mounting for all side mounting models.<br />
General features:<br />
c Temperature setting can be adjusted from +20 to +50 ºC.<br />
c As standard, the units are fitted with an automatic reset pressure switch. A<br />
value higher than safety pressure value (on the high pressure circuit) actuates<br />
compressor and external fan switch-off.<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
c The equipment is fitted with switches enabling an alarm report.<br />
c Cooling power of 240 W to 3100 W.<br />
CLL760<br />
c Possibility of partial flush mounting.<br />
Reference CLL240 CLL370 CLL760<br />
Voltage<br />
230 V 50/60 Hz<br />
Cooling power (50/60 Hz) acording to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
240 W (819 Btu/h)<br />
190 W (649 Btu/h)<br />
370/390 W (1263/1331 Btu/h)<br />
300/310 W (1024/1058 Btu/h)<br />
760/810 W (2594/2765 Btu/h)<br />
610/640 W (2082/2184 Btu/h)<br />
Dimensions<br />
Height<br />
Width<br />
Depth<br />
450 mm<br />
350 mm<br />
140 mm + (15 mm inside)<br />
620 mm<br />
300 mm<br />
170 mm<br />
800 mm<br />
350 mm<br />
195 mm<br />
Current<br />
Start-up<br />
Nominal<br />
2.8 A<br />
0.7 A<br />
5.8/6.7 A<br />
1.5/1.8 A<br />
7.7/8.8 A<br />
2/2.3 A<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
140 W<br />
160 W<br />
290/330 W<br />
330/380 W<br />
380/440 W<br />
440/500 W<br />
EER energetic performance<br />
L35 - L35 1.7 1.3/1.2 2.0/1.8<br />
Temperature regulator Thermostat<br />
Temperature setting range 20 - 45 °C 20 - 50 °C<br />
Maximum external temperature 50 °C 55 °C<br />
Noise level 58 dB (A) 65 dB (A) 67 dB (A)<br />
Airflow<br />
Internal circuit<br />
External circuit<br />
Alarm type contact free power<br />
160 m 3 /h<br />
320 m 3 /h<br />
160/175 m 3 /h<br />
210/230 m 3 /h<br />
350/385 m 3 /h<br />
350/385 m 3 /h<br />
Inverter contact<br />
Weight 15 kg 21 kg 33 kg<br />
Cooling gas R134a (0.25 kg) R134a (0.3 kg) R134a (0.5 kg)<br />
Internal IP circuit 54 54 54<br />
External IP circuit 34 34 34<br />
External circuit filter Optional Yes<br />
Mounting model<br />
Side<br />
Recommended protection (fuse curve) T1.6 A T3 A T3 A<br />
6/44
CLL<br />
Cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
CLL240: Dimensions<br />
Cut-out dimensions<br />
Ref. CLL240<br />
External mounting<br />
Partial fl ush mounting<br />
FIG. 2<br />
Side mounting: dimensions<br />
26<br />
P<br />
Ref. CLL370 and CLL760<br />
C<br />
E<br />
H<br />
G<br />
Q<br />
30<br />
A<br />
= =<br />
B<br />
K<br />
ø S<br />
M<br />
60<br />
R<br />
L<br />
N<br />
D<br />
F<br />
Dimensions in mm CLL370 CLL760<br />
A 260 266<br />
B 0 52<br />
C 80 116<br />
D 40 193,5<br />
E 300 375<br />
F 540 413<br />
G 60 80<br />
H 620 800<br />
K 136 136<br />
L 300 350<br />
M 240 294<br />
N - -<br />
P 170 195<br />
Q 35 149<br />
R 0 24<br />
S 8 8<br />
FIG. 3<br />
Curves<br />
CLL240 50/60 Hz CLL370 50 Hz CLL370 60 Hz<br />
400<br />
700<br />
700<br />
350<br />
Ti [ ºC ]<br />
600<br />
Ti [ ºC ]<br />
600<br />
Ti [ ºC ]<br />
Pf [ W ]<br />
300<br />
250<br />
200<br />
150<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
500<br />
400<br />
300<br />
200<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
500<br />
400<br />
300<br />
200<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
100<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50/60 Hz<br />
100<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
100<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
CLL760 50 Hz<br />
1400<br />
CLL760 60 Hz<br />
1400<br />
Pf [ W ]<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
400<br />
200<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
400<br />
200<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
6/45
CLL<br />
Cooling units<br />
Side mounting<br />
Cooling units for switchboards:<br />
c Respect for the environment by using the ecological gas R134a.<br />
c Automatic evaporation of condensation water on all top mounting models.<br />
c Cooling power of 240 W to 3100 W.<br />
c Possibility of partial flush mounting for all side mounting models.<br />
General features:<br />
c Temperature setting can be adjusted from +20 to +50 ºC.<br />
c As standard, the units are fitted with an automatic reset pressure switch.<br />
A value higher than safety pressure value (on the high pressure circuit)<br />
activates compressor and external fan switch-off.<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
CLL1650<br />
c The equipment is fitted with switches enabling an alarm report.<br />
c Cooling power of 240 W to 3100 W.<br />
c Possibility of partial flush mounting.<br />
Reference CLL1050 CLL1650 CLL1650T<br />
Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />
Cooling power (50/60 Hz) according to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
1050/1100 W<br />
(3584/3755 Btu/h)<br />
840/890 W (2867/3038 Btu/h)<br />
1650/1700 W (5631/5802 Btu/h)<br />
1300/1400 W (4438/4779 Btu/h)<br />
1800/1900 W (6143/6485 Btu/h)<br />
1400/1500 W (4779/5121 Btu/h)<br />
Dimensions<br />
Height<br />
Width<br />
Depth<br />
900 mm<br />
400 mm<br />
195 mm<br />
1000 mm<br />
400 mm<br />
220 mm<br />
Current<br />
Start-up<br />
Nominal<br />
10.1/11.6 A<br />
2.7/3 A<br />
16.1/18.5 A<br />
4.2/4.9 A<br />
6.8/7.9 A<br />
2.1/2.5 A<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
550/580 W<br />
580/660 W<br />
800/920 W<br />
920/1100 W<br />
1200/1400 W<br />
1400/1600 W<br />
EER energetic performance<br />
L35 - L35 2.1/1.9 2.1/1.9 1.5/1.4<br />
Temperature setting range Thermostat<br />
Control range 20 - 50 °C<br />
Max. external ambient temperature 55 °C<br />
Noise level 67 dB (A) 67 dB (A) 69 dB (A)<br />
Airflow<br />
Internal circuit<br />
External circuit<br />
350/385 m 3 /h<br />
510/560 m 3 /h<br />
550/600 m 3 /h<br />
620/680 m 3 /h<br />
Alarm contact Potential-free<br />
Weight 39 kg 42 kg 46 kg<br />
Cooling gas R134a (0.7 kg) R134a (0.75 kg)<br />
Internal IP circuit 54 54 54<br />
External IP circuit 34 34 34<br />
External circuit filter Yes<br />
Mounting model Side<br />
Recommended protection (fuse curve) T4 A T6 A T3 A<br />
6/46
CLL<br />
Cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
Side mounting: dimensions<br />
26<br />
P<br />
C<br />
E<br />
H<br />
G<br />
Q<br />
30<br />
A<br />
= =<br />
B<br />
K<br />
ø S<br />
M<br />
60<br />
R<br />
L<br />
N<br />
D<br />
F<br />
Dimensions in mm CLL1050 CLL1650 CLL1650T<br />
A 300 300 300<br />
B 0 0 0<br />
C 135 135 135<br />
D 30 30 30<br />
E 465 475 475<br />
F 840 840 840<br />
G 100 100 100<br />
H 900 1000 1000<br />
K 180 180 180<br />
L 400 400 400<br />
M 320 320 320<br />
N - 470 470<br />
P 195 220 220<br />
Q 35 25 25<br />
R 195 195 195<br />
S 0 10 10<br />
FIG. 2<br />
Curves<br />
CLL1050 50 Hz CLL1050 60 Hz CLL1650 50 Hz<br />
1800<br />
1800<br />
3000<br />
Pf [ W ]<br />
1600<br />
1400<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1600<br />
1400<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2600<br />
2200<br />
1800<br />
1400<br />
1000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
400<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
400<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
CLL1650 60 Hz CLL1650T 50 Hz CLL1650T 60 Hz<br />
3000<br />
3200<br />
3200<br />
Pf [ W ]<br />
2600<br />
2200<br />
1800<br />
1400<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2800<br />
2400<br />
2000<br />
1600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2800<br />
2400<br />
2000<br />
1600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1000<br />
1200<br />
1200<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
6/47
CLT<br />
Cooling units<br />
Top mounting<br />
Cooling units for electrical switchboards:<br />
c Respect for the environment by using the ecological gas R134a.<br />
c Automatic evaporation of condensation water.<br />
c Cooling power of 760 W to 3100 W.<br />
General features:<br />
c Temperature setting can be adjusted from +20 to +50 ºC.<br />
CLT1050<br />
c As standard, the units are fitted with an automatic reset pressure switch.<br />
A value higher than safety pressure value (on the high pressure circuit)<br />
actuates compressor and external fan switch-off.<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
c The equipment is fitted with switches enabling an alarm report.<br />
c System of automatic recovery and evaporation of condensates.<br />
Reference CLT760 CLT1050 CLT1460<br />
Voltage<br />
230 V 50/60 Hz<br />
Cooling power (50/60 Hz) according to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
760/810 W (2594/2765 Btu/h)<br />
610/640 W (2082/2184 Btu/h)<br />
1050/1100 W (3584/3755 Btu/h)<br />
840/890 W (2867/3038 Btu/h)<br />
1460/1500 W (4983/5121 Btu/h)<br />
1200/1200 W (4096/4096 Btu/h)<br />
Dimensions<br />
Height<br />
Width<br />
Depth<br />
340 mm<br />
600 mm<br />
350 mm<br />
400 mm<br />
700 mm<br />
400 mm<br />
Current<br />
Starting current<br />
Rated current<br />
7.7/8.8 A<br />
2/2.3 A<br />
10.1/11.6 A<br />
2.7/3 A<br />
14.1/16.2 A<br />
3.7/4.3 A<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
380/440 W<br />
440/500 W<br />
550/580 W<br />
580/660 W<br />
730/810 W<br />
810/930 W<br />
EER energetic performance<br />
L35 - L35 2.0/1.8 2.1/1.9 2.1/1.9<br />
Control type thermostatic<br />
Thermostat<br />
Temperature setting range 20 - 50 °C<br />
Maximum external temperature 55 °C<br />
Noise level 67 dB (A) 69 dB (A)<br />
Airflow<br />
Internal circuit<br />
External circuit<br />
Alarm type free power<br />
350/385 m 3 /h<br />
350/385 m 3 /h<br />
400/440 m 3 /h<br />
620/680 m 3 /h<br />
Inverter contact<br />
Weight 33 kg 41 kg 45 kg<br />
Cooling gas R134a (0.5 kg) R134a (0.7 kg) R134a (0.75 kg)<br />
Internal IP circuit 54 54 54<br />
External IP circuit 34 34 34<br />
External circuit filter Yes<br />
Mounting model<br />
Top<br />
Recommended protection (fuse curve) T3 A T4 A T6 A<br />
6/48
CLT<br />
Cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
Top-mounting Ref.: CLT760-CTL1050-CTL1460<br />
J<br />
26<br />
A<br />
B<br />
ø 8<br />
K<br />
250<br />
300<br />
C<br />
M*<br />
D<br />
E<br />
H<br />
F<br />
G<br />
Drilling template for top mounting without<br />
intermediate frame<br />
Reference A B C D E F G H I K M<br />
CLT760 108 350 350 40 136 292 80 600 600 340 600<br />
CLT1050 118 420 400 45 180 328 90 700 700 400 700<br />
CLT1460 118 420 400 45 180 328 90 700 700 400 700<br />
FIG. 2<br />
Curves<br />
CLT760 50 Hz CLT760 60 Hz CLT1050 50 Hz<br />
1400<br />
1400<br />
1800<br />
Pf [ W ]<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1600<br />
1400<br />
1200<br />
1000<br />
800<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
400<br />
400<br />
600<br />
200<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
200<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
400<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
CLT1050 60 Hz CLT1460 50 Hz CLT1460 60 Hz<br />
1800<br />
2400<br />
2400<br />
Pf [ W ]<br />
1600<br />
1400<br />
1200<br />
1000<br />
800<br />
600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2100<br />
1800<br />
1500<br />
1200<br />
900<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2100<br />
1800<br />
1500<br />
1200<br />
900<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
400<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
6/49
CLT<br />
Cooling units<br />
Top mounting<br />
Cooling units for electrical switchboards:<br />
c Respect for the environment by using the ecological gas R134a.<br />
c Automatic evaporation of condensation water.<br />
c Cooling power of 760 W to 3100 W.<br />
General features:<br />
c Temperature setting can be adjusted from +20 to +50 ºC.<br />
CLT1650<br />
c As standard, the units are fitted with an automatic reset pressure switch.<br />
A value higher than safety pressure value (on the high pressure circuit)<br />
actuates compressor and external fan switch-off.<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
c The equipment is fitted with switches enabling an alarm report.<br />
c System of automatic recovery and evaporation of condensates.<br />
Reference CLT1650 CLT1650T<br />
Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />
Cooling power (50/60 Hz) according to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
1650/1700 W (5631/5802 Btu/h)<br />
1300/1400 W (4438/4779 Btu/h)<br />
1650/2100 W (6826/7169 Btu/h)<br />
1600/1700 W (5462/5803 Btu/h)<br />
Dimensions<br />
Height<br />
Width<br />
Depth<br />
430 mm<br />
700 mm<br />
400 mm<br />
Current<br />
Starting current<br />
Rated current<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
16.1/18.5 A<br />
4.2/4.5 A<br />
800/920 W<br />
920/1100 W<br />
6.8 /7.9 A<br />
2.1/2.5 A<br />
1200/1400 W<br />
1400/1700 W<br />
EER energetic performance<br />
L35 - L35 2.1/1.9 1.7/1.5<br />
Temperature regulator<br />
Thermostat<br />
Temperature setting range 20 - 50 °C<br />
Maximum external temperature 55 °C<br />
Noise level 67 dB (A) 69 dB (A)<br />
Airflow<br />
Internal circuit<br />
External circuit<br />
Alarm type free power<br />
550/600 m 3 /h<br />
620/680 m 3 /h<br />
Inverter contact<br />
Weight 47 kg 60 kg<br />
Cooling gas<br />
R134a (1.0 kg)<br />
Internal IP circuit 54<br />
External IP circuit 34<br />
External circuit filter<br />
Yes<br />
Mounting model<br />
Top<br />
Recommended protection (fuse curve) T6 A T3 A<br />
6/50
CLT<br />
Cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
Top mounting Ref.: CLT1650-CLT1650T<br />
J<br />
26<br />
A<br />
B<br />
ø 8<br />
K<br />
250<br />
300<br />
C<br />
M*<br />
D<br />
E<br />
H<br />
F<br />
G<br />
Drilling template for top mounting without<br />
intermediate frame<br />
Reference A B C D E F G H I K M<br />
CLT1650 118 420 400 45 180 328 90 700 700 430 700<br />
CLT1650T 118 420 400 45 180 328 90 700 700 430 700<br />
FIG. 2<br />
Curves<br />
CLT1650 50 Hz<br />
CLT1650 60 Hz<br />
3000<br />
3000<br />
Pf [ W ]<br />
2600<br />
2200<br />
1800<br />
1400<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2600<br />
2200<br />
1800<br />
1400<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
1000<br />
1000<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
3200<br />
CLT1650T 50 Hz<br />
3200<br />
CLT1650T 60 Hz<br />
Pf [ W ]<br />
2800<br />
2400<br />
2000<br />
1600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2800<br />
2400<br />
2000<br />
1600<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1200<br />
1200<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
6/51
CLT<br />
Cooling units<br />
Top mounting<br />
Cooling units for electrical switchboards:<br />
c Respect for the environment by using the ecological gas R134a.<br />
c Automatic evaporation of condensation water.<br />
c Cooling power of 760 W to 3100 W.<br />
General features:<br />
c Temperature setting can be adjusted from +20 to +50 ºC.<br />
c As standard, the units are fitted with an automatic reset pressure switch.<br />
A value higher than safety pressure value (on the high pressure circuit)<br />
actuates compressor and external fan switch-off.<br />
CLT3100T<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
c The equipment is fitted with switches enabling an alarm report.<br />
c System of automatic recovery and evaporation of condensates.<br />
Reference CLT2450T CLT3100T<br />
Voltage<br />
Cooling power (50/60 Hz) according to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
Dimensions<br />
Height<br />
Width<br />
Depth<br />
2450/2600 W (8362/8876 Btu/h)<br />
2000/2100 W (6828/7169 Btu/h)<br />
3 400 V 50 Hz / 3 440 V 60 Hz<br />
470 mm<br />
800 mm<br />
450 mm<br />
3100/3300 W (10580/11266 Btu/h)<br />
2500/2600 W (8532/8876 Btu/h)<br />
Current<br />
Start-up<br />
Nominal<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
8.4/10.1 A<br />
2.6/3.2 A<br />
1500/1800 W<br />
1800/2100 W<br />
9.6/11.3 A<br />
3.0/3.5 A<br />
1700/2000 W<br />
2000/2300 W<br />
EER energetic performance<br />
L35 - L35 1.6/1.5 1.8/1.7<br />
Temperature regulator Thermostat<br />
Control range 20 - 50 °C<br />
Max. external ambient temperature 55 °C<br />
Noise level<br />
69 dB (A)<br />
Internal IP circuit 750/820 m 3 /h<br />
External IP circuit 1200/1310 m 3 /h<br />
Alarm type contact free power<br />
Inverter contact<br />
Weight 65 kg<br />
Cooling gas R134a (1.5 kg) R134a (1.7 kg)<br />
Internal IP circuit 54<br />
External IP circuit 34<br />
External circuit filter Yes<br />
Mounting model Top<br />
Recommended protection (fuse curve) T4 A T4 A<br />
6/52
CLT<br />
Cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
Top mounting Ref.: CLT2450T-CLT3100T<br />
26<br />
800<br />
26<br />
220<br />
360<br />
ø 10<br />
*<br />
470<br />
300<br />
300<br />
450<br />
70<br />
140<br />
380<br />
140<br />
800<br />
800*<br />
* Maximum overall dimensions of the intermediate frame<br />
FIG. 2<br />
Curves<br />
CLT2450T 50 Hz<br />
CLT2450T 60 Hz<br />
4000<br />
4000<br />
Pf [ W ]<br />
3500<br />
3000<br />
2500<br />
2000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
3500<br />
3000<br />
2500<br />
2000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
1500<br />
1500<br />
1000<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
1000<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
5500<br />
CLT3100T 50 Hz<br />
5500<br />
CLT3100T 60 Hz<br />
4900<br />
4900<br />
Pf [ W ]<br />
4300<br />
3700<br />
3100<br />
2500<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
4300<br />
3700<br />
3100<br />
2500<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1900<br />
1900<br />
1300<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
1300<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
6/53
CLL / CLT<br />
Accessories<br />
Frames for partial flush mounting<br />
c For partial flush mounting of the CLL cooling units.<br />
Reference<br />
MECL370<br />
MECL760<br />
MECL1050<br />
MECL1650<br />
To fit the units<br />
CLL370<br />
CLL760<br />
CLL1050<br />
CLL1650/1650T<br />
Partial fl ush unit mounting<br />
Frame for partial mounting<br />
Reference T V V* W* X Y<br />
MECL370 320 635 646 346 80 90<br />
MECL760 370 815 826 396 95 100<br />
MECL1050 420 915 926 446 95 100<br />
MECL1650 420 1015 1026 446 120 100<br />
* Maximum dimensions of the frame<br />
T<br />
* V<br />
U<br />
26<br />
X<br />
Y<br />
*20<br />
* W<br />
26<br />
X<br />
Y<br />
6/54
CLL / CLT<br />
Accessories<br />
Intermediate frame for top mounting<br />
c For mounting the CLT760 cooling unit on the top of enclosures<br />
width = 600 mm<br />
depth = 400 mm<br />
c Colour grey RAL-7032.<br />
c Dimensions: 60 595 360 mm.<br />
Reference<br />
MMI64<br />
Characteristics<br />
To fit enclosures 600 mm<br />
wide and 400 mm deep.<br />
26<br />
360<br />
Replacement filter<br />
Reference<br />
Characteristics<br />
FCLIC<br />
To fit to all cooling units<br />
6/55
6/56<br />
Cooling units<br />
CLLMP/CLTMP electronic control
c Available in two<br />
versions: top- and<br />
side-mounting.<br />
c Power from 1100 W to<br />
1800 W allowing you to<br />
install the equipment<br />
that best suits your<br />
needs in each case.<br />
Comfortable and<br />
easy to assemble and<br />
disassemble.<br />
The side-mounted air<br />
conditioners feature<br />
an exclusive quickinstallation<br />
system:<br />
c Two retractable<br />
handles facilitate the<br />
installation of the air<br />
conditioner by a single<br />
operator.<br />
c They have an exclusive<br />
quick-fixing system<br />
without screws that<br />
facilitates mounting<br />
on the enclosure and<br />
guarantees the IP54<br />
degree of protection.<br />
c The electrical<br />
connection is carried<br />
out with removable<br />
connectors supplied<br />
with the cooling unit.<br />
One single machining<br />
size.<br />
The machining sizes are<br />
the same for all sidemounted<br />
cooling units.<br />
c Fast access to<br />
the inside makes<br />
unit cleaning and<br />
maintenance easy.<br />
c Its design renders<br />
filters unnecessary<br />
in most cases. It is<br />
possible to install a<br />
filter in the exterior<br />
circuit for particularly<br />
polluted atmospheres.<br />
c The design of the<br />
aluminium slats of<br />
the condenser makes<br />
maintenance easier<br />
and less frequent.<br />
ENVIRONMENTALLY<br />
friendly<br />
The inside and outside<br />
air circuits are perfectly<br />
separated and maintain<br />
the enclosure’s IP54<br />
watertightness.<br />
Two fans guarantee air<br />
circulation in each of the<br />
circuits:<br />
c Recirculation fan<br />
for air inside the<br />
enclosure.<br />
The internal circuit fan<br />
is always on, thereby<br />
maintaining a uniform<br />
temperature inside<br />
the enclosure and<br />
preventing hot spots.<br />
c Fan to circulate<br />
the air outside the<br />
enclosure.<br />
The inside thermostat<br />
controls the fan and<br />
starts it up when the<br />
temperature of the air<br />
inside the enclosure<br />
is above the required<br />
temperature.<br />
Electronic regulation<br />
provides:<br />
c Precise control of the<br />
operating temperature:<br />
– Start-up of the compressor<br />
at +1 °C above the preset<br />
temperature.<br />
– Switching off of the<br />
compressor at -5 °C below<br />
the preset temperature.<br />
c Door contact<br />
management.<br />
c Manual alarm reset.<br />
c Manual rearming of the<br />
alarms.<br />
c Control of the idle and<br />
operation times of the<br />
compressor.<br />
All models, side-and<br />
top-mounting, have an<br />
automatic evaporation<br />
system for the<br />
condensation water.<br />
Use of R134 ecological<br />
gas.<br />
Temperature adjustment<br />
range from +20 to +50 °C.<br />
6/57
CLLMP<br />
Electronically-controlled cooling units<br />
Side mounting<br />
CLLMP1400<br />
General characteristics:<br />
c Main components: high temperature compressor, two fans mounted on<br />
removable support, two exchange cassettes, ecological cooling fluid HFC<br />
R134a, electronic control and evaporation device (with anti-corrosion finish)<br />
for side and top models.<br />
c Temperature setting can be adjusted from +20 to +50 ºC (pre-adjustment<br />
and temperature recommended: 35 ºC).<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
c Electronic control by microprocessor enables:<br />
v Adjustment of set temperature.<br />
v Door contact control.<br />
v Data is stored in the memory in the event of a power cut:<br />
– Minimum compressor operating time.<br />
– Minimum compressor idle time.<br />
v Compressor switch-on at set temperature +1 ºC.<br />
v Compressor switch-off at set temperature –5 ºC.<br />
v Alarm management.<br />
v Alarm reset by “acknowledgement” (manual reset).<br />
Operating conditions:<br />
c Operating temperature: +20 to +55 ºC.<br />
c An optional filter is required in cases of installation in the following<br />
applications: intensive welding, hot metal forging, fibres and textiles, crushing,<br />
rubber processing and other difficult environments.<br />
c The air conditioner incorporates two retractable handles to facilitate transport.<br />
c The air conditioner incorporates a quick attachment device. A circular screw/<br />
cage nut assembly ensures locking of the unit from the exterior.<br />
c <strong>Electric</strong>al connection is by plug-in connectors, included with the unit.<br />
c Do not obstruct, even partially, air inlets and outlets.<br />
c The unit should be installed spaced at least 30 cm from walls and at least<br />
10 cm from floor level.<br />
Reference CLLMP1100 CLLMP1400 CLLMP1400T CLLMP1800T<br />
Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />
Cooling power (50/60 Hz) according to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
Dimensions<br />
Height Width Depth<br />
Current<br />
Start-up<br />
Nominal<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
EER energetic performance<br />
L35 - L35<br />
1100/1200 W<br />
(3755/4097 Btu/h)<br />
880/930 W<br />
(3004/3175 Btu/h)<br />
12.1/13.9 A<br />
3.2/3.7 A<br />
600/690 W<br />
690/790 W<br />
1400/1500 W<br />
(4780/5121 Btu/h)<br />
1200/1300 W<br />
(4097/4438 Btu/h)<br />
1400/1500 W<br />
(4780/5121 Btu/h)<br />
1200/1300 W<br />
(4097/4438 Btu/h)<br />
1,010 mm 400 mm 240 mm<br />
18.1/22.2 A<br />
4.8/5.8 A<br />
900/1,100 W<br />
1100/1300 W<br />
3.7/4.3 A<br />
1.2/1.4 A<br />
700/810 W<br />
810/930 W<br />
1800/1900 W<br />
(6145/6485 Btu/h)<br />
1400/1500 W<br />
(4780/5121 Btu/h)<br />
5.3/6.3 A<br />
1.8/2.1 A<br />
1000/1200 W<br />
1200/1300 W<br />
1.8/1.7 1.6/1.4 2.0/1.9 1.8/1.7<br />
Temperature regulator Microprocessor (with display and diagnosis)<br />
Temperature setting range 20 - 50 °C<br />
Max. external ambient temperature 55 °C<br />
Noise level 62 dB (A) 64 dB (A) 66 dB (A) 69 dB (A)<br />
Airflow<br />
Internal circuit<br />
External circuit<br />
Alarm type free power<br />
575/600 m 3 /h<br />
860/900 m 3 /h<br />
860/900 m 3 /h<br />
860/900 m 3 /h<br />
860/900 m 3 /h<br />
860/900 m 3 /h<br />
885/900 m 3 /h<br />
1050/1160 m 3 /h<br />
Inverter contact<br />
Weight 45 kg 46 kg 47 kg 50 kg<br />
Cooling gas R134a (0.85 kg) R134a (0.85 kg) R134a (0.85 kg) R134a (0.85 kg)<br />
Internal IP circuit 54 54 54 54<br />
External IP circuit 34 34 34 34<br />
External circuit filter Optional<br />
Mounting model Side<br />
Recommended protection (fuse curve) T6 A T8 A T2 A T3 A<br />
6/58
CLLMP<br />
Electronically-controlled cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
Drilling template for side mounting<br />
Drilling template for side mounting<br />
FIG. 2<br />
Curves<br />
CLLMP1100 50 Hz CLLMP1100 60 Hz CLLMP1400T 50 Hz<br />
2000<br />
1800<br />
2000<br />
1800<br />
2200<br />
2000<br />
Ti [ ºC ]<br />
Ti [ ºC ]<br />
1600<br />
1400<br />
50<br />
45<br />
1600<br />
1400<br />
50<br />
45<br />
40<br />
1800<br />
1600<br />
1200<br />
40<br />
35<br />
1200<br />
35<br />
30<br />
1400<br />
1000<br />
800<br />
30<br />
25<br />
20<br />
1000<br />
800<br />
25<br />
20<br />
1200<br />
1000<br />
Pf [ W ]<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
600<br />
400<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
400<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
800<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
CLLMP1400T 60 Hz<br />
Pf [ W ]<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
CLLMP1400 50 Hz<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
CLLMP1400 60 Hz<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
800<br />
800<br />
800<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
CLLMP1800T 50 Hz<br />
3000<br />
2800<br />
2600<br />
2400<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
800<br />
Pf [ W ]<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
CLLMP1800T 60 Hz<br />
3000<br />
Ti [ ºC ]<br />
2800<br />
2600<br />
2400<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
1200<br />
1000<br />
800<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
6/59
CLTMP<br />
Electronically-controlled cooling units<br />
Top mounting<br />
CLTMP1400<br />
General characteristics:<br />
c Main components: high temperature compressor, two fans mounted on<br />
removable support, two exchange cassettes, ecological cooling fluid HFC<br />
R134a, electronic control and evaporation device (with anti-corrosion finish)<br />
for side and top models.<br />
c Temperature setting can be adjusted from +20 to +50 ºC (pre-adjustment<br />
and temperature recommended: 35 ºC).<br />
c Internal and external air circuits are totally independent and IP54 sealing is<br />
assured between external ambient air and air within the enclosure.<br />
c The internal circuit fan which runs continuously, prevents formation of hot<br />
spots and improves thermal dissipation of the enclosure.<br />
c Electronic control by microprocessor enables:<br />
v Adjustment of set temperature.<br />
v Door contact control.<br />
v Data is stored in the memory in the event of a power cut:<br />
– Minimum compressor operating time.<br />
– Minimum compressor idle time.<br />
v Compressor switch-on at set temperature +1 ºC.<br />
v Compressor switch-off at set temperature –5 ºC.<br />
v Alarm management.<br />
v Alarm reset by “acknowledgement” (manual reset).<br />
Operating conditions:<br />
c Operating temperature: +20 to +55 ºC.<br />
c An optional filter is required in cases of installation in the following<br />
applications: intensive welding, hot metal forging, fibres and textiles,<br />
crushing, rubber processing and other difficult environments.<br />
c The air conditioner incorporates two retractable handles to facilitate<br />
transport.<br />
c The air conditioner incorporates a quick attachment device. A circular<br />
screw/cage nut assembly ensures locking of the unit from the exterior.<br />
c <strong>Electric</strong>al connection is by plug-in connectors, included with the unit.<br />
c Do not obstruct, even partially, air inlets and outlets.<br />
c The unit should be installed spaced at least 30 cm from walls and at least<br />
10 cm from floor level.<br />
Reference CLTMP1400 CLTMP1800T<br />
Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />
Cooling power (50/60 Hz) according to EN 14511<br />
L35 - L35<br />
L35 - L50<br />
1400/1500 W (4780/5121 Btu/h)<br />
1200/1300 W (4097/4438 Btu/h)<br />
1800/1900 W (6145/6485 Btu/h)<br />
1400/1500 W (4780/5121 Btu/h)<br />
Dimensions<br />
Height Width Depth<br />
415 mm 750 mm 412 mm<br />
Intensity<br />
Starting current<br />
Rated current<br />
<strong>Electric</strong>al power absorbed<br />
L35 - L35<br />
L35 - L50<br />
18.1/22.2 A<br />
4.8/5.8 A<br />
900/1100 W<br />
1100/1300 W<br />
5.3/6.3 A<br />
1.8/2.1 A<br />
1000/1200 W<br />
1200/1300 W<br />
EER energetic performance<br />
L35 - L35 1.6/1.4 1.8/1.7<br />
Temperature regulator<br />
Microprocessor (with display and diagnosis)<br />
Temperature setting range 20 - 50 °C<br />
Max. external ambient temperature 55 °C<br />
Noise level 64 dB (A) 69 dB (A)<br />
Airflow<br />
Internal circuit<br />
External circuit<br />
Alarm type free power<br />
860/900 m 3 /h<br />
860/900 m 3 /h<br />
885/900 m 3 /h<br />
1050/1160 m 3 /h<br />
Inverter contact<br />
Weight 48 kg 50 kg<br />
Cooling gas R134a (0.95 kg) R134a (0.95 kg)<br />
Internal IP circuit 54<br />
External IP circuit 34<br />
External circuit filter Optional<br />
Mounting model<br />
Top<br />
Recommended protection (fuse curve) T8 A T3 A<br />
6/60
CLTMP<br />
Electronically-controlled cooling units<br />
Dimensions (mm)<br />
FIG. 1<br />
Drilling template for top mounting<br />
Drilling template for top mounting<br />
FIG. 2<br />
Curves<br />
CLTMP1400 60 Hz<br />
CLTMP1400 50 Hz<br />
Pf [ W ]<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
2200<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
800<br />
800<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
600<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
CLTMP1800T 50 Hz<br />
3000<br />
2800<br />
2600<br />
2400<br />
2200<br />
Pf [ W ]<br />
2000<br />
1800<br />
1600<br />
1400<br />
1200<br />
1000<br />
800<br />
Ti [ ºC ]<br />
50<br />
45<br />
40<br />
35<br />
30<br />
25<br />
20<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 50 Hz<br />
CLTMP1800T 60 Hz<br />
3000<br />
Ti [ ºC ]<br />
2800<br />
2600<br />
50<br />
2400<br />
45<br />
2200<br />
40<br />
2000<br />
35<br />
1800<br />
30<br />
1600<br />
25<br />
1400<br />
20<br />
1200<br />
1000<br />
800<br />
20 25 30 35 40 45 50 55<br />
Te [ ºC ] f = 60 Hz<br />
Te: ambient air temperature (°C)<br />
Ti: temperature inside enclosure (°C)<br />
Pf: cooling power (W)<br />
6/61
CLLMP / CLTPM<br />
Accessories<br />
Filter unit<br />
c For installation in the outside circuit of the side cooling units.<br />
Reference CLLMP...<br />
c Reference: CFCLL.<br />
CFCLL<br />
c Replacement filter.<br />
Reference: CFLL.<br />
CFLL<br />
6/62
CLLMP / CLTPM<br />
Accessories<br />
Side panels prepared for air conditioners<br />
c Set of 2 side panels for fixing inside or outside the enclosure. One<br />
pre-knocked panel for the direct fi xing of the CLLMP side-mounted<br />
cooling units…<br />
Reference Height Depth<br />
2PLOL186CLM 1,800 600<br />
2PLOL188CLM 1,800 800<br />
2PLOL206CLM 2,000 600<br />
2PLOL208CLM 2,000 800<br />
6/63
6/64<br />
Insulated resistance heaters<br />
Heating safely
c Available in two versions: by convection and with fan.<br />
c Alternating or direct current.<br />
c Powers from 10 W to 550 W.<br />
It has a plastic covering<br />
to prevent direct contact<br />
with the aluminium<br />
radiator.<br />
c The resistors equipped<br />
with fan guarantee<br />
air recirculation and<br />
an even temperature<br />
inside the enclosure.<br />
c High-flow, silent fans.<br />
c Small size.<br />
c Fast electrical connection by means of snap-on<br />
terminals.<br />
c Fast and simple fixing to the 35 mm DIN rail.<br />
c Maintenance-free.<br />
c Protected from direct contact with the aluminium<br />
radiator.<br />
c <strong>Electric</strong>al connection protected from direct contact<br />
by means of a plastic terminal block cover.<br />
c Equipped with a PTC-type heating element.<br />
c Surface temperature below +70 ºC.<br />
c The configuration of the aluminium section produces<br />
a chimney effect. High natural convection.<br />
c Low energy consumption thanks to the autoadjustment<br />
of the PTC resistor.<br />
Certifications<br />
c EC Marking.<br />
c Compliant with UL and VDE across the range.<br />
6/65
RESISTANCE<br />
HEATERS<br />
Selection guide<br />
INSULATED RESISTANCE HEATERS<br />
Reference Power W Voltage V<br />
Terminal block<br />
Type of connection<br />
Cable<br />
RC10/12-36AI 10 12-36 DC X<br />
RC10AI 10 110-250 AC X<br />
RC20/12-36AI 21 12-36 DC X<br />
RC20AI 21 110-250 AC X<br />
RC50/12-36AI 55 12-36 DC X<br />
RC50AI 55 110-250 AC X<br />
RC50/270-420AI 55 270-420 AC X<br />
RC100/12-36AI 102 12-36 DC X<br />
RC100AI 102 110-250 AC X<br />
RC100/270-420AI 102 270-420 AC X<br />
RC150/12-36AI 147 12-36 DC X<br />
RC150AI 147 110-250 AC X<br />
6/66
RESISTANCE<br />
HEATERS<br />
Selection guide<br />
INSULATED RESISTANCE HEATERS WITH FAN<br />
Reference Power W Voltage V<br />
Type of connection<br />
Terminal block<br />
Cable<br />
RCV170 170 230 AC X<br />
THERMOFANS<br />
Reference Power W Voltage V<br />
Typo of connection<br />
Terminal block<br />
Cable<br />
TMV350-550/120 400/550 120 AC X<br />
TMV350/550 400/550 230 AC X<br />
TMV350 350 230 AC X<br />
6/67
RC ... AI<br />
Resistance heaters<br />
Insulated<br />
RC10AI - RC20AI<br />
10 W and 20 W insulated resistance<br />
heaters<br />
General characteristics:<br />
c Compact resistance heater which prevents the condensation of water and<br />
ice inside the enclosures.<br />
c Innovative design for better natural convection and high thermal<br />
performance.<br />
c Compact, smaller resistance heater.<br />
c Extruded aluminium body.<br />
c Features an insulated UL94 V0 plastic cover in light grey to avoid direct<br />
contact with the heating elements (PTC) and the aluminium radiator.<br />
c Surface temperature limited to less than 70 °C.<br />
c Equipped with a connection cable.<br />
c Double safety insulated (plastic).<br />
c PTC technology range.<br />
c Quick clip-fixing onto the 35 mm DIN rail.<br />
c Compliant with UL and VDE EC Marking.<br />
Usage conditions:<br />
c The resistance heaters should be used together with a temperature<br />
regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />
installed).<br />
c The enclosure must be sealed in order to prevent the penetration of<br />
external air.<br />
c The electrical protection devices must be installed between the supply<br />
source and the resistance heaters themselves.<br />
Characteristics<br />
Reference<br />
RC10AI RC10/12-36AI RC20AI RC20/12-36AI<br />
Heating power at 0 °C 10 W 21 W<br />
Power supply voltage 110-250 V AC/DC 12-36 V AC/DC 110-250 V AC/DC 12-36 V AC/DC<br />
Heating element<br />
PTC<br />
Surface temperature<br />
RC ... AI<br />
Resistance heaters<br />
Dimensions (mm)<br />
FIG. 1<br />
Connections<br />
Reference<br />
L (mm)<br />
RC10AI 98<br />
RC20AI 98<br />
75<br />
Clip clip de on<br />
35 fijación mm<br />
DIN para rail carril<br />
DIN de<br />
35 mm<br />
98<br />
38<br />
1 2<br />
1 2<br />
6/69
RC ... AI<br />
Resistance heaters<br />
RC50AI - RC100AI - RC150AI<br />
55 W - 100 W - 147 W insulated<br />
resistance heaters<br />
General characteristics:<br />
c Compact resistance heater which prevents the condensation of water and<br />
ice inside the enclosures.<br />
c Innovative design for better natural convection and high thermal<br />
performance.<br />
c Compact, smaller resistance heater.<br />
c Extruded aluminium body.<br />
c Features an insulated UL94 V0 plastic cover in light grey to avoid direct<br />
contact with the heating elements (PTC) and the aluminium radiator.<br />
c Surface temperature limited to less than 70 °C.<br />
c Fitted with 2.5 mm 2 quick-connection terminals.<br />
c Double safety insulated (plastic).<br />
c PTC technology range.<br />
c Quick clip-fixing onto the 35 mm DIN rail (EN 50022).<br />
c Certifications compliant with UL and VDE and EC Marking.<br />
Usage conditions:<br />
c The resistance heaters should be used together with a temperature<br />
regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />
installed).<br />
c The enclosure must be sealed in order to prevent the penetration of<br />
external air.<br />
c The electrical protection devices must be installed between the supply<br />
source and the resistance heaters themselves.<br />
Characteristics<br />
Reference<br />
RC50AI<br />
RC50/12-36AI<br />
RC50/<br />
270-420AI<br />
RC100AI<br />
RC100/<br />
12-36AI<br />
RC100/<br />
270-420AI<br />
RC 150AI<br />
Heating power at 0 °C 55 W 102 W 147 W<br />
Power supply voltage<br />
110-250 V<br />
AC/DC<br />
12-36 V<br />
AC/DC<br />
270-420 V<br />
AC/DC<br />
110-250 V<br />
AC/DC<br />
12-36 V<br />
AC/DC<br />
Heating element<br />
PTC<br />
Surface temperature<br />
RC ... AI<br />
Resistance heaters<br />
Dimensions (mm)<br />
FIG. 1<br />
Reference<br />
L (mm)<br />
RC50AI 110<br />
RC50/12-36AI 110<br />
RC50/270-420AI 110<br />
RC100AI 110<br />
RC100/12-36AI 110<br />
RC100/270-420AI 150<br />
RC150AI 150<br />
RC150/12-36AI 150<br />
FIG. 2<br />
Diagram<br />
Heating power diagram - Ambient temperature<br />
Heating power (W)<br />
RC150AI<br />
RC100AI<br />
RC50AI<br />
Ambient temperature (°C)<br />
6/71
RCV<br />
Resistance heaters with fan<br />
RCV170<br />
General characteristics:<br />
c Compact resistance heater which prevents the condensation of water and<br />
ice inside the enclosures.<br />
c Includes an axial fan to ensure uniform heating inside the enclosure.<br />
c Compact, smaller resistance heater.<br />
c Extruded aluminium body.<br />
c Features an insulated UL94 V0 plastic cover in black to avoid direct contact<br />
with the heating elements (PTC) and the aluminium radiator.<br />
c Surface temperature limited to less than 50 °C.<br />
c Fitted with 2.5 mm 2 quick-connection terminals.<br />
c Double safety insulated (plastic).<br />
c PTC technology range.<br />
c Quick clip-fixing onto the 35 mm DIN rail (EN 50022).<br />
c Certifications compliant with UL and VDE and EC Marking.<br />
Usage conditions:<br />
c The resistance heaters should be used together with a temperature<br />
regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />
installed).<br />
c The enclosure should be sealed in order to prevent the penetration of<br />
external air.<br />
c An electrical protection device should be installed on the supply side of the<br />
unit.<br />
Characteristics<br />
Reference<br />
RCV170<br />
Heating power at 0 °C<br />
177 W<br />
Power supply voltage<br />
230 V AC 50-60 Hz<br />
Heating element<br />
PTC<br />
Surface temperature<br />
Max. of 50 ºC in the enclosure, 100 ºC in the upper protection grill (for an external temperature of 20 °C/68 °F)<br />
Service life 40000 h to 40 °C<br />
Airflow 13.8 m 3 /h<br />
<strong>Electric</strong>al connection 2 poles of 2.5 mm 2<br />
Fixing Clip for the 35 mm DIN rail (EN 50022)<br />
Cover<br />
Plastic UL94 V0<br />
Operating position<br />
Vertical<br />
Operating temperature<br />
–40 to +70 °C (–10 to +158 °F)<br />
IP Protection/Class<br />
IP20II (double insulation)<br />
Certifications<br />
VDE and UL in process<br />
6/72
RCV<br />
Resistance heaters with fan<br />
Dimensions (mm)<br />
FIG. 1<br />
RCV170<br />
6/73
6/74<br />
Standard heating resistors<br />
Traditional convection
The Himel heating<br />
resistors for electrical<br />
or electronic enclosures<br />
are equipped with PTCtype<br />
heating elements<br />
(Positive Temperature<br />
Coefficient). The use of<br />
these semi-conductors<br />
as heating elements<br />
means that:<br />
c The aluminium surface<br />
temperature of the<br />
diffuser stabilises at<br />
+75 ºC (for an ambient<br />
temperature of –5 ºC).<br />
c <strong>Electric</strong>al energy<br />
consumption is<br />
reduced.<br />
The design of the profile<br />
of the Himel heating<br />
resistors produces a<br />
“chimney” effect. Thus,<br />
a uniform temperature<br />
is achieved inside the<br />
enclosure.<br />
The resistors are secured<br />
by means of fast-fixing<br />
clips on the 35 mm DIN<br />
rails.<br />
The 10 and 20 W resistors<br />
are equipped with a 2 <br />
0.75 300 mm electrical<br />
connection cable.<br />
Higher power resistors<br />
are equipped with fastconnection<br />
terminals.<br />
Their broad range of<br />
powers, from 10 to<br />
400 W, means that any<br />
solution is possible.<br />
Models from 250 and<br />
400 W with a built-in fan.<br />
6/75
RESISTANCE<br />
HEATERS<br />
Selection guide<br />
RESISTANCE HEATERS<br />
Reference Power (W) Voltage (V)<br />
Terminal block<br />
Connection type<br />
Cable<br />
RC10/12-36 10 12-36 DC X<br />
RC10 10 110-250 AC X<br />
RC20/12-36 20 12-36 DC X<br />
RC20 20 110-250 AC X<br />
RC20/270-420 20 270-420 AC X<br />
RC55/12-36 55 12-36 DC X<br />
RC55 55 110-250 AC X<br />
RC55/270-420 55 270-420 AC X<br />
RC100/12-36 90 12-36 DC X<br />
RC100 90 110-250 AC X<br />
RC100/270-420 90 270-420 AC X<br />
RC150/12-36 150 12-36 DC X<br />
RC150 150 110-250 AC X<br />
RC150/270-420 150 270-420 AC X<br />
6/76
RESISTANCE<br />
HEATERS<br />
Selection guide<br />
RESISTANCE HEATERS WITH FAN<br />
References Power (W) Voltage (V)<br />
Terminal block<br />
Connection type<br />
Cable<br />
RCV250 250 230 AC X<br />
RCV400 400 230 AC X<br />
RCV200P/115 200 115 AC X<br />
RCV200P 200 230 AC X<br />
6/77
RC / RCV / TMV<br />
Resistance heaters<br />
Resistance heaters<br />
c Range of resistance heaters from 10 to 400 W ensuring the proper heating of the<br />
enclosure to prevent condensation.<br />
General characteristics:<br />
c Extruded aluminium body.<br />
c Surface temperature limited to less than 75 °C with an ambient temperature<br />
of –5 °C.<br />
c 500 mm-long power supply cable with silicone insulation (except for the<br />
RCV400, R55, 90 and 150 models, which are equipped with a connection<br />
terminal block).<br />
Usage conditions:<br />
c The resistance heaters should be used together with a temperature<br />
regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />
installed).<br />
c The enclosure should be sealed in order to prevent the penetration of external<br />
air.<br />
c The electrical protection devices must be installed between the supply<br />
source and the resistance heaters themselves.<br />
Reference Power (W) Voltage (V) Start-up current (A) Nominal current (A) Class Dimensions (mm)<br />
RC10/12-36 10 12-36 DC II 25 50 50<br />
RC10 10 110-250 AC 0.80 0.60 II 25 50 50<br />
RC20/12-36 20 12-36 DC II 25 50 75<br />
RC20 20 110-250 AC 1 1.05 II 25 50 75<br />
RC20/270-420 20 270-420 AC II 25 50 75<br />
RC55/12-36 55 12-36 DC II 70 50 140<br />
RC55 55 110-250 AC 1.50 0.24 II 70 50 140<br />
RC55/270-420 55 270-420 AC II 70 50 140<br />
RC90/12-36 90 12-36 DC II 70 50 140<br />
RC90 90 110-250 AC 2.40 0.40 II 70 50 140<br />
RC90/270-420 90 270-420 AC II 70 50 140<br />
RC150/12-36 150 12-36 DC II 70 50 220<br />
RC150 150 110-250 AC 4.50 0.65 II 70 50 220<br />
RC150/270-420 150 270-420 AC II 70 50 220<br />
RC250 250 220-230 1.10 1.10 II 70 50 220<br />
RC400 400 220-230 1.70 1.70 II 70 50 220<br />
6/78
RC / RCV / TMV<br />
Resistance heaters<br />
Resistance heaters with fan<br />
c The fan maintains an even temperature inside the electric switchboard.<br />
Reference Power (W) Voltage (V)<br />
Start-up<br />
current (A)<br />
Nominal<br />
current (A)<br />
Class<br />
Dimensions (mm)<br />
RCV250 250 230 CA 1.20 1.20 I 180 85 95<br />
RCV400 400 230 CA 1.80 1.80 I 80 80 248<br />
Plain resistance heater with fan<br />
Reference Power (W) Voltage (V)<br />
Start-up<br />
current (A)<br />
Nominal<br />
current (A)<br />
Class<br />
Dimensions (mm)<br />
RCV200P 200 230 CA - 0.90 I 120 120 47<br />
RCV200P/115 200 115 CA - 1.80 I 120 120 47<br />
Thermofans<br />
c This device combines a the heating power of a resistor with the<br />
operation of an axial fan, offering optimal heat distribution inside the<br />
enclosure.<br />
c Fixing onto a DIN rail.<br />
c Adjustable temperature from 10 to 50 °C for TMV350, and from 0 to 60 °C<br />
for TMV350/550.<br />
TMV350<br />
c Power-on indicator lamp.<br />
Reference Power ( W) Voltage (V) Dimensions (mm)<br />
TMV350 350 230 CA 200 45 180<br />
TMV350/550 400/550 230 CA 180 85 95<br />
TMV350-550/120 400/550 120 CA 180 85 95<br />
TMV350/550<br />
6/79
Selection guide<br />
Control devices<br />
Temperature under control<br />
Compact thermostats (adjustable)<br />
NO (blue button): with normally open contact, when the temperature increases, the<br />
contact closes, activating the fan to extract the heat.<br />
NC (red button): with normally closed contact, when the temperature falls below<br />
the preset value, the contact closes, activating the resistance heater to prevent<br />
condensation.<br />
c Broad range of temperature control.<br />
c Small size.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
c Easy access terminals.<br />
c High-power connection.<br />
24 V DC electronic thermostat (adjustable)<br />
It can control 24 V direct-current electrical equipment by means of a potential-free<br />
inverter contact. Resistors, fan, etc. may be connected.<br />
They have a PTC temperature probe for more precise control and low hysteresis.<br />
c High DC switching capacity.<br />
c Low hysteresis (greater temperature precision).<br />
c Switching by means of an inverter contact.<br />
c Simple fixing by clip onto the 35 mm DIN/EN rail.<br />
Dual thermostat (adjustable)<br />
To control two units independently and simultaneously: a resistance heater and a fan.<br />
NC (red button): normally closed contact (NC) for resistance heater control.<br />
NO (blue button): normally open contact (NO) for fan control.<br />
c Double thermostats in the same housing, with separate adjustment and operation.<br />
c Easy access terminals.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
NO/NC Thermostat (adjustable)<br />
Its NO/NC inverter contact controls a resistance heater or a fan.<br />
c Switching by means of two NO/NC contacts.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
c Easy access terminals.<br />
c High-power connection.<br />
6/80
Hygrometer (adjustable)<br />
Combination of thermostat and hygrostat in the same unit to control relative<br />
humidity.<br />
The resistance heaters or fans are switched on when the two limit values are<br />
exceeded.<br />
c Adjustable temperature and relative humidity of the air.<br />
c High switching capacity.<br />
c Visual operation indication.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
c Easy access terminals.<br />
Compact fixed thermostats<br />
c Preset factory temperature:<br />
v Red button: 5, 10 and 15 °C.<br />
v Blue button: 25, 30 and 35 °C.<br />
c Small size.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
c Easy access terminals.<br />
c High-power connection.<br />
Fixed dual thermostat<br />
c To control two units independently and simultaneously:<br />
v NO/NC: fan and resistor.<br />
v NO/NO: fan and alarm.<br />
v NC /NC: resistance and alarm.<br />
c Preset factory values.<br />
c Double thermostats in the same housing, with separate operation.<br />
c Easy access terminals.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
Fixed hygrostat<br />
c Factory-adjusted relative humidity: 60% RH.<br />
c Switching by means of an NO contact.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
c Easy access terminals.<br />
c High-power connection.<br />
Hygrostat (adjustable)<br />
It is used to adjust the relative humidity in the enclosure by controlling resistance<br />
heaters or fans.<br />
The hygrostat prevents condensation and the corrosion of components.<br />
c Adjustable relative humidity.<br />
c Switching by means of an inverter contact.<br />
c Simple fixing by clip onto the 35 mm DIN rail.<br />
c Easy access terminals.<br />
c High-power connection.<br />
6/81
CONTROL<br />
DEVICES<br />
Selection guide<br />
THERMOSTATS<br />
References<br />
Power supply<br />
voltage<br />
(V)<br />
Control<br />
Contact<br />
type<br />
Application<br />
Control<br />
element<br />
Switching<br />
power<br />
(ohmic load)<br />
TS140<br />
TS140F °F NC<br />
TS141 °C NO<br />
-<br />
TS141F °F NO<br />
°C NC Resistance<br />
heaters<br />
Ventilation<br />
systems<br />
Bimetal<br />
30 W DC<br />
250 V AC 10 A<br />
120 V AC 15 A<br />
TS170 °C Switch<br />
Resistance<br />
heaters or<br />
ventilation<br />
systems<br />
250 V AC 10 A<br />
DOUBLE THERMOSTAT<br />
References<br />
Power supply<br />
voltage<br />
(V)<br />
Control<br />
Contact<br />
type<br />
Application<br />
Control<br />
element<br />
Switching<br />
power<br />
(ohmic load)<br />
TDS1401 - °C NC+NO<br />
Resistance<br />
heaters and<br />
ventilation<br />
systems<br />
Bimetal<br />
250 V AC 10 A<br />
120 V AC 15 A<br />
ELECTRONIC THERMOSTAT<br />
References<br />
Power supply<br />
voltage<br />
(V)<br />
Control<br />
Contact<br />
type<br />
Application<br />
Control<br />
element<br />
Switching<br />
power<br />
(ohmic load)<br />
TSE200 24 DC °C 2 NO<br />
Resistance<br />
heaters and<br />
ventilation<br />
systems<br />
Electronic<br />
NO or NC:<br />
24 V DC<br />
2 8 A<br />
FIXED THERMOSTAT<br />
References<br />
Fixed<br />
adjustment<br />
Contact type<br />
Application<br />
Switching power<br />
(ohmic load)<br />
TS140F5 5 °C/41 °F NC<br />
TS140F10 10 °C/50 °F NC<br />
TS140F15 15 °C/59 °F NC<br />
Resistance heaters<br />
250 V AC 10 A<br />
120 V AC 15 A<br />
DC 30 W<br />
TS141F25 25 °C/77 °F NO<br />
TS141F30 30 °C/86 °F NO<br />
TS141F35 35 °C/95 °F NO<br />
Ventilation systems<br />
250 V AC 10 A<br />
120 V AC 15 A<br />
DC 30 W<br />
6/82
CONTROL<br />
DEVICES<br />
Selection guide<br />
FIXED DUAL THERMOSTAT<br />
References Fixed adjustment Contact type<br />
Switching<br />
power<br />
(ohmic load)<br />
TSD1401F10/35<br />
TSD1401F35/45<br />
TSD1401F5/15<br />
10 °C/50 °F<br />
35 °C/95 °F<br />
35 °C/95 °F<br />
45 °C/113 °F<br />
5 °C/41 °F<br />
15 °C/59 °F<br />
NC<br />
NO<br />
NO<br />
NO<br />
NC<br />
NC<br />
250 V AC 10 A<br />
120 V AC 15 A<br />
DC 30 W<br />
HYGROMETER<br />
References<br />
Power supply<br />
voltage<br />
(V)<br />
Control<br />
Contact<br />
type<br />
Application<br />
Control<br />
element<br />
Switching<br />
power<br />
(ohmic load)<br />
THS3000 230 CA % RH, °C Switch<br />
Resistance<br />
heaters and<br />
ventilation<br />
systems<br />
Bimetal<br />
240 V AC 8 A<br />
120 V AC 8 A<br />
HYGROSTAT<br />
References<br />
Power supply<br />
voltage<br />
(V)<br />
Control<br />
Contact<br />
type<br />
Application<br />
Control<br />
element<br />
Switching<br />
power (ohmic<br />
load)<br />
HS300 - % RH Switch<br />
Resistance<br />
heaters and<br />
ventilation<br />
systems<br />
Bimetal<br />
230 V AC 5 A<br />
FIXED HYGROSTAT<br />
References Fixed adjustment Contact type<br />
HS300F60 60% RH Switch<br />
Max. control<br />
current<br />
250 V AC 5 A<br />
DC 20 W<br />
6/83
TS<br />
Control devices<br />
Thermostat TS140<br />
c Thermostat (normally closed contact (NC) for the control of resistance<br />
heaters.<br />
c Thermostat use increases service life of resistors, switching them only when<br />
required by the temperature.<br />
c Fixing onto a DIN rail.<br />
c IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Adjustable temperature from 0 to 60 °C.<br />
c Connection: 2 x 2.5 mm 2 terminals.<br />
Reference Dimensions (mm) Max. control current<br />
TS140 60 33 43 250 V 10 A<br />
TS140F 60 33 43 250 V 10 A<br />
FIG. 1<br />
Technical specifications<br />
carga load<br />
2<br />
V<br />
υ<br />
Sensor element<br />
Contact type<br />
Contact resistance<br />
Service life<br />
Bimetal<br />
Normally closed (NC), snap action contact<br />
< 10 m<br />
> 100000 cycles<br />
L<br />
N<br />
1<br />
Load Carga = resistance = resistencia<br />
Max. switching capacity<br />
250 V AC 10 A (ohmic load)<br />
120 V AC 15 A (ohmic load)<br />
250/120 V AC 2 A<br />
(inductive load cos = 0.6)<br />
DC 30 W<br />
Connection<br />
Terminals with two 2.5 mm poles<br />
Mounting Clip for the 35 mm DIN rail , EN 50022<br />
Cover<br />
V0 thermoplastic UL94, light grey<br />
Dimensions<br />
60 33 43 mm<br />
Weight<br />
40 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
–20 to +80 °C (–4 to +176 °F)<br />
Degree of protection<br />
IP20<br />
Hysteresis 7 °K<br />
Adjustable temperature From 0 to 60 °C<br />
6/84
TS<br />
Control devices<br />
Thermostat TS141<br />
c Thermostat (normally open – NO contact) for control of fans.<br />
c This thermostat allows the regulation of temperature in the enclosure,<br />
starting the fan only in case fresh air is required. As a result, service life of<br />
the fan is increased and its filter stays cleaner.<br />
c DIN rail fixing.<br />
c Degree of protection IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Adjustable temperature from 0 to 60 ºC.<br />
c Connection: 2 2.5 mm 2 terminals.<br />
Reference Dimensions (mm) Max. control current<br />
TS141 60 33 43 250 V 10 A<br />
TS141F 60 33 43 250 V 10 A<br />
FIG. 1<br />
Technical specifications<br />
carga load<br />
2<br />
Sensor element<br />
Contact type<br />
Contact resistance<br />
Bimetal<br />
Normally open (NO), snap action contact<br />
< 10 m<br />
V<br />
υ<br />
Service life<br />
> 100000 cycles<br />
L<br />
N<br />
1<br />
Load Carga = fan = ventilador<br />
250 V AC 10 A (ohmic load)<br />
Max. switching capacity<br />
120 V AC 15 A (ohmic load)<br />
250/120 V AC 2 A (inductive load cos = 0.6)<br />
DC 30 W<br />
Connection<br />
Terminals with two 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
60 33 43 mm<br />
Weight<br />
40 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
–20 to +80 °C (–4 to +176 °F)<br />
Degree of protection<br />
IP20<br />
Hysteresis 7 °K<br />
Adjustable temperature From 0 to 60 °C<br />
6/85
TS<br />
Control devices<br />
Thermostat TS170<br />
c Thermostat (contact switch) to control the fan or resistance heaters.<br />
c With this device, the internal temperature of the panel may be regulated by<br />
switching on a resistor or a fan.<br />
c Fixing on a DIN rail.<br />
c IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Adjustable temperature from 10 to 60 °C.<br />
c Connection: 4 2.5 mm 2 terminals.<br />
Reference Dimensions (mm) Max. control current<br />
TS170 67 50 44 (NA) 5 A/(NC) 10 A<br />
FIG. 1<br />
Technical specifications<br />
Load 2<br />
Load 3<br />
> <br />
Sensor element<br />
Contact type<br />
Contact resistance<br />
Service life<br />
Max. switching capacity<br />
Bimetal<br />
Switch contact, snap action<br />
< 10 m<br />
> 100000 cycles<br />
250 V AC 10 A (ohmic load)<br />
Max. opening contact<br />
250 V AC 4 A (inductive load cos = 0.6)<br />
DC 30 W<br />
L<br />
N<br />
Load (2) =resistance<br />
Load (3) = fan<br />
Connection<br />
Terminals with four 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
67 50 44 mm<br />
Weight<br />
100 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
–20 to +80 °C (–4 to +176 °F)<br />
Degree of protection<br />
IP20<br />
Hysteresis 7 °K<br />
Adjustable temperature From 5 to 60 °C<br />
6/86
TS<br />
Control devices<br />
Dual thermostat TSD1401<br />
c Dual temperature regulator.<br />
c Two thermostats in one single enclosure.<br />
c Separate control and operation.<br />
c Fixing clip for the 35 mm DIN rail.<br />
c IP20.<br />
c Dual thermostat (two thermostats in one single box). With the red button<br />
(normally closed contact- NC), the resistance heater can be regulated.<br />
A fan, signalling system or alarm can be controlled with the blue button<br />
(normally open contact- NO).<br />
This thermostat allows the simultaneous control of a resistance heater and a<br />
fan, making an independent temperature adjustment possible.<br />
Reference Dimensions (mm) Max. control current<br />
TSD1401 67 50 44<br />
250 V AC 10 A<br />
120 V AC 15 A<br />
FIG. 1<br />
N1 L1 11<br />
Technical specifications<br />
Sensor element<br />
Bimetal<br />
A<br />
12<br />
V<br />
Contact type<br />
Contact resistance<br />
Service life<br />
1 normally open (NO), 1 normally closed (NC), snap action<br />
< 10 m<br />
> 100000 cycles<br />
N2<br />
L2<br />
B<br />
23<br />
24<br />
V<br />
Max. switching capacity<br />
250 V AC 10 A (ohmic load)<br />
120 V AC 15 A (ohmic load)<br />
250/120 V AC 2 A<br />
(inductive load cos = 0,6)<br />
DC 30 W<br />
Connection<br />
Terminals with six 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
67 50 44 mm<br />
Weight<br />
90 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
–20 to +80 °C (–4 to +176 °F)<br />
Degree of protection<br />
IP20<br />
Hysteresis 7 °K<br />
Adjustable temperature From 0 to 60 °C<br />
6/87
TS<br />
Control devices<br />
Thermostat TSE200<br />
c Electronic temperature regulator.<br />
c 24 V DC supply.<br />
c Fixing by clip for 35 mm DIN rail.<br />
c IP20.<br />
c Thermostat with volt-free 2 dry contact switching relay.<br />
c Allows high number of switching operations with improved temperature<br />
accuracy (± 2 °K) thanks to its PTC probe.<br />
c The miniature communication relays installed in the thermostat are powerful<br />
(230 A) and safe.<br />
c Possibility of having a thermostat with open-contact switches or inverted<br />
switches.<br />
Reference Dimensions (mm) Max. rated current<br />
TSE200 67 50 44<br />
NA o NC:<br />
24 V DC 2 8 A<br />
FIG. 1<br />
Technical specifications<br />
+24 V<br />
_<br />
+<br />
11<br />
12<br />
21<br />
V<br />
Adjustable temperature From 0 to +60 °C<br />
Hysteresis 2 °K ± 2 °K<br />
Sensor element<br />
PTC probe<br />
Connection<br />
Terminals with six 2.5 mm 2 poles<br />
Contact type<br />
2 normally open (NO), snap action contact<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
ABS according to UL94 V0<br />
22<br />
Operating temperature<br />
0 to +60 °C (–32 to +140 °F)<br />
Degree of protection<br />
Dimensions<br />
Weight<br />
IP20<br />
67 50 44 mm<br />
80 g<br />
6/88
TS<br />
Control devices<br />
Fixed thermostats TS140F<br />
c Thermostat (normally closed contact - NC) to control resistance heaters.<br />
c DIN rail fixing.<br />
c Degree of protection IP20.<br />
c V0 self-extinguishing thermoplastic material as per UL94.<br />
c Factory-adjusted temperature.<br />
c Connection: 2 2.5 mm 2 terminals.<br />
Reference Fixed adjustment Max. control current<br />
TS140F5 5 °C/41 °F<br />
TS140F10 10 °C/50 °F<br />
TS140F15 15 °C/59 °F<br />
250 V AC 10 A 120 V AC 15 A<br />
DC 30 W<br />
FIG. 1<br />
Technical specifications<br />
Load carga1<br />
2<br />
V<br />
υ<br />
Sensor element<br />
Contact type<br />
Contact resistance<br />
Service life<br />
Bimetal<br />
Normally closed (NC), snap action contact Normally closed (NC),<br />
snap action contact<br />
< 10 m<br />
> 100000 cycles<br />
L<br />
N<br />
Load Carga = resistance = resistencia<br />
1<br />
Max. switching capacity<br />
250 V AC 10 A (ohmic load)<br />
120 V AC 15 A (ohmic load)<br />
250/120 V AC 2 A<br />
(inductive load cos = 0.6)<br />
DC 30 W<br />
Connection<br />
Terminals with two 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail 35 mm, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
60 33 43 mm<br />
Weight<br />
40 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
Degree of protection<br />
–20 to +80 °C (–4 to +176 °F)<br />
IP20<br />
6/89
TS<br />
Control devices<br />
Fixed thermostats TS141F<br />
c Thermostat (normally open - NO contact) to control fans.<br />
c Degree of protection IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Factory-adjusted temperature.<br />
c Connection: 2 2.5 mm 2 terminals.<br />
c DIN rail fixing.<br />
Reference Fixed adjustment Max. control current<br />
TS141F25 25 °C/77 °F 250 V AC 10 A<br />
TS141F30 30 °C/86 °F<br />
120 V AC 15 A<br />
TS141F35 35 °C/95 °F<br />
DC 30 W<br />
FIG. 1<br />
Technical specifications<br />
Sensor element Bimetal<br />
carga<br />
2<br />
V<br />
υ<br />
Contact type Normally open (NO), snap action contact<br />
Contact resistance<br />
< 10 m<br />
Service life<br />
> 100000 cycles<br />
L<br />
N<br />
Load<br />
Carga<br />
= fan<br />
= ventilador<br />
1<br />
250 V AC 10 A (ohmic load)<br />
Max. switching capacity<br />
120 V AC 15 A (ohmic load)<br />
250/120 V AC 2 A (inductive load cos = 0.6)<br />
DC 30 W<br />
Connection<br />
Terminals with two 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
60 33 43 mm<br />
Weight<br />
40 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
–20 to + 80 °C (–4 to +176 °F)<br />
Degree of protection<br />
IP20<br />
Hysteresis 7 °K<br />
6/90
TS<br />
Control devices<br />
Fixed dual thermostat TSD1401F<br />
c Dual temperature regulator.<br />
c Two thermostat in one enclosure with separated setting and operation.<br />
c 35 mm DIN rail clip fixing.<br />
c Factory-adjusted temperature.<br />
c This unit allows trip control of a fan and a resistance heater, independent<br />
setting and operation.<br />
Reference Contact type Fixed adjustment<br />
TSD1401F10/35<br />
TSD1401F35/45<br />
TSD1401F5/15<br />
NC:<br />
NO:<br />
NO:<br />
NO:<br />
NC:<br />
NC:<br />
10 ºC/50 ºF<br />
35 ºC/95 ºF<br />
35 ºC/95 ºF<br />
45 ºC/113 ºF<br />
5 ºC/41 ºF<br />
15 ºC/59 ºF<br />
Technical specifications<br />
FIG. 1<br />
N1 L1 11<br />
Sensor element<br />
Contact type<br />
Contact resistance<br />
Service life<br />
Bimetal<br />
Snap action<br />
< 10 m<br />
> 100000 cycles<br />
N2<br />
L2<br />
A<br />
B<br />
12<br />
23<br />
24<br />
V<br />
V<br />
Max. switching capacity<br />
250 V AC 10 A (ohmic load)<br />
120 V AC 15 A (ohmic load)<br />
250/120 V AC 2 A (inductive load<br />
cos = 0.6)<br />
DC 30 W<br />
Connection<br />
Terminals with six 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
67 50 44 mm<br />
Weight<br />
90 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
–20 to +80 °C (–4 to +176 °F)<br />
Degree of protection<br />
IP20<br />
Hysteresis 7 °K<br />
6/91
TS<br />
Control devices<br />
Hygrometer THS3000<br />
c The device independently measures the temperature and humidity within<br />
the electrical enclosure. The resistance heater is switched on when either of<br />
the limiting values set for the two parameters is exceeded: the temperature<br />
rises and the relative humidity RH falls. The hygrometer switch should be<br />
preferably be installed in the upper part of the enclosure at a minimum<br />
distance of 50 cm from the resistance heater.<br />
c DIN rail fixing.<br />
c Degree of protection IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Adjustable temperature from 0 to 60 ºC.<br />
c Adjsutable relative humidity from 50 to 90%.<br />
FIG. 1<br />
c Hysteresis: 2 °C, 3% RH.<br />
c Service life: >100000 cycles.<br />
Reference Dimensions (mm) Max. control current<br />
T°<br />
RH<br />
THS3000 67 50 43<br />
250 V AC 8 A<br />
12 V DC 8 A<br />
35 V DC 5 A<br />
1 2 3 4 5<br />
Carga Load<br />
L 230 V<br />
50 Hz<br />
N<br />
Technical specifications<br />
Power supply voltage<br />
230 V AC 50/60 Hz<br />
Switching precision<br />
Temperature 2 °K (±1 °K)<br />
Switching precision Humidity 4% (±1%)<br />
Response time<br />
Approx. 160 sec.<br />
Contact type<br />
Switch<br />
Contact resistance<br />
< 10 m<br />
Service life<br />
> 100000 cycles<br />
Max. switching capacity<br />
240 V AC 8 A (ohmic load)<br />
240/120 V AC 4 A<br />
(inductive load cos = 0.6)<br />
240 V DC 0.1 A<br />
48 V DC 0.8 A<br />
24 V DC 8 A<br />
Connection<br />
Terminals with five 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
67 50 43 mm<br />
Weight<br />
200 g<br />
Fitting position<br />
Vertical<br />
Operating temperature<br />
Degree of protection<br />
Power-on indicator<br />
–20 to +60 °C (–4 to +140 °F)<br />
IP20<br />
LED<br />
6/92
TS<br />
Control devices<br />
Hygrostat HS300<br />
c This device only measures the relative humidity inside the enclosure.<br />
c It is used to switch on the resistance heater when the humidity rises above<br />
the set value.<br />
c DIN rail fixing.<br />
c Degree of protection IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Adjustable relative humidity from 30 to 90%.<br />
Reference Dimensions (mm) Max. control current<br />
HS300 67 50 37 250 V AC 5 A<br />
FIG. 1<br />
Technical specifications<br />
Control<br />
35% to 95% RH<br />
Switching precision Humidity 4% (±3%)<br />
carga Load 1<br />
3<br />
Permissible air velocity<br />
15 m/sec<br />
carga Load 2<br />
1<br />
4<br />
V<br />
ϕ<br />
Contact type<br />
Contact resistance<br />
Service life<br />
Switch<br />
< 10 m<br />
50000 cycles<br />
Min. switching power<br />
20 V AC/DC 100 mA<br />
L<br />
N<br />
Load Carga 1 = 1 resistance = resistencia (dehumidifier) (deshumidificador)<br />
Load Carga 2 = 2 humidifier = humidificador<br />
Max. switching capacity<br />
230 V AC 5 A (ohmic load)<br />
230/120 V AC 0.2 A<br />
(inductive load cos Ø = 0.6<br />
50 V DC 1 A/75 V DC 0.5 A<br />
(inductive load L/R = 3 ms)<br />
Connection<br />
Terminals with three 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail , EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
67 50 37 mm<br />
Weight<br />
100 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
Degree of protection<br />
–20 to +60 °C (–4 to +140 °F)<br />
IP20<br />
6/93
TS<br />
Control devices<br />
Fixed hygrostat HS300F<br />
c This device only measures the relative humidity inside the enclosure.<br />
c It can be used to start up a resistance heater when this relative humidity<br />
exceeds the preset value.<br />
c DIN rail fixing.<br />
c Degree of protection IP20.<br />
c V0 self-extinguishing thermoplastic as per UL94.<br />
c Factory-adjusted relative humidity.<br />
Reference Fixed adjustment Max. control current<br />
HS300F60<br />
60% RH<br />
250 V AC 5 A<br />
DC 20 W<br />
FIG. 1<br />
Technical specifications<br />
Switching precision Humidity 4% (±3%)<br />
carga 1<br />
3<br />
Permissible air velocity<br />
15 m/sec<br />
carga 2<br />
1<br />
4<br />
V<br />
ϕ<br />
Contact type<br />
Contact resistance<br />
Service life<br />
Switch<br />
< 10 m<br />
50000 cycles<br />
L<br />
N<br />
Load 1 = resistance (dehumidifier)<br />
Carga 1 = resistencia (deshumidificador)<br />
Load<br />
Carga<br />
2<br />
2<br />
=<br />
=<br />
humidifier<br />
humidificador<br />
Min. switching power<br />
Max. switching capacity<br />
20 V AC/DC 100 mA<br />
250 V AC 5 A (ohmic load)<br />
250 V AC 0,2 A (inductive load cos = 0.6)<br />
DC 20 W<br />
Connection<br />
Terminals with three 2.5 mm 2 poles<br />
Mounting Clip for the 35 mm DIN rail, EN 50022<br />
Cover<br />
V0 UL94 thermoplastic, light grey<br />
Dimensions<br />
67 50 37 mm<br />
Weight<br />
100 g<br />
Fitting position<br />
Non-defined<br />
Operating temperature<br />
Degree of protection<br />
–20 to +60 °C (–4 to +140 °F)<br />
IP20<br />
6/94
HEAT CALCULATION<br />
Thermal management for electrical control panels<br />
Due to the miniaturisation of the components, the generalisation of electronics,<br />
and the appearance of new electronically-based power products, temperature<br />
control has become an increasingly important necessity that must be taken<br />
into account when designing electrical and/or electronic control panels, as is<br />
being done with the IP degree of protection.<br />
Reliability and the search for minimal breakdown rates are two determining<br />
factors in process industries where hourly operation costs for the installations<br />
are extremely high; the smallest breakdown can immediately result in<br />
losses totalling hundreds of thousands of pesetas. The service life of the<br />
components depends on the temperature and humidity conditions in the<br />
enclosure.<br />
The solutions to these problems are varied, and can depend on environmental<br />
conditions, the type of components in the electrical control panel<br />
and, of course, their cost!<br />
In certain cases, it is enough to oversize the enclosure or to use fans. In<br />
other cases, where ambient temperatures are higher, heat exchangers or<br />
cooling units must be used.<br />
Himel offers a wide range of solutions adapted to all situations.<br />
To air<br />
Natural dissipation (through the enclosure walls).<br />
In some cases, using a larger enclosure can solve the heating problem.<br />
Natural ventilation<br />
Providing fresh exterior air through ventilation outlet grilles improves heat<br />
dissipation through natural convection.<br />
Nevertheless, this solution can only be used in low-dust environments when<br />
the power to be dissipated is low.<br />
If At > Dt<br />
If At < Dt<br />
At = ambient temperature.<br />
Dt = internal desired temperature.<br />
6/95
HEAT CALCULATION<br />
Thermal management for electrical control panels<br />
To ventilate<br />
Ventilation<br />
Using a fan to circulate air within the enclosure can even out the temperature<br />
and prevent hot spots which could be harmful to certain components.<br />
Forced ventilation<br />
HIMEL fans are designed to remove large quantities of heat generated by<br />
electrical control panel components. This signifi cantly increases component<br />
longevity, thus ensuring the durability and correct operation of the installation.<br />
The fans, which are easy to install and maintain, as well as economical, are<br />
an effective solution to the problem of rising temperatures in electrical control<br />
panels.<br />
Due to their IP degree of protection, they can be used both in industrial<br />
environments and in the tertiary sector.<br />
To cool<br />
Air/air exchangers<br />
HIMEL air-air exchangers combine performance and simplicity: the movement<br />
of hot air from the enclosure and cool air from the surrounding environment<br />
by means of two fans circulating on either side of sealed divider walls<br />
prevents dust and humidity from penetrating the enclosure. Warm air from the<br />
panel heats these walls, which are then cooled by the colder external air. The<br />
heat transfer always takes place from the warmer to the cooler area. For this<br />
reason, these devices can only be used if the ambient temperature is at least<br />
5ºC lower than the required internal temperature of the enclosure.<br />
The aluminium exchange battery is at the heart of the system. This element<br />
can be cleaned as it is easily removed.<br />
In addition, the continuous operation of an internal fan prevents hot spots<br />
in the electrical control panel. The temperature is regulated by switching the<br />
external circuit fan on and off.<br />
Undesired effects on the components installed in poorly-cooled environments.<br />
6/96
HEAT CALCULATION<br />
Thermal management for electrical control panels<br />
To cool<br />
Air/water exchangers<br />
The operating principle of HIMEL air/water exchangers is similar to that of the<br />
air/air exchangers: the cool external air is replaced by cold water supplied by<br />
the piping of the installation itself on the industrial site.<br />
Due to this fl uid exchange, much larger quantities of heat can be removed,<br />
and the temperature within the electrical control panel can be adjusted to<br />
below that of the ambient air.<br />
Temperature within the panel is regulated by modulating the water fl ow.<br />
The water circuit is protected by a supply shut-off device ensuring the safety<br />
of your electrical installation.<br />
Cooling units<br />
HIMEL cooling units can be used in the most severe environments, where<br />
temperatures can reach 55ºC. These units are particularly suitable when<br />
the required temperature of the enclosure must be lower than the ambient<br />
temperature, or when large quantities of heat must be removed. As in the<br />
case of the exchangers, they do not affect the IP rating of the panel.<br />
Due to the fi lter located at the intake of the external air circuit, they can<br />
operate even when the ambient air is very dusty or greasy. This device is easy<br />
to replace and ensures that the effi ciency of the equipment is maintained<br />
throughout its entire service life.<br />
The cooling units have an enclosure temperature control system and an alarm<br />
function which is triggered in the event of a malfunction.<br />
To heat<br />
Resistance heaters<br />
There are two reasons to use resistance heaters:<br />
c To heat the electrical control enclosure when the ambient temperature is<br />
too low for the components to operate correctly.<br />
c To prevent water condensation from forming.<br />
Condensation can cause short circuits, premature contact oxidation,<br />
corrosion of metal parts (particularly those of the enclosure), and it can<br />
signifi cantly reduce the service life of electrical and electronic components.<br />
Condensation occurs when the temperature quickly drops below the dew<br />
point. This can be prevented by simply maintaining the temperature within the<br />
enclosure at a few degrees above the ambient temperature.<br />
The design of the HIMEL heaters facilitates natural convection and ensures a<br />
both uniform and rapid heating of the enclosure.<br />
6/97
HEAT CALCULATION<br />
Thermal calculation and mounting suggestions<br />
Determining the temperature control equipment<br />
The temperature control calculation consists of comparing the power<br />
dissipated by the operating components with the power exchanged<br />
spontaneously by the enclosure walls. It enables calculation of the internal<br />
temperature in the enclosure without use of a temperature control system and<br />
therefore determination of whether or not one should be installed, taking into<br />
account the required external and internal temperatures.<br />
The following presents a simple method of making such a selection.<br />
Example: OLN<br />
Ref.: OLN208/40<br />
Height = 2000<br />
Width = 800<br />
Depth = 400<br />
1 ENCLOSURE CHARACTERISTICS<br />
Enclosure<br />
position<br />
Placement as specified by IEC 890<br />
Accessible from all sides<br />
Formula for calculation of S (m 2 )<br />
(A)<br />
Height<br />
(B)<br />
Width<br />
(C)<br />
Depth<br />
S = 1.8 A (B+C) + 1.4 B C<br />
Placed against a wall.<br />
S = 1.4 B (A+C) + 1.8 C A<br />
End, in the case of coupling<br />
End, in the case of coupling and placed against<br />
a wall<br />
Intermediate in the case of coupling<br />
S = 1.4 C (A+B) + 1.8 B A<br />
S = 1.4 A (B+C) + 1.4 B C<br />
S = 1.8 3 B 3 A + 1.4 3 B 3 C + C 3 A<br />
Installation type:<br />
enclosure placed against<br />
a wall.<br />
S = 4.13 m 2<br />
Intermediate in the case of coupling and placed<br />
against a wall<br />
Intermediate in the case of coupling and placed<br />
against a wall with the upper part covered<br />
S = 1.4 B (A+C) + C A<br />
S = 1.4 B A + 0.7 B C + C A<br />
S = m 2<br />
Assume that the components<br />
dissipate 800 W.<br />
Pd = 800 W<br />
2 POWER DISSIPATED BY OPERATING COMPONENTS<br />
This is obtained by totalling the power dissipated by each component<br />
installed.<br />
If the individual values are unknown, use the tables on page which provide<br />
average values.<br />
Pd = W<br />
Temperature conditions<br />
are as follows:<br />
Te max<br />
= 35 °C<br />
Te mín<br />
= 15 °C<br />
3 CHARACTERISTICS OF AMBIENT AIR<br />
Maximum ambient temperature.<br />
Minimum ambient temperature.<br />
Average relative humidity.<br />
Te max<br />
= °C<br />
Te mín<br />
= °C<br />
Td max<br />
= 40 °C<br />
Td mín<br />
= 15 °C<br />
Cooling is required<br />
Ti max<br />
= 70 °C<br />
Ti mín<br />
= 15 °C<br />
4 REQUIRED INTERNAL AVERAGE TEMPERATURES<br />
These are characterised by the type of components and the characteristics<br />
of the ambient air.<br />
Maximum internal temperature (desired).<br />
Minimun internal temperature (desired).<br />
Td mín<br />
Td max<br />
=<br />
=<br />
°C<br />
°C<br />
5 FINAL ENCLOSURE TEMPERATURE WITHOUT TEMPERATURE CONTROL SYSTEM<br />
Maximum internal temperature Ti Pd<br />
max<br />
= + Te<br />
K S max<br />
Ti mín<br />
= °C<br />
Minimun internal temperature Ti min<br />
= Te min<br />
(voltage-free panel).<br />
K = 5.5 W/m 2 ºK for a metal enclosure.<br />
K = 3.5 W/m 2 ºK for a polyester enclosure.<br />
K = 3.7 W/m 2 ºK for a stainless steel enclosure.<br />
K = 12 W/m 2 ºK for an aluminium enclosure.<br />
Ti max<br />
= °C<br />
6/98
HEAT CALCULATION<br />
Thermal calculation and mounting suggestions<br />
6 DETERMINATION OF THE TYPE OF TEMPERATURE CONTROL SYSTEM AND ITS POWER PSYST<br />
Td mín<br />
< Ti mín<br />
Td mín<br />
> Ti mín<br />
Td max<br />
< Ti max<br />
Td max<br />
> Ti max<br />
Temperature control system not required,<br />
but circulation fan could be installed to<br />
even out temperature.<br />
Temperature control system required:<br />
resistance heater.<br />
1 Permanent switchboard operation<br />
Psyst = K S (Td mín<br />
– Te mín<br />
) – Pd<br />
2 Intermittent operation:<br />
Temperature control system required: either<br />
fan, exchanger or cooling unit.<br />
Psis = Pd – K S (Td max<br />
– Te max<br />
)<br />
Psis = 800 – 5.5 4.13 (40 – 35) ± 690 W<br />
Temperature control system not required, but a<br />
circulation fan could be installed to eliminate hot<br />
spots.<br />
Psyst = K S (Td mín<br />
– Te mín<br />
)<br />
Ventilating<br />
Temperature conditions Solution Advantages of solution Constraints of solution<br />
Avoid hot spots. Install circulation fans in the enclosure. Highly economical maintenance-free<br />
solution. Simple installation. Installation IP<br />
maintained.<br />
Quantity of heat removed is relatively low.<br />
Cooling<br />
Temperature conditions Solution Advantages of solution Constraints of solution<br />
Oversize the enclosure.<br />
Economical maintenance-free solution.<br />
Simple installation. Installation IP<br />
maintained.<br />
Quantity of heat removed is relatively low.<br />
Increased dimensions.<br />
Final temperature required in the enclosure<br />
Ts (max) at least 5 °C higher than the<br />
maximum ambient temperature Te (max).<br />
Install ventilation louvres.<br />
Highly economical maintenance-free<br />
solution. Simple installation.<br />
Quantity of heat removed is low, depending on<br />
arrangement of components. IP downgraded<br />
(dust penetration).<br />
Td max ≥ Te max + 5 °C<br />
Install fresh air inlet fans.<br />
D =<br />
Psyst<br />
3.1 m 3 /h<br />
(Tsmax-Temax)<br />
Economical maintenance-free solution,<br />
simple to install. Quantity of heat removed<br />
high. Temperature control possible.<br />
Regular filter maintenance. IP slightly<br />
downgraded.<br />
Use an air/air exchanger.<br />
q =<br />
Psyst<br />
wk<br />
(Tsmax-Temax)<br />
Simple installation. Installation IP<br />
maintained. Temperature control as<br />
standard. Simple maintenance.<br />
Regular filter maintenance.<br />
Final temperature required in the enclosure<br />
Ts (max) at least 5 ºC lower than the<br />
maximun ambient temperature Te (max).<br />
Use a cooling unit.<br />
Simple installation. Enables evacuation<br />
of large quantities of heat, even when<br />
ambient temperature is high. Installation IP<br />
maintain. Temperature regulation.<br />
Regular filter maintenance. Can not be used<br />
above ambient temperature 55 °C.<br />
Td max ≤ Te max + 5 °C<br />
Use an air/water exchanger.<br />
Simple installation. Enables evacuation<br />
of large quantities of heat, even when<br />
ambient temperature is high. Installation IP<br />
maintain. Temperature control as standard.<br />
No filter to maintain.<br />
Water circuit required. Water consumption cost<br />
if mains supply used.<br />
Heating<br />
Temperature conditions Solution Advantages of solution Constraints of solution<br />
External temperature lower than the<br />
minimum temperature admissible by<br />
components.<br />
Condensation risk.<br />
Heating by resistance heater.<br />
Heating by resistance heater to maintain<br />
temperature above the dew point<br />
temperature.<br />
Economical, reliable.Temperature in<br />
enclosure can be controlled.<br />
Economical, reliable, Humidity in enclosure<br />
can be controlled.<br />
Energy consumption. Space occupied in<br />
enclosure.<br />
Energy consumption. Space occupied in<br />
enclosure.<br />
6/99
ClimaSys: calculation support service<br />
PROclima 4.0<br />
PROclima 4.0<br />
We have developed the PROclima programme to facilitate the calculation<br />
and selection of temperature control equipment for enclosures containing<br />
electrical or electronic equipment.<br />
The programme calculates the thermal balance inside the enclosure and<br />
recommends the most suitable solution based on the values entered.<br />
Data entry<br />
Entry of the data for the installation necessary to calculate the “thermal<br />
balance”.<br />
The steps to follow are:<br />
1 Input of the project and customer data.<br />
2 Input of the temperature data.<br />
3 Input of the electrical data of the installation (voltage for selecting the<br />
solution and intensity for the calculation of the dissipation in the busbars).<br />
4 Input of the power dissipated by the electrical components inside the<br />
enclosure; if the programme is not known, provide the means for its<br />
calculation:<br />
– By entering the type and quantity of the installed components.<br />
– In the case of manoeuvres during operation, by reading the interior/exterior<br />
temperature.<br />
5 Select the enclosure model and the method of installation.<br />
Results<br />
6 Select the control system (fans, exchangers, etc.).<br />
7 View and print the result.<br />
Printing and drawing up of the thermal study report<br />
Once the calculation has been made, a report can be printed, which details<br />
all the calculation data, the results obtained, as well as the equipment<br />
recommended to maintain the internal temperature of the enclosure under the<br />
conditions indicated.<br />
The report provides the machining template to scale, as well as the<br />
dimensions and electrical characteristics of the recommended equipment.<br />
6/100
1 Input the project and customer<br />
data (optional).<br />
5 Select the enclosure model<br />
and the method of installation<br />
(compulsory).<br />
2 Input the internal and external<br />
temperature data of the enclosures<br />
(compulsory).<br />
6 Select the control system (fans,<br />
exchangers, etc.) (compulsory).<br />
3 Input the electrical data of the<br />
installation (compulsory).<br />
4 Input the power dissipated by the<br />
electrical components inside the<br />
enclosure (compulsory).<br />
7 View and print the result.<br />
6/101
HEAT CALCULATION<br />
Calculation support software<br />
Calculation and selection assistance software<br />
PROclima software<br />
c Calculation and selection programme for temperature control equipment for<br />
enclosures containing electrical or electronic equipment.<br />
c The programme performs the calculations presented on pages 6/98 and<br />
6/99, as well as the dissipation surface areas, based on the dimensions of<br />
the enclosure and its position with respect to the walls.<br />
c Available on CD-ROM in two languages: Spanish and English.<br />
c Minimum requirements: PC that is IBM PC 486 SX compatible, 33 MHz,<br />
with 8 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA<br />
graphics card (640 480 pixels).<br />
c Recommended requirements: PC that is IBM Pentium 90 MHz compatible,<br />
with 16 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA<br />
graphics card (800 600 pixels).<br />
c Required components: Microsoft DOS version 5.0 or later, Microsoft<br />
Windows version 3.1 or later, Microsoft Windows NT version 3.51.944 or<br />
later.<br />
Project phases with the PROclima software<br />
c General project data.<br />
Customer, technical manager, name, place, and date of project.<br />
c Selection of enclosure model.<br />
Range, dimensions, placement.<br />
c Temperature data:<br />
v Minimum and maximum temperatures, possible external temperatures.<br />
v Minimum and maximum temperatures desired inside the enclosure.<br />
v Altitude.<br />
v Relative humidity.<br />
c Dissipated power assessment.<br />
It is theoretically known or can be recreated from a database:<br />
v Enter the dissipated power of the components.<br />
v And/or select all the electrical and electronic elements installed inside the<br />
enclosure to then calculate an approximate value.<br />
The thermal balance consists of comparing the energy dissipated by the<br />
components of the installation with the energy dissipated spontaneously by<br />
the walls of the enclosure.<br />
It makes it possible to defi ne the external temperature of the enclosure<br />
without a temperature control element and to justify the installation of<br />
equipment.<br />
c Selection of the temperature control element.<br />
A screen makes it possible to select the control system (fan, exchanger,<br />
cooling unit, resistance heaters) to proportion with the programme.<br />
After the calculation, the power, specifi cations, and reference numbers<br />
of the temperature control element and the respective accessories are<br />
needed.<br />
The programme provides a project summary that can be printed.<br />
6/102
HEAT CALCULATION<br />
Calculation example<br />
Data<br />
Enclosure characteristics<br />
c Dimensions<br />
Height: 2000 mm<br />
Width: 800 mm<br />
Depth: 500 mm<br />
c Location: against a wall<br />
c Material: enclosure in painted sheet steel<br />
c Thermal power dissipated by operating components<br />
Pd: 950 W<br />
c Environment and temperature data:<br />
Maximum temperature expected outside the enclosure<br />
Te max<br />
: 25 ºC<br />
Minimum temperature expected outside the enclosure<br />
Te min<br />
: 25 ºC<br />
Minimum temperature dissipated inside the enclosure<br />
Te max<br />
: 35 ºC<br />
Minimum temperature dissipated outside the enclosure<br />
Te min<br />
: 25 ºC<br />
Atmosphere characteristics: little pollution with low dust levels<br />
Selection and calculation:<br />
The maximum required temperature (Ts max<br />
) inside the enclosure is 10 ºC higher<br />
than the maximum value expected outside (Ti max<br />
).<br />
It is possible to cool the enclosure using fi ltered ventilation systems.<br />
Calculation of the fan required:<br />
Usage formulas:<br />
Psis = Pd – (k S (Ts max<br />
– Te max<br />
)<br />
Flow = f Psis / (Td max<br />
– Te max<br />
)<br />
Pd: thermal power dissipated by operating components<br />
S = 1.4 L (H+P) + 1.8 P H = 4.6 m 2 . Conforming to standard IEC 890.<br />
K = Constant defi ned by the material used to construct the enclosure<br />
K = 5.5 W/m 2 ºC for a painted steel sheet enclosure<br />
K = 3.5 W/m 2 ºC for a polyester enclosure<br />
K = 3.7 W/m 2 ºC for a stainless steel enclosure<br />
For the calculation, it is necessary to know the altitude above sea level of the installation site:<br />
Altitude above sea level: 800 m<br />
f = Coeffi cient related to the altitude above sea level (value)<br />
0 to 100 m f = 3.1<br />
100 to 250 m f = 3.2<br />
250 to 500 m f = 3.3<br />
500 to 750 m f = 3.4<br />
750 to 1000 m f = 3.5<br />
................<br />
In our example:<br />
Psis = 950 – 5.5 4.6 (35 – 25) = 497 W<br />
Flow = 3.5 697/(35 – 25) = 244 m 3 /h<br />
Selecting from the quick-selection table of fans<br />
1 fan with standard VF300 fi lter + 1 outlet grille with standard FS615 + fi lter<br />
1 thermostat TS141F35<br />
They provide a 302 m 3 /h fl ow rate<br />
The minimum expected exterior temperature is less than the minimum required temperature<br />
inside the enclosure.<br />
It is necessary to install resistance heaters:<br />
Calculation of the resistance necessary:<br />
Usage formulas:<br />
W = 5.5 4.6 (15 – 10) = 127 W<br />
In our example:<br />
W = 5.5 4.6 (15 – 10) = 127 W<br />
Selecting from the quick-selection table of resistance heaters<br />
1 resistance heater Ref. RC150AI + 1 thermostat Ref. TS140F15<br />
6/103
HEAT CALCULATION<br />
Dissipation surface area<br />
Dissipation surface area of the metal<br />
enclosures: CRN-CRNG<br />
Accessible on all sides<br />
Installation mode<br />
Against a wall<br />
At one end of a row<br />
At one end of a row, against a wall<br />
Intermediate in a row<br />
Intermediate in a row, against a wall<br />
Intermediate in a row, against a wall,<br />
closed covered top<br />
Enclosure model<br />
CRN / CRNG<br />
Dimensions in mm<br />
A B C<br />
Type of installation conforming to IEC 890<br />
■ 250 200 150 0.20 0.18 0.18 0.16 0.17 0.15 0.13<br />
■ 300 250 150 0.27 0.24 0.25 0.22 0.23 0.20 0.18<br />
■ 300 250 200 0.31 0.28 0.29 0.26 0.27 0.24 0.20<br />
■ 300 300 150 0.31 0.27 0.29 0.25 0.27 0.23 0.20<br />
■ 300 300 200 0.35 0.32 0.33 0.29 0.31 0.27 0.23<br />
■ 300 400 200 0.44 0.39 0.41 0.40 0.39 0.34 0.28<br />
■ 400 300 150 0.39 0.34 0.36 0.32 0.34 0.29 0.26<br />
■ 400 300 200 0.44 0.40 0.41 0.36 0.38 0.33 0.29<br />
■ 400 400 200 0.54 0.48 0.51 0.45 0.48 0.42 0.36<br />
■ 400 600 250 0.82 0.73 0.78 0.69 0.74 0.65 0.54<br />
■ 400 600 300 0.90 0.80 0.85 0.76 0.80 0.71 0.58<br />
■ 500 400 150 0.58 0.50 0.55 0.47 0.52 0.44 0.40<br />
■ 500 400 200 0.65 0.57 0.61 0.53 0.57 0.49 0.44<br />
■ 500 400 250 0.73 0.65 0.68 0.60 0.63 0.55 0.48<br />
■ 500 500 250 0.85 0.75 0.80 0.70 0.75 0.65 0.56<br />
■ 600 400 150 0.68 0.58 0.64 0.55 0.61 0.51 0.47<br />
■ 600 400 200 0.76 0.66 0.71 0.62 0.66 0.57 0.51<br />
■ 600 400 250 0.84 0.75 0.78 0.69 0.72 0.63 0.56<br />
■ 600 500 150 0.81 0.69 0.77 0.65 0.74 0.62 0.56<br />
■ 600 500 200 0.90 0.78 0.85 0.73 0.80 0.68 0.61<br />
■ 600 500 250 0.99 0.87 0.93 0.81 0.87 0.75 0.66<br />
■ 600 600 250 1.13 0.98 1.07 0.92 1.01 0.86 0.76<br />
■ 600 600 300 1.22 1.08 1.15 1.01 1.08 0.94 0.81<br />
■ 600 800 300 1.52 1.33 1.45 1.36 1.38 1.19 1.02<br />
■ 700 500 200 1.02 0.88 0.97 0.83 0.91 0.77 0.70<br />
■ 700 500 250 1.12 0.98 1.05 0.91 0.98 0.84 0.75<br />
■ 800 600 200 1.32 1.13 1.26 1.06 1.19 1.00 0.92<br />
■ 800 600 250 1.43 1.24 1.35 1.16 1.27 1.08 0.98<br />
■ 800 600 300 1.55 1.36 1.45 1.26 1.36 1.16 1.04<br />
■ 800 800 200 1.66 1.41 1.60 1.34 1.54 1.28 1.17<br />
■ 800 800 300 1.92 1.66 1.82 1.57 1.73 1.47 1.30<br />
■ 800 1000 300 2.29 1.97 1.45 1.36 1.38 1.19 1.02<br />
■ 1000 600 250 1.74 1.50 1.64 1.40 1.54 1.30 1.20<br />
■ 1000 600 300 1.87 1.63 1.75 1.51 1.63 1.39 1.27<br />
1000 800 200 2.02 1.70 1.94 1.62 1.86 1.54 1.43<br />
■ 1000 800 250 2.17 1.85 2.07 1.75 1.97 1.65 1.51<br />
■ 1000 800 300 2.32 2.00 2.20 1.88 2.08 1.76 1.59<br />
■ 1000 1000 300 2.76 2.36 2.64 2.24 2.52 2.12 1.91<br />
■ 1000 1200 300 3.20 2.72 3.08 2.75 2.96 2.48 2.23<br />
■ 1200 800 300 2.71 2.33 2.57 2.18 2.42 2.04 1.87<br />
■ 1200 1000 300 3.23 2.75 3.08 2.60 2.94 2.46 2.25<br />
Surface areas are expressed in m 2 .<br />
6/104
HEAT CALCULATION<br />
Dissipation surface area<br />
Dissipation surface area of the metal enclosures:<br />
CMO and OLN<br />
Accessible on all sides<br />
Installation mode<br />
Against a wall<br />
At one end of a row<br />
At one end of a row, against a wall<br />
Intermediate in a row<br />
Intermediate in a row, against a wall<br />
Intermediate in a row, against a wall,<br />
closed covered top<br />
Enclosure reference<br />
number<br />
Dimensions in mm<br />
A B C<br />
Type of installation conforming to IEC 890<br />
CMO1010/30 1000 1000 300 2.76 2.36 2.64 2.36 2.52 2.12 1.91<br />
CMO128/30 1200 800 300 2.71 2.33 2.57 2.28 2.42 2.04 1.87<br />
CMO1210/30 1200 1000 300 3.23 2.75 3.08 2.72 2.94 2.46 2.25<br />
CMO1212/40 1200 1200 400 4.13 3.55 3.94 3.55 3.74 3.17 2.83<br />
CMO146/30 1400 600 300 2.52 2.18 2.35 2.09 2.18 1.85 1.72<br />
CMO146/40 1400 600 400 2.86 2.52 2.63 2.39 2.41 2.07 1.90<br />
CMO148/30 1400 800 300 3.11 2.66 2.94 2.59 2.77 2.32 2.16<br />
CMO148/40 1400 800 400 3.47 3.02 3.25 2.93 3.02 2.58 2.35<br />
CMO1410/40 1400 1000 400 4.09 3.53 3.86 3.46 3.64 3.08 2.80<br />
CMO1412/40 1400 1200 400 4.70 4.03 4.48 4.00 4.26 3.58 3.25<br />
CMO166/30 1600 600 300 2.84 2.46 2.65 2.34 2.46 2.08 1.95<br />
CMO166/40 1600 600 400 3.22 2.83 2.96 2.67 2.70 2.32 2.15<br />
CMO168/30 1600 800 300 3.50 2.99 3.31 2.90 3.12 2.61 2.44<br />
CMO168/40 1600 800 400 3.90 3.39 3.65 3.26 3.39 2.88 2.66<br />
CMO1610/30 1600 1000 300 4.16 3.52 3.97 3.45 3.78 3.14 2.93<br />
CMO1610/40 1600 1000 400 4.95 3.95 4.34 3.86 4.08 3.44 3.16<br />
CMO1612/30 1600 1200 300 4.82 4.06 4.63 4.01 4.44 3.67 3.42<br />
CMO1612/40 1600 1200 400 5.28 4.51 5.02 4.45 4.77 4.00 3.66<br />
CMO186/30 1800 600 300 3.17 2.74 2.95 2.59 2.74 2.30 2.18<br />
CMO186/40 1800 600 400 3.58 3.14 3.29 2.95 3.00 2.57 2.40<br />
CMO188/30 1800 800 300 3.90 3.32 3.68 3.20 3.47 2.89 2.72<br />
CMO188/40 1800 800 400 4.34 3.76 4.05 3.60 3.76 3.18 2.96<br />
CMO188/50 1800 800 500 4.77 4.20 4.41 4.00 4.05 3.48 3.20<br />
CMO188/60 1800 800 600 5.21 4.63 4.78 4.39 4.34 3.77 3.43<br />
CMO1810/40 1800 1000 400 5.10 4.38 4.81 4.25 4.52 3.80 3.52<br />
CMO1810/50 1800 1000 500 5.56 4.84 5.20 4.68 4.84 4.12 3.77<br />
CMO1812/40 1800 1200 400 5.86 4.99 5.57 4.90 5.28 4.42 4.08<br />
CMO1812/50 1800 1200 500 6.35 5.48 5.99 5.36 5.63 4.76 4.34<br />
CMO1816/40 1800 1600 400 7.38 6.22 7.09 6.19 6.80 5.65 5.20<br />
CMO1816/50 1800 1600 500 7.92 6.77 7.56 6.73 7.20 6.05 5.49<br />
CMO206/30 2000 600 300 3.49 3.01 3.25 2.84 3.01 2.53 2.41<br />
CMO206/40 2000 600 400 3.94 3.46 3.62 3.23 3.30 2.82 2.65<br />
CMO208/30 2000 800 300 4.30 3.66 4.06 3.51 3.82 3.18 3.01<br />
CMO208/40 2000 800 400 4.77 4.13 4.45 3.94 4.13 3.49 3.26<br />
CMO208/50 2000 800 500 5.24 4.60 4.84 4.36 4.44 3.80 3.52<br />
CMO208/60 2000 800 600 5.71 5.07 5.23 4.78 4.75 4.11 3.78<br />
CMO2010/40 2000 1000 400 5.60 4.80 5.28 4.64 4.96 4.16 3.88<br />
CMO2010/50 2000 1000 500 6.10 5.30 5.70 5.10 5.30 4.50 4.15<br />
CMO2012/40 2000 1200 400 6.43 5.47 6.11 5.34 5.79 4.83 4.50<br />
CMO2012/50 2000 1200 500 6.96 6.00 6.56 5.84 6.16 5.20 4.78<br />
CMO2012/60 2000 1200 600 7.49 6.53 7.01 6.34 6.53 5.57 5.06<br />
CMO2016/40 2000 1600 400 8.10 6.82 7.78 6.75 7.46 6.18 5.73<br />
CMO2016/50 2000 1600 500 8.68 7.40 8.28 7.32 7.88 6.60 6.04<br />
CMO2016/60 2000 1.600 600 9.26 7.98 8.78 7.89 8.30 7.02 6.35<br />
6/105
HEAT CALCULATION<br />
Dissipation surface area<br />
Dissipation surface area of the metal<br />
enclosures: OLN<br />
Enclosure reference<br />
number<br />
Dimensions in mm<br />
A B C<br />
Type of installation conforming to IEC 890<br />
OLN126/40 1200 600 400 2.50 2.21 2.30 2.02 2.11 1.82 1.66<br />
OLN126/60 1200 600 600 3.70 2.81 2.81 2.52 2.52 2.23 1.98<br />
OLN126/80 1200 600 800 3.70 3.41 3.31 3.02 2.93 2.64 2.30<br />
OLN128/40 1200 800 400 3.04 2.66 2.85 2.46 2.66 2.27 2.05<br />
OLN128/60 1200 800 600 3.70 3.31 3.41 3.02 3.12 2.74 2.40<br />
OLN128/80 1200 800 800 4.35 3.97 3.97 3.58 3.58 3.20 2.75<br />
OLN146/40 1400 600 400 2.86 2.52 2.63 2.30 2.41 2.07 1.90<br />
OLN146/60 1400 600 600 3.53 3.19 3.19 2.86 2.86 2.52 2.27<br />
OLN146/80 1400 600 800 4.20 3.86 3.75 3.42 3.30 2.97 2.63<br />
OLN148/40 1400 800 400 3.47 3.02 3.25 2.80 3.02 2.58 2.35<br />
OLN148/60 1400 800 600 4.20 3.75 3.86 3.42 3.53 3.08 2.74<br />
OLN148/80 1400 800 800 4.93 4.48 4.48 4.03 4.03 3.58 3.14<br />
OLN166/60 1600 600 600 3.96 3.58 3.58 3.19 3.19 2.81 2.56<br />
OLN166/80 1600 600 800 4.70 4.32 4.19 3.81 3.68 3.30 2.96<br />
OLN168/60 1600 800 600 4.70 4.19 4.32 3.81 3.94 3.42 3.09<br />
OLN168/80 1600 800 800 5.50 4.99 4.99 4.48 4.48 3.97 3.52<br />
OLN186/40 1800 600 400 3.58 3.14 3.29 2.86 3.00 2.57 2.40<br />
OLN186/50 1800 600 500 3.98 3.55 3.62 3.19 3.26 2.83 2.62<br />
OLN186/60 1800 600 600 4.39 3.96 3.96 3.53 3.53 3.10 2.84<br />
OLN186/80 1800 600 800 5.21 4.78 4.69 4.20 4.06 3.62 3.29<br />
OLN188/40 1800 800 400 4.34 3.76 4.05 3.47 3.76 3.18 2.96<br />
OLN188/50 1800 800 500 4.77 4.20 4.41 3.84 4.05 3.48 3.20<br />
OLN188/60 1800 800 600 5.21 4.63 4.78 4.20 4.34 3.77 3.43<br />
OLN1810/40 1800 1000 400 5.10 4.38 4.81 4.09 4.52 3.80 3.52<br />
OLN1810/40/2P 1800 1000 400 5.10 4.38 4.81 4.09 4.52 3.80 3.52<br />
OLN1810/50 1800 1000 500 5.56 4.84 5.20 4.48 4.84 4.12 3.77<br />
OLN1810/50/2P 1800 1000 500 5.56 4.84 5.20 4.48 4.84 4.12 3.77<br />
OLN1810/60 1800 1000 600 6.02 5.30 5.59 4.87 5.16 4.44 4.02<br />
OLN1810/60/2P 1800 1000 600 6.02 5.30 5.59 4.87 5.16 4.44 4.02<br />
OLN1812/40/2P 1800 1200 400 5.86 4.99 5.57 4.70 5.28 4.42 4.08<br />
OLN1812/50/2P 1800 1200 500 6.35 5.48 5.99 5.12 5.63 4.76 4.34<br />
OLN1812/60/2P 1800 1200 600 6.84 5.98 6.41 5.54 5.98 5.11 4.61<br />
OLN203/50 2000 300 500 3.09 2.85 2.69 2.45 2.29 2.05 1.95<br />
OLN203/60 2000 300 600 3.49 3.25 3.01 2.77 2.53 2.29 2.17<br />
OLN203/80 2000 300 600 4.30 4.06 3.66 3.51 3.02 2.78 2.61<br />
OLN206/40 2000 600 400 3.94 3.46 3.62 3.14 3.30 2.82 2.65<br />
OLN206/50 2000 600 500 4.38 3.90 3.98 3.50 3.58 3.10 2.89<br />
OLN206/60 2000 600 600 4.82 4.34 4.34 3.86 3.86 3.38 3.13<br />
OLN206/80 2000 600 800 5.71 5.23 5.07 4.59 4.43 3.95 3.62<br />
OLN208/40 2000 800 400 4.77 4.13 4.45 3.81 4.13 3.49 3.26<br />
OLN208/50 2000 800 500 5.24 4.60 4.84 4.20 4.44 3.80 3.52<br />
OLN208/60 2000 800 600 5.71 5.07 5.23 4.59 4.7 4.11 3.78<br />
OLN208/80 2000 800 800 6.66 6.02 6.02 5.38 5.38 4.74 4.29<br />
OLN2010/40 2000 1000 400 5.60 4.80 5.28 4.48 4.96 4.16 3.88<br />
OLN2010/40/2P 2000 1000 400 5.60 4.80 5.28 4.48 4.96 4.16 3.88<br />
OLN2010/50 2000 1000 500 6.10 5.30 5.70 4.90 5.30 4.50 4.15<br />
OLN2010/50/2P 2000 1000 500 6.10 5.30 5.70 4.90 5.30 4.50 4.15<br />
OLN2010/60 2000 1000 600 6.60 5.80 6.12 5.32 5.64 4.84 4.42<br />
OLN2010/60/2P 2000 1000 600 6.60 5.80 6.12 5.32 5.64 4.84 4.42<br />
OLN2010/80 2000 1000 800 7.60 6.80 6.96 6.16 6.32 5.52 4.96<br />
OLN2010/80/2P 2000 1000 800 7.60 6.80 6.96 6.16 6.32 5.52 4.96<br />
OLN2012/40/2P 2000 1200 400 6.43 5.47 6.11 5.15 5.79 4.83 4.50<br />
OLN2012/50/2P 2000 1200 500 6.96 6.00 6.56 5.60 6.16 5.20 4.78<br />
OLN2012/60/2P 2000 1200 600 7.49 6.53 7.01 6.05 6.53 5.57 5.06<br />
OLN2012/80/2P 2000 1200 800 8.54 7.58 7.90 6.94 7.26 6.30 5.63<br />
OLN226/60 2200 600 600 5.26 4.73 4.73 4.20 4.20 3.67 3.42<br />
OLN226/80 2200 600 800 6.22 5.69 5.51 4.98 4.81 4.28 3.94<br />
OLN228/60 2200 800 600 6.22 5.51 5.69 4.98 5.16 4.46 4.12<br />
OLN228/80 2200 800 800 7.23 6.53 6.53 5.82 5.82 5.12 4.67<br />
OLN2210/60 2200 1000 600 7.18 6.30 6.65 5.77 6.12 5.24 4.82<br />
OLN2210/80 2200 1000 800 8.25 7.37 7.54 6.66 6.84 5.96 5.40<br />
OLN2210/80/2P 2200 1000 800 8.25 7.37 7.54 6.66 6.84 5.96 5.40<br />
OLN2212/60/2P 2200 1200 600 8.14 7.08 7.61 6.55 7.08 6.02 5.52<br />
OLN2212/80/2P 2200 1200 800 9.26 8.21 8.56 7.50 7.86 6.80 6.13<br />
6/106
HEAT CALCULATION<br />
Dissipation surface area of the polyester<br />
enclosures: POLYMEL<br />
Enclosure reference<br />
number<br />
Dimensions in mm<br />
A B C<br />
Type of installation conforming to IEC 890<br />
PLM3025 308 255 160 0.29 0.23 0.26 0.27 0.25 0.22 0.19<br />
PLM32 310 215 160 0.26 0.23 0.24 0.21 0.22 0.19 0.17<br />
PLM43 430 330 200 0.50 0.45 0.47 0.41 0.43 0.38 0.33<br />
PLM54 530 430 200 0.72 0.63 0.68 0.59 0.64 0.55 0.49<br />
PLM64 647 436 250 0.95 0.84 0.89 0.77 0.82 0.71 0.63<br />
PLM75 747 536 300 1.35 1.19 1.26 1.10 1.17 1.01 0.90<br />
PLM86 847 636 300 1.69 1.48 1.59 1.38 1.49 1.28 1.14<br />
PLM108 1056 800 350 2.46 2.14 2.32 2.00 2.18 1.86 1.67<br />
Dissipation surface area of the polyester<br />
enclosures: PLA<br />
Enclosure reference number<br />
Dimensions in mm<br />
A B C<br />
Type of installation conforming to IEC 890<br />
PLA553 500 500 320 0.96 0.86 0.90 0.86 0.83 0.73 0.62<br />
PLA554 500 500 420 1.12 1.02 1.04 1.02 0.95 0.85 0.71<br />
PLA573 500 750 320 1.30 1.15 1.24 1.18 1.17 1.02 0.85<br />
PLA574 500 750 420 1.49 1.34 1.41 1.39 1.33 1.18 0.96<br />
PLA5103 500 1000 320 1.64 1.44 1.57 1.50 1.51 1.31 1.08<br />
PLA5104 500 1000 420 1.87 1.67 1.78 1.75 1.70 1.50 1.20<br />
PLA5123 500 1250 320 1.97 1.72 1.91 1.82 1.85 1.60 1.32<br />
PLA5124 500 1250 420 2.24 1.99 2.15 2.11 2.07 1.82 1.45<br />
PLA753 750 500 320 1.33 1.18 1.24 1.15 1.14 0.99 0.88<br />
PLA754 750 500 420 1.54 1.39 1.41 1.34 1.28 1.13 0.99<br />
PLA773 750 750 320 1.78 1.56 1.68 1.56 1.59 1.36 1.20<br />
PLA774 750 750 420 2.02 1.80 1.89 1.80 1.77 1.54 1.32<br />
PLA7103 750 1000 320 2.23 1.93 2.13 1.96 2.04 1.74 1.51<br />
PLA7104 750 1000 420 2.51 2.21 2.38 2.25 2.25 1.95 1.66<br />
PLA7123 750 1250 320 2.68 2.30 2.58 2.37 2.49 2.11 1.83<br />
PLA7124 750 1250 420 2.99 2.61 2.86 2.70 2.74 2.36 2.00<br />
PLA1053 1000 500 320 1.70 1.50 1.57 1.44 1.44 1.24 1.13<br />
PLA1054 1000 500 420 1.95 1.75 1.78 1.67 1.61 1.41 1.27<br />
PLA1073 1000 750 320 2.26 1.96 2.13 1.93 2.01 1.71 1.54<br />
PLA1074 1000 750 420 2.55 2.25 2.38 2.21 2.21 1.91 1.69<br />
PLA10103 1000 1000 320 2.82 2.42 2.70 2.42 2.57 2.17 1.94<br />
PLA10104 1000 1000 420 3.14 2.74 2.98 2.74 2.81 2.41 2.11<br />
PLA10123 1000 1250 320 3.39 2.89 3.26 2.92 3.13 2.63 2.35<br />
PLA10124 1000 1250 420 3.74 3.24 3.57 3.28 3.41 2.91 2.54<br />
PLA1253 1250 500 320 2.07 1.82 1.91 1.72 1.75 1.50 1.39<br />
PLA1254 1250 500 420 2.36 2.11 2.15 1.99 1.94 1.69 1.55<br />
PLA1273 1250 750 320 2.74 2.37 2.58 2.30 2.42 2.05 1.88<br />
PLA1274 1250 750 420 3.07 2.70 2.86 2.61 2.65 2.28 2.06<br />
PLA12103 1250 1000 320 3.42 2.92 3.26 2.89 3.10 2.60 2.37<br />
PLA12104 1250 1000 420 3.78 3.28 3.57 3.24 3.36 2.86 2.57<br />
PLA12123 1250 1250 320 4.09 3.47 3.93 3.47 3.77 3.15 2.87<br />
PLA12124 1250 1250 420 4.49 3.87 4.28 3.87 4.07 3.45 3.08<br />
PLA1553 1500 500 320 2.44 2.14 2.25 2.01 2.05 1.75 1.64<br />
PLA1554 1500 500 420 2.78 2.48 2.53 2.31 2.27 1.97 1.83<br />
PLA1573 1500 750 320 3.23 2.78 3.03 2.68 2.84 2.39 2.22<br />
PLA1574 1500 750 420 3.60 3.15 3.35 3.02 3.10 2.65 2.43<br />
PLA15103 1500 1000 320 4.01 3.41 3.82 3.35 3.63 3.03 2.80<br />
PLA15104 1500 1000 420 4.42 3.82 4.17 3.74 3.92 3.32 3.02<br />
PLA15123 1500 1250 320 4.80 4.05 4.61 4.02 4.42 3.67 3.39<br />
PLA15124 1500 1250 420 5.24 4.49 4.99 4.45 4.74 3.99 3.62<br />
6/107