<strong>THERMAL</strong> <strong>MANAGEMENT</strong><br />

<strong>SYSTEMS</strong><br />

Concept 6/2<br />

Selection guide 6/6<br />

VF<br />

Ventilation systems 6/8<br />

ICL-AI/ICT-AI<br />

Air/air exchangers 6/30<br />

ICL-AG/ICT-AG<br />

Air/water exchangers 6/36<br />

CLL/CLT<br />

CLLMP/CLTMP<br />

Cooling units 6/40<br />

- Mechanical control<br />

- Electronic control<br />

RC<br />

Resistance heaters 6/64<br />

- Insulated<br />

- Standard<br />

TS<br />

Control devices 6/80<br />

Thermal management<br />

for electrical panels 6/95<br />

Support service for<br />

the PROclima 4.0 software<br />

calculation 6/100


6/2<br />

Thermal management for electrical and<br />

electronic switchboards: a need


What is temperature control?<br />

Technological evolution<br />

The miniaturisation of components, the generalisation of electronics,<br />

the appearance of new products based on power electronics mean<br />

that temperature management is a need that must increasingly<br />

be taken into account in the design of electrical and/or electronic<br />

switchboards.<br />

What are the advantages of good temperature<br />

control?<br />

Temperature control in electrical switchboards is one of the important<br />

factors of good industrial maintenance.<br />

The risks involved through failure to have a suitable thermal solution<br />

are multiple, affecting the life of components and the performance of<br />

installations to such an extent that they may halt production.<br />

The service life of the components themselves is a function of the<br />

temperature and humidity conditions in the enclosure. Ideal are<br />

values from +15…+35 ºC for temperature and from 30 to 90% relative<br />

humidity (RH).<br />

Cooling, Heating, controlling<br />

Just like the degrees of IP/IK protection suited to each installation,<br />

the equipment installed inside an enclosure needs suitable thermal<br />

protection.<br />

There are different solutions to these problems, depending on<br />

environmental conditions, the nature of the components of the<br />

electrical switchboard, etc.<br />

In some cases it is suffi cient to oversize the enclosure, use fans or<br />

air-air exchangers. In other, more extreme cases, in which the<br />

ambient temperature is higher, air-water heat exchangers or cooling<br />

units must be used.<br />

A solution for every need<br />

With this objective in mind, Himel proposes a comprehensive<br />

Thermal Offer to secure your installation.<br />

Cooling<br />

Heating<br />

Control<br />

Calculation<br />

1. Forced ventilation system<br />

2 . Air/air exchangers<br />

3 . Air/water exchangers<br />

4. Cooling units<br />

5. Resistance heaters<br />

6. Thermal control systems<br />

7. PROclima 4.0 software<br />

6/3


System Natural ventilation Forced ventilation Air-air exchangers<br />

Natural convection helps to reduce the<br />

temperature inside the enclosure, whereby<br />

installing (without filter) outlet grilles or raising<br />

the enclosure tops may be a suitable solution.<br />

Fans with a Himel filter have been designed to<br />

evacuate a large amount of heat economically.<br />

They have an aluminium exchange battery that<br />

separates the two air circuits (inside and outside)<br />

and stops dust from getting inside.<br />

When to use them<br />

This solution is only feasible in cases where the<br />

power that has to be dissipated is weak, and in<br />

atmospheres with low dust levels.<br />

When you need to evacuate greater dissipated<br />

power, and when the outside environment is<br />

polluted.<br />

In highly polluted atmospheres or when large<br />

amounts of heat must be evacuated without<br />

bringing the outside and inside atmospheres<br />

into contact.<br />

Ta: ambient temperature<br />

Td: temperature required<br />

Ta < Td Ta < Td Ta < Td<br />

The inside and outside air circuits are<br />

independent.<br />

NO NO YES<br />

Advantages<br />

c Economic solution.<br />

c Maintenance-free.<br />

c Easy and quick to install.<br />

c Economic solution.<br />

c Easy maintenance.<br />

c Easy and quick to install.<br />

c Even temperature inside the enclosure.<br />

c High protection degree (IP54 or IP55).<br />

c They do not bring the atmospheres inside and<br />

outside the enclosure into contact.<br />

c Easy maintenance.<br />

c High protection degree (IP54).<br />

c The temperature inside the enclosure is always<br />

Drawbacks<br />

c The amount of heat evacuated is weak.<br />

c Reduction in protection degree.<br />

c Dust penetration.<br />

higher than the outside.<br />

c They bring the atmospheres inside and outside<br />

the enclosure into contact.<br />

c Maintenance is required: filter change.<br />

c The temperature inside the enclosure is<br />

always higher than the outside.<br />

Solutions<br />

Outlet grilles<br />

Fans and outlet grills<br />

Air-air exchangers<br />

6/4


Air-water exchangers Cooling Heating<br />

They cool the enclosure by means of a water-cooled exchange<br />

battery.<br />

The regulation of the temperature in the enclosure is performed<br />

by means of a thermostat that closes or opens an<br />

electro-valve.<br />

They are cooling unit devices that guarantee effective and<br />

independent cooling from the outside environment, and avoid<br />

the appearance of heat sources.<br />

Resistance heaters avoid problems of condensation inside the<br />

enclosure and guarantee maintenance of the ideal temperature<br />

for the correct operation of the electronic components.<br />

c When a large amount of heat has to be evacuated and a<br />

water cooling installation stable in temperature and flow is<br />

available.<br />

c Particularly suitable for difficult and highly polluted<br />

atmosphere, since there is no outside air circuit.<br />

c Our cooling units can be used in the severest atmospheres,<br />

where the temperature can reach up to 55 ºC.<br />

c Our cooling units feature the temperature adjustment<br />

function, as well as an indication of any anomalies by<br />

means of an alarm.<br />

Resistance heaters are used to heat the electrical switchboard<br />

when the ambient temperature is too low, or to prevent the<br />

formation of condensation water.<br />

Ta > Td Ta > Td Ta < Td<br />

YES<br />

YES<br />

c The inside temperature of the enclosure does not depend on<br />

the outside.<br />

c They do not bring the atmospheres inside and outside the<br />

enclosure into contact.<br />

c It has a leak detection device.<br />

c Even temperature inside the enclosure.<br />

c High protection degree (IP54).<br />

c They use ecological gas.<br />

c Small size.<br />

c Fitted with a PTC-type heating element that stabilises the<br />

surface temperature of the aluminium section.<br />

c In two versions: insulated, with low surface temperature<br />

and in aluminium with a surface temperature below<br />

< 75 ºC.<br />

c The fan-equipped resistance heaters guarantee the<br />

temperature inside the enclosure and prevent hot spots.<br />

c They need cold water.<br />

c They need a specific plumbing installation.<br />

c The installation of a drain is recommended.<br />

c Maintenance is required: filter change.<br />

Air-water exchangers Cooling units Resistance heaters<br />

6/5


<strong>THERMAL</strong> <strong>MANAGEMENT</strong><br />

Selection guide<br />

A thermal solution for every environment<br />

Ventilation systems with filter<br />

Particularly suited for installations in which:<br />

c The temperature expected outside the enclosure may be lower than the<br />

maximum required inside it.<br />

c A high degree of protection must be maintained (IP54/IP55).<br />

c The outside environment is not too dusty.<br />

Broad range of solutions:<br />

c 42 models.<br />

c In RAL-7032 and RAL-7035.<br />

c From 38 to 850 m 3 /h.<br />

c In 5 voltages:<br />

AC: 400/440 V, 230 V, 115 V (50/60 Hz).<br />

DC: 48 V and 24 V.<br />

Air-air exchangers<br />

Particularly suited for installations in which:<br />

c The temperature expected outside the enclosure may be lower than the<br />

maximum required inside it.<br />

c Maintaining good watertightness is important (IP54/IP55).<br />

c The outside environment is highly polluted.<br />

Broad range of solutions:<br />

c 4 models.<br />

c Top- and side-mounting versions.<br />

c Performance from 15 to 70 W.<br />

c Voltage: 230 V (50/60 Hz).<br />

Air-water exchangers<br />

Particularly suited for installations in which:<br />

c The temperature required inside the enclosure must be lower than the<br />

maximum expected outside.<br />

c In corrosive atmospheres, the outside and inside air circuit never come into<br />

contact.<br />

c Very polluted atmospheres, since they are water-cooled and there is no<br />

outside air circuit.<br />

c When the heat needs to be extracted from the confines of the building.<br />

Broad range of solutions:<br />

c 3 models.<br />

c Top- and side-mounting versions.<br />

c Cooling power from 2100 W and 3000 W.<br />

c Voltage: 230 V (50/60 Hz).<br />

6/6


<strong>THERMAL</strong> <strong>MANAGEMENT</strong><br />

Selection guide<br />

Cooling units<br />

They give the equipment installed in the enclosure the temperature it needs<br />

to operate correctly:<br />

Regardless of the outside temperature.<br />

They do not bring the inside and outside air circuit into contact.<br />

They reduce humidity in the enclosure.<br />

Range of solutions:<br />

c 19 models.<br />

c Top- and side-mounting versions.<br />

c Cooling power from 240 up to 3.100 W.<br />

c Tension: 230 V (50/60 Hz); 3 400/440 V (50/60 Hz).<br />

Resistance heaters<br />

With a twofold objective:<br />

c They avoid condensation problems inside the enclosure.<br />

c They guarantee maintenance of the ideal temperature for the correct<br />

operation of the electronic components.<br />

Range of solutions:<br />

c 30 models.<br />

c Insulated or aluminium versions.<br />

c Convection or circulation fan versions.<br />

c Heating power from 10 up to 550 W.<br />

c Tension: from 12 to 450 V AC/DC.<br />

Control devices<br />

Thermostats: they maintain the temperature inside the enclosure and send a<br />

signal when certain defi ned values are exceeded:<br />

c Maximum value (cooling action).<br />

c Minimum value (heating action).<br />

Range of solutions:<br />

c 16 models.<br />

c Two versions: adjustable or preset temperature.<br />

c Hygrostat: relative humidity regulators. They are used together with<br />

resistance heaters or fans.<br />

c Hygrometer: relative humidity control with a double-function device: hygrostat-thermostat.<br />

Calculation assistance software: PROclima<br />

We provide our clients and users with this software to help them select their<br />

temperature control equipment.<br />

The program calculates the thermal balance in the enclosure and suggests<br />

the best ventilation or cooling solution.<br />

6/7


Ventilation systems VF<br />

Wide range of ventilation products<br />

1<br />

2<br />

7<br />

5<br />

9<br />

6<br />

8<br />

4<br />

3<br />

6/8


0.8 mm<br />

2.2<br />

2.3<br />

2.1<br />

4.5 mm<br />

1 Minimum pressure<br />

loss. Better air flow.<br />

The angles of walls, the<br />

tilting of slats, the fixing<br />

distance of the motor<br />

and the sizing of the<br />

unit have been studied<br />

to guarantee the best<br />

possible air conduction<br />

and minimise pressure<br />

loss.<br />

2 Fixing guide (2.1). Exclusive device (patented) that<br />

centres the fan body with the machining carried out<br />

on the enclosure wall. This system corrects possible<br />

defects in sizing and in the precision of machining.<br />

It also facilitates the operation of the “multiple fixing<br />

clips”.<br />

Multiple thickness fixing clips system (2.2). This<br />

exclusive patented device guarantees easy and<br />

reliable fixing of the ventilation system on 0.8 mm<br />

to 4.5 mm thick walls without the need for any other<br />

screws.<br />

It also guarantees a perfect joint compression on the<br />

cut outline. Protection between the grille and the wall<br />

is guaranteed for all materials: steel, stainless steel,<br />

polyester, aluminium, etc.<br />

Tilted profile of the grill (2.3). This innovating profile<br />

increases the protection of the filter against vertical<br />

exposure:<br />

c Each slat is protected by the slat above it.<br />

c The external size remains small.<br />

3 IP54-55.<br />

Designed (patented)<br />

especially to evacuate<br />

any water that might<br />

be retained by the filter<br />

blanket for applications<br />

that may be splashed<br />

under pressure.<br />

4 Wide offer of filters.<br />

c For application in<br />

greasy atmospheres<br />

(OEMs).<br />

c Anti-insect filters.<br />

c Small fine filter (when<br />

greater dust protection<br />

is required).<br />

ENVIRONMENTALLY<br />

friendly<br />

5 Environment.<br />

c Recyclable plastic<br />

materials and filters.<br />

c Motors compliant with<br />

the ROHS legislation.<br />

c Lower electrical<br />

consumption for<br />

greater air flow.<br />

6 Selection of plastic materials.<br />

The materials (ASA/PC) selected give the system:<br />

c Good behaviour (long service life) with regard to<br />

UV rays.<br />

c Excellent mechanical behaviour.<br />

c The colours of the grills in the standard supply are<br />

RAL-7032 and 7035.<br />

c Grill colour can be changed by mould injection<br />

(check with the sales network).<br />

7 Strong, reliable and effortless fixing that is<br />

evident upon installation, made possible by the set of<br />

“guide devices” and the “multiple fixing clips”.<br />

It also allows traditional enclosures to be fixed with<br />

fasteners.<br />

8 Fast replacement of<br />

the filter blanket.<br />

Fast, easy and secure<br />

replacement of the filter<br />

blanket, even with the<br />

fan operating.<br />

Reversibility.<br />

The rotation of the fan<br />

motor can be easily<br />

changed on all models<br />

(extraction/discharge).<br />

9 Motor selection. State-of-the-art motors have been<br />

selected from leading manufacturers in the sector, with<br />

a view to achieving:<br />

c Higher flow rate.<br />

c Longer useful life.<br />

The largest range of voltages is available in the<br />

standard motor selection, both in alternating (50/60 Hz)<br />

and direct current.<br />

Self-extinguishing. Self-extinguishing according to<br />

the UL94 VO regulation.<br />

6/9


<strong>SYSTEMS</strong><br />

Selection guide<br />

VENTILATION <strong>SYSTEMS</strong> WITH FILTER<br />

Free flow<br />

(fan with filter)<br />

Fan + 1 outlet grill<br />

Flow rate (m 3 /h)<br />

Fan + 2 outlet grills<br />

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz<br />

Voltage<br />

Type of<br />

connection<br />

(*)<br />

Total<br />

(external) (mm)<br />

Dimensions<br />

(mm)<br />

Cut-out<br />

(mm)<br />

38 39 25 26 33 34 230 V C<br />

38 39 27 28 35 36 115 V C<br />

58 39 47 24 DC C<br />

137 117 92 92<br />

44 34 41 48 DC C<br />

85 98 63 72 71 83 230 V F<br />

79 92 65 74 73 79 115 V F<br />

80 57 77 24 DC F<br />

170 150 125 125<br />

79 59 68 48 DC F<br />

165 193 153 171 161 175 230 V F<br />

164 192 153 171 161 174 115 V F<br />

188 171 179 24 DC F<br />

193 171 179 48 DC F<br />

302 350 260 307 268 311 230 V F<br />

268 248 223 223<br />

302 348 263 305 271 314 115 V F<br />

262 221 229 24 DC F<br />

247 210 218 48 DC F<br />

562 586 473 477 481 485 230 V B<br />

582 583 485 475 494 477 115 V B<br />

838 803 718 568 728 585 230 V B<br />

336 316 291 291<br />

983 944 843 642 854 667 115 V B<br />

931 803 798 568 809 585 400/440 V B<br />

(*) C = by cable, F = by connector, B = by terminal block.<br />

NEW Fans with type of connection F include a fan connection cable (L = 2 m)<br />

6/10


Reference<br />

Fan with filter Outlet grille Fan with filter Outlet grille<br />

IP<br />

RAL-7032 RAL-7032 RAL-7035 RAL-7035<br />

VF38<br />

VF38R35<br />

VF38/115<br />

VF38/115R35<br />

FS38<br />

FS38R35 54<br />

VF38/24DC<br />

VF38/24DCR35<br />

VF38/48DC<br />

VF38/48DCR35<br />

VF85<br />

VF85R35<br />

VF85/115<br />

VF85/115R35<br />

FS85<br />

FS85R35 54<br />

VF85/24DC<br />

VF85/24DCR35<br />

VF85/48DC<br />

VF85/48DCR35<br />

VF165<br />

VF165R35<br />

VF165/115<br />

VF165/115R35<br />

VF165/24DC<br />

VF165/24DCR35<br />

VF165/48DC<br />

VF165/48DCR35<br />

FS165<br />

FS165R35 54<br />

VF300<br />

VF300R35<br />

VF300/115<br />

VF300/115R35<br />

VF300/24DC<br />

VF300/24DCR35<br />

VF300/48DC<br />

VF300/48DCR35<br />

VF560<br />

VF560R35<br />

VF560/115<br />

VF560/115R35<br />

VF850<br />

FS560<br />

VF850R35<br />

FS560R35 54<br />

VF850/115<br />

VF850/115R35<br />

VF850/400<br />

VF850/400R35<br />

6/11


VENTILATION <strong>SYSTEMS</strong><br />

Selection guide<br />

OUTLET GRILLES<br />

Reference<br />

Dimensions<br />

(mm)<br />

IP<br />

RAL-7032 RAL-7035 Total (outside) Cut-out<br />

FS38 FS38R35 137 117 92 92 54<br />

FS85 FS85R35 170 150 125 125 54<br />

FS165 FS165R35 268 248 223 223 54<br />

FS560 FS560R35 336 316 291 291 54<br />

VANDAL PROOF SYSTEM<br />

Reference<br />

Dimensions<br />

(mm)<br />

Set of<br />

RAL-7011<br />

ANVF 137 177 2<br />

ANVF 170 150 2<br />

ANVF 268 248 2<br />

ANVF 336 316 2<br />

POWER CONNECTION CABLE FOR FANS<br />

Reference<br />

Length (mm)<br />

CBMV100 1000<br />

CBMV200 2000<br />

FILTERS<br />

Reference Concept For fans and grilles with dimensions (mm)<br />

F38<br />

137 117<br />

F85 Standard filter (G2 class<br />

170 150<br />

F165 conforming to EN 779)<br />

268 248<br />

F560 336 316<br />

F85OEM<br />

170 150<br />

F165OEM “Greasy environments” OEM filter<br />

268 248<br />

F560OEM 336 316<br />

FF85<br />

170 150<br />

FF165<br />

Fine filter (G3 class conforming<br />

to EN 779)<br />

268 248<br />

FF560 336 316<br />

FAIN38<br />

137 117<br />

FAIN85 170 150<br />

“Anti-insect” filters<br />

FAIN165 268 248<br />

FAIN560 336 316<br />

6/12


VENTILATION <strong>SYSTEMS</strong><br />

Selection guide<br />

EMC EXTERNAL KIT IP55<br />

Reference<br />

For fans and grilles with dimensions (mm)<br />

VF85/KITIPCEM 170 150<br />

VF165/KITIPCEM 268 248<br />

VF560/KITIPCEM 336 316<br />

PROTECTION KIT IP55<br />

For grilles and fans<br />

(mm)<br />

Aluzinc<br />

RAL-7032<br />

Aluzinc<br />

RAL-7035<br />

Stainless steel<br />

Replacement<br />

filters<br />

170 150 VF85/KITIPALZ32 VF85/KITIPALZ35 VF85/KITIP F85/KITIP<br />

268 248 VF165/KITIPALZ32 VF165/KITIPALZ35 VF165/KITIP F165/KITIP<br />

336 316 VF560/KITIPALZ32 VF560/KITIPALZ35 VF560/KITIP F560/KITIP<br />

Forced ventilation<br />

The movement of air inside the enclosure with the aid of a fan makes it<br />

possible to:<br />

1<br />

Increase thermal dissipation through the enclosure walls and, as a result,<br />

reduce the inside temperature.<br />

2<br />

Avoid hot spots in the enclosure (even temperature) harmful to some<br />

components.<br />

Natural ventilation<br />

Solution 1<br />

Solution 2<br />

The provision of fresh air from the outside by means of ventilation grills<br />

improves the dissipation of heat by natural convection. However, this<br />

solution is feasible in cases where the power to be dissipated is weak and<br />

in atmospheres with low dust levels. There are 4 ways of ventilating, with a<br />

common principle: entry of cold air through the bottom of the enclosure by<br />

means of an accessory and the exit of hot air through the top of the enclosure<br />

by means of an accessory:<br />

1<br />

By elevating the ceiling of the enclosures (only in Spacial 6000 models) and<br />

adding a fi lterless bottom air inlet (solution 1).<br />

2<br />

By means of a ceiling ventilation device, adding a fi lterless air inlet at the<br />

bottom (solution 1).<br />

3<br />

By means of inlet and outlet grills (fi lterless) (solution 2).<br />

4<br />

By means of ventilation lugs (Solution for insulating enclosures).<br />

6/13


VF<br />

Forced ventilation system<br />

IP54 (EN 60529)<br />

VF38 Fans…<br />

General features:<br />

c The Himel fans are comprised of an axial motor, a protection housing for<br />

the front and rear sides, and a filter for retaining dust particles.<br />

c The filter can even be replaced during operation, without any risk of contact<br />

with the blades or other rotating elements.<br />

c The cut-out template included with the standard supply avoids drawing and<br />

protects the enclosure surface from the risk of scratches during handling.<br />

Conditions of use:<br />

c The outside temperature Te should be 5 °C below the temperature required<br />

Ts in the enclosure.<br />

c The filters the fans are equipped with must be cleaned or replaced<br />

periodically.<br />

c The environment should be relatively “clean” and over-frequent filter<br />

replacement should be avoided.<br />

c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />

or single opening) must be taken into consideration to determine ventilation<br />

flow.<br />

Characteristics<br />

Reference<br />

Colour RAL-7032 VF38 VF38/115 VF38/24DC VF38/48DC<br />

Colour RAL-7035 VF38R35 VF38/115R35 VF38/24DCR35 VF38/48DCR35<br />

Flow rate with filter (m 3 /h) (50/60 Hz) 38/39 38/39 58 44<br />

Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 25/26 27/28 39 34<br />

Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />

Voltage range 150...250 V 75...125 V 10...27.6 V 24...55 V<br />

Absorbed power (50/60 Hz) 4.5/4.8 W 3.3/3.5 W 3.6 W 4.6 W<br />

Intensity max. (50/60 Hz) 0.16/0.17 A 0.16/0.16 A 0.18 A 0.074 A<br />

Noise level<br />

40/41 dB (A)<br />

Bearing<br />

Balls<br />

IP Degree of protection (with standard filter) 54<br />

External dimensions (mm) 137 117 49<br />

Cut-out dimensions (mm) 92 92<br />

Weight 0.220 kg 0.230 kg<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –10 a +70 °C –10 a +70 °C<br />

Storage temperature –40 a +70 °C<br />

100% operating factor 100%<br />

Maximum static pressure (0 m 3 /h airflow)<br />

20 Pa<br />

Outlet grilles<br />

Characteristics<br />

Reference<br />

Colour RAL-7032<br />

FS38<br />

Colour RAL-7035<br />

FS38R35<br />

Degree of protection IP54 54<br />

External dimensions (mm)<br />

137 117 18<br />

(height length depth)<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Operating temperature –20 a +70 °C<br />

Replacement filter<br />

Characteristics<br />

Standard filter (G2 class conforming to EN 779)<br />

Reference<br />

F38<br />

6/14


VF<br />

Forced ventilation system<br />

IP54 (EN 60529)<br />

Dimensions (mm)<br />

FIG. 1<br />

Fans VF38-VF38/115<br />

13<br />

137<br />

91.85<br />

80<br />

92 92<br />

117 49 9<br />

FIG. 2<br />

“Pressure/Flow” Diagram<br />

Pa<br />

VF38<br />

Difference in static pressure (SP)<br />

Flow rate m 3 /h<br />

6/15


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

VF85 Fans…<br />

General features:<br />

c The Himel fans are comprised of an axial motor, a protection housing for<br />

the front and rear sides, and a filter for retaining powder particles.<br />

c The filter can even be replaced during operation, without any risk of contact<br />

with the blades or other rotating elements.<br />

c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />

protection for dust-sensitive installations.<br />

c The cut-out template included with the standard supply avoids drawing and<br />

protects the enclosure surface from the risk of scratches during handling.<br />

Conditions of use:<br />

c The outside temperature Te should be 5 °C below the temperature required<br />

Ts in the enclosure.<br />

c The filters the fans are equipped with must be cleaned or replaced<br />

periodically.<br />

c The environment should be relatively “clean” and over-frequent filter<br />

replacement should be avoided.<br />

c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />

or single opening) must be taken into consideration to determine ventilation<br />

flow.<br />

Characteristics<br />

Reference<br />

Colour RAL-7032 VF85 VF85/115 VF85/24DC VF85/48DC<br />

Colour RAL-7035 VF85R35 VF85/115R35 VF85/24DCR35 VF85/48DCR35<br />

Flow rate with filter (m 3 /h) (50/60 Hz) 85/98 79/92 80<br />

Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 63/72 65/74 60<br />

Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />

Voltage range 175...253 V 75...126 V 10...27.6 V 25...55.2 V<br />

Absorbed power (50/60 Hz) 17/15 W 16/15 W 7.6 W 8 W<br />

Intensity max. (50/60 Hz) 0.12/0.097 A 0.21/0.179 A 0.30 A 0.173 A<br />

Noise level<br />

46/49 dB (A)<br />

Bearing<br />

Balls<br />

IP Degree of protection (with standard filter) 54<br />

External dimensions (mm) 170 150 62<br />

Cut-out dimensions (mm) 125 125<br />

Weight 0.780 kg 0.480 kg<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –20 a +60 °C –10 a +70 °C<br />

Storage temperature –40 a +70 °C<br />

100% operating factor 100%<br />

Maximum static pressure (0 m 3 /h airflow)<br />

50 Pa<br />

Outlet grills<br />

Characteristics<br />

Reference<br />

Colour RAL-7032<br />

FS85<br />

Colour RAL-7035<br />

FS85R35<br />

IP 54<br />

Outside dimensions (mm)<br />

170 150 18<br />

(height width depth)<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –20 a +70 °C<br />

Replacement filter<br />

Characteristics<br />

Standard filter (filtration capacity: G2 conforming to EN 779)<br />

OEM filter (oily environment)<br />

Fine filter<br />

Anti-insect filter<br />

Reference<br />

F85<br />

F85OEM<br />

FF85<br />

FAIN85<br />

6/16


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

Dimensions (mm)<br />

FIG. 1<br />

Fans<br />

15<br />

170<br />

124.85<br />

119<br />

125 x 125<br />

150<br />

62<br />

9<br />

FIG. 2<br />

“Pressure/Flow” Diagram<br />

Pa<br />

VF85<br />

Difference in static pressure (SP)<br />

Flow rate m 3 /h<br />

6/17


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

VF165 Fans…<br />

General features:<br />

c The Himel fans are comprised of an axial motor, a protection housing for<br />

the front and rear sides, and a filter for retaining powder particles.<br />

c The filter can even be replaced during operation, without any risk of contact<br />

with the blades or other rotating elements.<br />

c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />

protection for dust-sensitive installations.<br />

c The cut-out template included with the standard supply avoids drawing and<br />

protects the enclosure surface from the risk of scratches during handling.<br />

Conditions of use:<br />

c The outside temperature Te should be 5 °C below the temperature required<br />

Ts in the enclosure.<br />

c The filters the fans are equipped with must be cleaned or replaced<br />

periodically.<br />

c The environment should be relatively “clean” and over-frequent filter<br />

replacement should be avoided.<br />

c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />

or single opening) must be taken into consideration to determine ventilation<br />

flow.<br />

Characteristics<br />

Reference<br />

Colour RAL-7032 VF165 VF165/115 VF165/24DC VF165/48DC<br />

Colour RAL-7035 VF165R35 VF165/115R35 VF165/24DCR35 VF165/48DCR35<br />

Flow rate with filter (m 3 /h) (50/60 Hz) 165/193 190<br />

Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 153/171 171<br />

Flow rate with 2 outlet grills (m 3 /h) (50/60 Hz) 161/175 179<br />

Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />

Voltage range 175...253 V 75...126 V 10...27.6 V 25...55.2 V<br />

Absorbed power (50/60 Hz) 16.3/14.3 W 15.5/14.4 W 8 W 8.7 W<br />

Intensity max. (50/60 Hz) 0.12 A/0.94 A 0.20 A/0.18 A 0.3 A 0.18 A<br />

Noise level<br />

50/51 dB (A)<br />

Bearing<br />

Balls<br />

IP Degree of protection (with standard filter) 54<br />

External dimensions (mm) 268 248 104<br />

Cut-out dimensions (mm) 223 223<br />

Weight 1.140 kg 0.810 kg<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –20 a +60 °C –10 a +70 °C<br />

Storage temperature –40 a +70 °C<br />

100% operating factor 100%<br />

Maximum static pressure (0 m 3 /h airflow)<br />

50 Pa<br />

Outlet grills<br />

Characteristics<br />

Reference<br />

Colour RAL-7032<br />

FS165<br />

Colour RAL-7035<br />

FS165R35<br />

IP 54<br />

Outside dimensions (mm)<br />

268 248 18<br />

(height width depth)<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –20 a +70 °C<br />

Replacement filter<br />

Characteristics<br />

Standard filter (filtration capacity: G2 conforming to EN 779)<br />

OEM filter (oily environment)<br />

Fine filter<br />

Anti-insect filter<br />

Reference<br />

F165<br />

F165OEM<br />

FF165<br />

FAIN165<br />

6/18


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

Dimensions (mm)<br />

FIG. 1<br />

Fans VF165-VF165/115<br />

18<br />

268<br />

222.7<br />

119<br />

223 x 223<br />

248<br />

104<br />

9.5<br />

FIG. 2<br />

“Pressure/Flow” Diagram<br />

Pa<br />

VF165<br />

Difference in static pressure (SP)<br />

Flow rate<br />

(m 3 /h)<br />

6/19


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

VF300 Fans…<br />

General features:<br />

c The Himel fans are comprised of an axial motor, a protection housing for<br />

the front and rear sides, and a filter for retaining powder particles.<br />

c The filter can even be replaced during operation, without any risk of contact<br />

with the blades or other rotating elements.<br />

c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />

protection for dust-sensitive installations.<br />

c The cut-out template included with the standard supply avoids drawing and<br />

protects the enclosure surface from the risk of scratches during handling.<br />

Conditions of use:<br />

c The outside temperature Te should be 5 °C below the temperature required<br />

Ts in the enclosure.<br />

c The filters the fans are equipped with must be cleaned or replaced<br />

periodically.<br />

c The environment should be relatively “clean” and over-frequent filter<br />

replacement should be avoided.<br />

c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />

or single opening) must be taken into consideration to determine ventilation<br />

flow.<br />

Characteristics<br />

Reference<br />

Colour RAL-7032 VF300 VF300/115 VF300/24DC VF300/48DC<br />

Colour RAL-7035 VF300R35 VF300/115R35 VF300/24DCR35 VF300/48DCR35<br />

Flow rate with filter (m 3 /h) (50/60 Hz) 300/350 262<br />

Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 260/307 221<br />

Flow rate with 2 outlet grills (m 3 /h) (50/60 Hz) 268/311 229<br />

Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 24 V DC 48 V DC<br />

Voltage range 145...253 V 75...126 V 12...30 V 25...60 V<br />

Absorbed power (50/60 Hz) 36/37 W 36/36 W 13 W 11 W<br />

Intensity max. (50/60 Hz) 0.17/0.16 A 0.35/0.32 A 0.53 A 0.24 A<br />

Noise level<br />

55/56 dB (A)<br />

Bearing<br />

Balls<br />

IP Degree of protection (with standard filter) 54<br />

External dimensions (mm) 268 248 116 268 248 103,4<br />

Cut-out dimensions (mm) 223 223<br />

Weight 1.3 kg 1.1 kg<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –10 a +70 °C –10 a +70 °C<br />

Storage temperature –40 a +70 °C<br />

100% operating factor 100%<br />

Maximum static pressure (0 m 3 /h airflow)<br />

158 Pa<br />

Outlet grills<br />

Characteristics<br />

Reference<br />

Colour RAL-7032<br />

FS165<br />

Colour RAL-7035<br />

FS165R35<br />

IP 54<br />

Outside dimensions (mm)<br />

268 248 18<br />

(height width depth)<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –20 a +70 °C<br />

Replacement filter<br />

Characteristics<br />

Standard filter (filtration capacity: G2 conforming to EN 779)<br />

OEM filter (oily environment)<br />

Fine filter<br />

Anti-insect filter<br />

Reference<br />

F165<br />

F165OEM<br />

FF165<br />

FAIN165<br />

6/20


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

Dimensions (mm)<br />

FIG. 1<br />

Fans VF300-VF300/115<br />

18<br />

268<br />

222.7<br />

172<br />

223 x 223<br />

248<br />

116<br />

9.5<br />

FIG. 2<br />

“Pressure/Flow” Diagram<br />

Pa<br />

VF300<br />

Difference in static pressure (SP)<br />

Flow rate m 3 /h<br />

6/21


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

VF560... and VF850... Fans<br />

General features:<br />

c The Himel fans are comprised of an axial motor, a protection housing for<br />

the front and rear sides, and a filter for retaining powder particles.<br />

c The filter can even be replaced during operation, without any risk of contact<br />

with the blades or other rotating elements.<br />

c Optionally, the fans can be fitted with a fine filter to provide more efficient<br />

protection for dust-sensitive installations.<br />

c The cut-out template included with the standard supply avoids drawing and<br />

protects the enclosure surface from the risk of scratches during handling.<br />

Conditions of use:<br />

c The outside temperature Te should be 5 °C below the temperature required<br />

Ts in the enclosure.<br />

c The filters the fans are equipped with must be cleaned or replaced<br />

periodically.<br />

c The environment should be relatively “clean” and over-frequent filter<br />

replacement should be avoided.<br />

c Load losses caused by the outlet element (grill with filter, ventilation louvre<br />

or single opening) must be taken into consideration to determine ventilation<br />

flow.<br />

Characteristics<br />

Reference<br />

Colour RAL-7032 VF560 VF560/115 VF850 VF850/115 VF850/400<br />

Colour RAL-7035 VF560R35 VF560/115R35 VF850R35 VF850/115R35 VF850/400R35<br />

Flow rate with filter (m 3 /h) (50/60 Hz) 562/586<br />

838 (50 Hz)<br />

983 (50 Hz)<br />

931 (50 Hz)<br />

803 (60 Hz)<br />

944 (60 Hz)<br />

803 (60 Hz)<br />

Flow rate with 1 outlet grill (m 3 /h) (50/60 Hz) 473/477<br />

718 (50 Hz)<br />

843 (50 Hz)<br />

798 (50 Hz)<br />

568 (60 Hz)<br />

642 (60 Hz)<br />

568 (60 Hz)<br />

Flow rate with 2 outlet grills (m 3 /h) (50/60 Hz) 481/485<br />

728 (50 Hz)<br />

854 (50 Hz)<br />

809 (50 Hz)<br />

585 (60 Hz)<br />

667 (60 Hz)<br />

585 (60 Hz)<br />

Voltage 230 V (50/60 Hz) 115 V (50/60 Hz) 230 V (50/60 Hz) 115 V (50/60 Hz) 400 V (50/60 Hz)<br />

Voltage range 207...244 V 103...122 V 207...244 V 103...122 V 396...466 V<br />

Absorbed power (50/60 Hz) 68/85 W 65/83 W 150/195 W 145/182 W 40/40 W<br />

Intensity max. (50/60 Hz) 0.52/0.37 A 0.60/0.72 A 0.65/0.85 A 0.13/1.6 A 0.22/0.23 A<br />

Noise level 59/59 dB (A) 76/75 dB (A) 78/77 dB (A) 77/75 dB (A)<br />

Bearing<br />

Balls<br />

IP Degree of protection (with standard filter) 54<br />

External dimensions (mm) 336 316 161 336 316 162<br />

Cut-out dimensions (mm) 291 291<br />

Weight 3.2 kg 4.1 kg<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –15 a +60 °C<br />

Storage temperature –40 a +50 °C<br />

100% operating factor 100%<br />

Maximum static pressure (0 m 3 /h airflow) 140 Pa 170 Pa<br />

Outlet grills<br />

Characteristics<br />

Reference<br />

Colour RAL-7032<br />

FS560<br />

Colour RAL-7035<br />

FS560R35<br />

IP 54<br />

Outside dimensions (mm) (height width depth) 336 316 18<br />

Material<br />

Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0<br />

Service temperature –20 a +70 °C<br />

Replacement filter<br />

Characteristics<br />

Standard filter (filtration capacity: G2 conforming to EN 779)<br />

OEM filter (oily environment)<br />

Fine filter<br />

Anti-insect filter<br />

Reference<br />

F560<br />

F560OEM<br />

FF560<br />

FAIN560<br />

6/22


VF<br />

Forced ventilation system<br />

IP54 (EN 60529) / IP55 (with IP55 protection kit)<br />

Dimensions (mm)<br />

FIG. 1<br />

VF560-VF560/115 Fans<br />

18<br />

336<br />

290.7<br />

225<br />

291 x 291<br />

291 291<br />

316<br />

160.5<br />

9.5<br />

FIG. 2<br />

VF650-VF650/115 Fans<br />

18<br />

336<br />

290.7<br />

280<br />

291 x 291<br />

316<br />

162<br />

9.5<br />

FIG. 3<br />

FIG. 4<br />

“Pressure/Flow” Diagram<br />

Pa<br />

VF560<br />

Pa<br />

VF850<br />

Difference in static pressure (Pa)<br />

Difference in static pressure (Pa)<br />

Flow rate m 3 /h<br />

Flow rate m 3 /h<br />

6/23


VF<br />

Accessories for forced and natural ventilation systems<br />

Circulation fan<br />

c To circulate the air inside the enclosures.<br />

c Fixing with screws.<br />

c User protection according to DIN 31001.<br />

Reference<br />

Flow rate<br />

(m 3 /h)<br />

Tension<br />

<strong>Electric</strong>al<br />

power (W)<br />

Weight<br />

(kg)<br />

VC150 150 230 V 50 Hz 17 0.82<br />

IP20 Fans<br />

c For uses where a high degree of protection is not required (IP20).<br />

c Self-extinguishing thermoplastic grille with a black fi nish.<br />

c Fixing to the enclosure with four M4 screws.<br />

Reference<br />

Flow rate<br />

(m 3 /h)<br />

Tension<br />

<strong>Electric</strong>al power (W)<br />

Weight<br />

(kg)<br />

Dimensions<br />

(mm)<br />

Outlet grilles<br />

Standard filter<br />

V65 65 230 V - 50 Hz 17 0.69 124 124 55 FS65 F65<br />

V65/115 65 115 V - 50 Hz 17 0.69 124 124 55 FS65 F65<br />

EMC external kit IP55<br />

c They are directly mounted onto the fans and grilles to protect the<br />

equipment from electromagnetic interference.<br />

Reference<br />

For fans and grilles with dimensions (mm)<br />

VF85/KITIPCEM 170 150<br />

VF165/KITIPCEM 268 248<br />

VF560/KITIPCEM 336 316<br />

6/24


VF<br />

Accessories for forced and natural ventilation systems<br />

Fans for 19” racks<br />

c Height: 1 U.<br />

c Connection cable.<br />

References:<br />

CBMV100 (L = 1 m).<br />

CBMV200 (L = 2 m).<br />

Reference<br />

Specifications<br />

Flow rate*<br />

(m 3 /h)<br />

Noise dB (A)<br />

Tension<br />

(V/Hz)<br />

<strong>Electric</strong>al power<br />

(W)<br />

VR312<br />

With 3 fans with a depth of 180 mm<br />

With thermostat and indicator light<br />

312 50 230/50-60 34<br />

VR400 With 3 fans with a depth of 180 mm 400 50 230/50-60 36<br />

VR624<br />

With 3 fans with a depth of 180 mm<br />

With thermostat and indicator light<br />

624 50 230/50-60 68<br />

VR800 With 6 fans with a depth of 310 mm 800 52 230/50-61 72<br />

VR1200 With 9 fans with a depth of 445 mm 1200 55 230/50-62 108<br />

*Flow measured without counter-pressure.<br />

19” 2 U tangential fan<br />

c Fan with air drawn in from the front and vertically channelled through the<br />

19” rack.<br />

c Height: 2 U.<br />

Reference<br />

Flow rate (m 3 /h)<br />

Noise<br />

dB (A)<br />

Tension (V/Hz)<br />

<strong>Electric</strong>al power<br />

(W)<br />

VTR300 300 53 230/50-60 37<br />

6/25


VF<br />

Accessories for forced and natural ventilation systems<br />

Fans<br />

c Turbine-type fan motor for ventilation/extraction.<br />

Ventilation filters<br />

c Outlet fi lter unit for enclosure ventilation. For fi tting to MV fans.<br />

Protective grille<br />

c Protective grille for enclosure fan motors. For fi tting to MV fans.<br />

Power connection cable for fans<br />

c For fi tting to the connection terminal of the fan motors.<br />

References:<br />

CBMV100 (L = 1 m).<br />

CBMV200 (L = 2 m).<br />

Reference<br />

Flow<br />

(m 3 /h)<br />

Tension<br />

(V/Hz)<br />

Power absorbed<br />

(W)<br />

Noise<br />

(dB) (A)<br />

External dimensions<br />

(mm)<br />

MV156 156 230/50-60 17/15 42 120 120 38 FS156 RV156<br />

MV156/115 156 120/50-60 17/15 42 120 120 38 FS156 RV156<br />

MV35 35 230/50-60 16/14 32 80 80 25 FS35 RV35<br />

MV35/115 35 120/50-60 16/14 32 80 80 25 FS35 RV35<br />

Filter<br />

Grille<br />

6/26


VF<br />

Accessories for forced and natural ventilation systems<br />

Ceiling ventilation<br />

c Ventilation accessories to be mounted on the top of OLN enclosures..<br />

VMT340<br />

VFT400<br />

340 90 6<br />

270<br />

68 22<br />

340<br />

270<br />

90 6<br />

68 22<br />

190<br />

ø7<br />

270<br />

340<br />

290.5<br />

270<br />

270<br />

340<br />

290.5<br />

6<br />

270<br />

228<br />

6<br />

228<br />

External dimensions (mm)<br />

Reference Description Height Width Depth Flow rate (m 3 /h) Tension (V/Hz) <strong>Electric</strong>al power (W)<br />

VMT340 Natural airing device 93 340 340 - - -<br />

VFT400<br />

Forced ventilation device<br />

(supplied with electric fan)<br />

90 340 340 400 230/50-60 85<br />

6/27


VF<br />

Accessories for forced and natural ventilation systems<br />

Outlet grilles with filter IP54<br />

c Injected thermoplastic, self-extinguishing, conforming to UL94 V0.<br />

c Operating temperature from –10 to +60 °C.<br />

c IP55 with IP55 watertightness protection kit.<br />

Reference<br />

Dimensions<br />

(mm)<br />

RAL-7032 RAL-7035 Total (exterior) Machined<br />

FS38 FS38R35 137 117 92 92<br />

FS85 FS85R35 170 150 125 125<br />

FS165 FS165R35 268 248 223 223<br />

FS560 FS560R35 336 316 291 291<br />

VANDAL PROOF SYSTEM<br />

Reference<br />

Dimensions<br />

(mm)<br />

Set of<br />

RAL-7011<br />

ANVF 137 177 2<br />

ANVF 170 150 2<br />

ANVF 268 248 2<br />

ANVF 336 316 2<br />

POWER CONNECTION CABLE FOR FANS<br />

Reference<br />

Length (mm)<br />

CBMV100 1000<br />

CBMV200 2000<br />

Filters<br />

Reference Concept For fans and grilles with dimensions (mm)<br />

F38<br />

137 117<br />

F85 Standard filter (G2 class<br />

170 150<br />

F165 conforming to EN 779)<br />

268 248<br />

F560 336 316<br />

F85OEM<br />

170 150<br />

F165OEM “Greasy environments” OEM filter<br />

268 248<br />

F560OEM 336 316<br />

FF85<br />

170 150<br />

Fine filter (G3 class conforming<br />

FF165 268 248<br />

to EN 779)<br />

FF560 336 316<br />

FAIN38<br />

137 117<br />

FAIN85 170 150<br />

“Anti-insect” filters<br />

FAIN165 268 248<br />

FAIN560 336 316<br />

Protection kit IP55<br />

For grilles and fans<br />

(mm)<br />

Aluzinc<br />

RAL-7032<br />

Aluzinc<br />

RAL-7035<br />

Stainless steel<br />

Replacement<br />

filter<br />

170 150 VF85/KITIPALZ32 VF85/KITIPALZ35 VF85/KITIP F85/KITIP<br />

268 248 VF165/KITIPALZ32 VF165/KITIPALZ35 VF165/KITIP F165/KITIP<br />

336 316 VF560/KITIPALZ32 VF560/KITIPALZ35 VF560/KITIP F560/KITIP<br />

6/28


VF<br />

Accessories for forced and natural ventilation systems<br />

Lifting screws<br />

c Lifting screws for the top of the OLN enclosures<br />

to improve ventilation<br />

c Reference: VET12.<br />

Ventilation devices<br />

c To connect the inside of the enclosure with the exterior atmosphere and<br />

prevent condensation. Can be fixed onto the outside (references VM25<br />

and VN27) or onto the internal sides connected with the rear self-ventilating<br />

windows of the POLYMEL enclosures (reference VM35).<br />

Reference<br />

Specifications<br />

VM25 For coupling to the exterior of all polyester enclosures<br />

VM25<br />

VM27<br />

VM27 For coupling to the exterior of all polyester enclosures<br />

VM35 For coupling to the interior of POLYMEL enclosures<br />

VM35<br />

Ventilation slots<br />

c Natural ventilation. Guarantee air circulation inside the enclosure.<br />

Texturised RAL-7032 colour<br />

F<br />

A<br />

F<br />

C<br />

= =<br />

B<br />

Ø5.3<br />

D<br />

E<br />

Reference A (mm) B (mm) C (mm) D (mm) E (mm) F (mm)<br />

TR1 144 62 36 110 - -<br />

TR2 208 90 72 94 190 -<br />

TR3 244 90 72 130 226 -<br />

TR4 345 118 100 231 237 115.5<br />

TR5 345 148 130 231 327 115.5<br />

TR6 445 148 130 297 427 148.5<br />

6/29


Air/air exchangers<br />

In details<br />

1<br />

2<br />

5<br />

4<br />

3<br />

AIR/AIR EXCHANGERS<br />

Reference Performance Voltage Mounting<br />

Dimensions (mm)<br />

Height Width Depth<br />

Integrated<br />

thermostat<br />

ICL15AI 15 W/°K 230 V 50/60 Hz Side 700 270 144 Yes<br />

ICL35AI 35 W/°K 230 V 50/60 Hz Side 780 325 144 Yes<br />

ICL35AILC 35 W/°K 230 V 50/60 Hz Side 780 325 144 No<br />

ICL35AIN 35 W/°K 230 V 50/60 Hz Side 780 325 144 Yes<br />

ICL60AI 70 W/°K 230 V 50/60 Hz Side 1480 450 144 Yes<br />

ICT50AI 50 W/°K 230 V 50/60 Hz Top 340 600 360 Yes<br />

See the accessories on pages 6/33 and 6/35.<br />

6/30


1 Available in two<br />

versions:<br />

c Side-mounting.<br />

c Top-mounting.<br />

Performance from 15 to<br />

70 W/°K that allows you<br />

to install the equipment<br />

best suited to your needs<br />

in each case.<br />

2 The exchangers<br />

come equipped with an<br />

adjustable thermostat<br />

that controls the interior<br />

temperature of the<br />

enclosure:<br />

c An auxiliary control<br />

thermostat does not<br />

need to be installed.<br />

c It guarantees the<br />

correct reading of the<br />

interior temperature of<br />

the enclosure.<br />

Temperature control range<br />

from +20 to +50 ºC.<br />

3 The air-air exchangers<br />

do not need inlet filters,<br />

thus reducing periodic<br />

maintenance.<br />

4 The interior and<br />

exterior air circuits are<br />

perfectly separated<br />

and maintain the IP54<br />

watertightness of the<br />

enclosure.<br />

Two fans guarantee air<br />

circulation in each of the<br />

circuits:<br />

c Circulation fan for air<br />

inside the enclosure.<br />

The internal circuit fan<br />

is always on, thereby<br />

maintaining a uniform<br />

temperature inside<br />

the enclosure and<br />

preventing hot spots.<br />

c Circulation fan<br />

for air outside the<br />

enclosure.<br />

The interior thermostat<br />

controls the fan and<br />

starts it when the<br />

temperature of the air<br />

inside the enclosure<br />

is above the required<br />

temperature.<br />

5<br />

c Fast access to<br />

the interior makes<br />

unit cleaning and<br />

maintenance easy.<br />

c The special<br />

configuration of the<br />

exchange battery<br />

makes it easy to clean.<br />

The spaces between<br />

the slats make it<br />

possible to access<br />

the inside aluminium<br />

walls for easy and fast<br />

cleaning.<br />

6/31


ICT / ICL / AI<br />

Air/air exchangers<br />

Side-mounting<br />

General features:<br />

c Main components: thermostatic adjustment system, exchange battery,<br />

circulation<br />

c The temperature required in the enclosure may be adjusted from +25 ºC to<br />

+50 ºC.<br />

c The interior and exterior air circuits are perfectly separated (IP54). Two fans<br />

guarantee air circulation in each one of the circuits; the inside circuit (that<br />

moves the enclosure air) is permanently on, which makes it possible to<br />

avoid hot spots in the electric circuits or the components.<br />

c The equipment is delivered with a drilling template, an installation guide,<br />

and a water and air-tightness gasket to be inserted between the exchanger<br />

and the enclosure.<br />

Conditions of use:<br />

c The exchangers can only be used when the outside temperature is 5 °C<br />

below the temperature required inside the enclosure.<br />

c The enclosure should be airtight to avoid the penetration of outside air<br />

(IP54 minimum).<br />

Reference<br />

ICL15AI ICL35AI ICL35AILC<br />

ICL35AIN<br />

(internal mounting)<br />

ICL60AI<br />

Cooling specifications<br />

Specific power (1) 15 W/°K 35 W/°K 35 W/°K 35 W/°K 70 W/°K<br />

Exterior circuit airflow 200 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h<br />

Inside circuit airflow 200 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h 450 m 3 /h<br />

Exchange surface 1.23 m 2 1.5 m 2 1.5 m 2 1.5 m 2 6.6 m 2<br />

Adjustment Yes Yes No Yes Yes<br />

Type Thermostatic Thermostatic - Thermostatic Thermostatic<br />

Temperature control range 25-50 °C 25-50 °C - 25-50 °C 25-50 °C<br />

Nature of the fluid Air Air Thermostatic Air Air<br />

<strong>Electric</strong>al specifications<br />

Power supply voltage 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz<br />

Start-up/rated intensity 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A 2.1/0.7 A<br />

<strong>Electric</strong>al power absorbed 150 W 150 W 150 W 150 W 150 W<br />

Physical features<br />

External dimensions<br />

A B C (mm)<br />

700 270 144 780 325 144 780 325 144 780 325 144 1480 450 144<br />

Internal IP circuit IP54 IP54 IP54 IP54 IP54<br />

External IP circuit IP22 IP22 IP22 IP22 IP22<br />

Weight 12 kg 15 kg 15 kg 15 kg 35 kg<br />

Noise level 64 dB (A) 64 dB (A) 64 dB (A) 64 dB (A) 64 dB (A)<br />

(1) Power in W is obtained by formula: specifi c power temperature difference between interior and exterior of enclosure.<br />

Example: for exchanger ref. ICL35AI for a difference of 10 °C, the system power is 35 10 = 350 W.<br />

6/32


ICT / ICL / AI<br />

Air/air exchangers<br />

Dimensions (mm)<br />

FIG. 1<br />

External mounting<br />

FIG. 2<br />

Internal mounting<br />

I<br />

=<br />

J<br />

=<br />

I<br />

B<br />

E<br />

F<br />

K<br />

G<br />

E<br />

A<br />

80<br />

136<br />

D<br />

G<br />

H<br />

= =<br />

(1)<br />

A<br />

80<br />

D<br />

136<br />

H<br />

= =<br />

26<br />

144<br />

(C)<br />

K<br />

ø 30<br />

B<br />

25<br />

25<br />

(1)<br />

144<br />

28 (C) 26<br />

J<br />

F<br />

(1) Filter grilles.<br />

Ref.: RPF (not included in the standard supply).<br />

ICL15AI<br />

ICL35AI<br />

ICL35AILC<br />

ICL35AIN<br />

ICL60AI<br />

A 700 780 1480<br />

B 270 325 450<br />

C 144 144 144<br />

D 220 294 420<br />

E 167 183.5 183.5<br />

F 82 77.5 77.5<br />

G 13 35.5 35.5<br />

H 366 413 1113<br />

I 226 266 393<br />

J 40 52 115<br />

K 4 8 Ø 4 8 Ø 6 8 Ø<br />

Accessories (side mounting)<br />

c Optional grille to mount the exchangers inside the enclosure.<br />

Reference<br />

For mounting with the exchanger<br />

RPF15AI ICL15AI<br />

RPF35AI ICL35AI/ICL35AILC<br />

RPF70AI ICL60AI<br />

Installation (internal mounting)<br />

6/33


ICT / ICL / AI<br />

Air/air exchangers<br />

Top mounting<br />

General features:<br />

c Main components: thermostatic adjustment system, exchange battery,<br />

circulation fans for air from the inside and outside circuits.<br />

c The temperature required in the enclosure may be adjusted from +25 ºC to<br />

+50 ºC.<br />

c The interior and exterior air circuits are perfectly separated (IP54). Two fans<br />

guarantee air circulation in each one of the circuits; the inside circuit (that<br />

moves the enclosure air) is permanently on, which makes it possible to<br />

avoid hot spots in the electric circuits or the components.<br />

ICT50AI<br />

c The equipment is delivered with a drilling template, an installation guide,<br />

and a water and air-tightness gasket to be inserted between the exchanger<br />

and the enclosure.<br />

Conditions of use:<br />

c The exchangers can only be used when the outside temperature is 5 °C<br />

below the temperature required inside the enclosure.<br />

c The enclosure should be airtight to avoid the penetration of outside air.<br />

Reference<br />

ICT50AI<br />

Cooling specifications<br />

Specific power (1)<br />

50 W/°K<br />

Exterior circuit airflow 450 m 3 /h<br />

Interior circuit airflow 450 m 3 /h<br />

Exchange surface 3.3 m 2<br />

Adjustment<br />

Yes<br />

Type<br />

Thermostatic<br />

Temperature control range 20-50 °C<br />

Nature of the fluid Air<br />

<strong>Electric</strong>al specifications<br />

Power supply voltage<br />

230 V 50/60 Hz<br />

Start-up/rated intensity 2.1/0.7 A<br />

<strong>Electric</strong>al power absorbed<br />

150 W<br />

Physical features<br />

External dimensions A B C (mm) 390 600 365<br />

Internal IP circuit<br />

IP54<br />

External IP circuit<br />

IP22<br />

Weight<br />

19 kg<br />

Noise level<br />

64 dB (A)<br />

(1) Power in W is obtained by formula: specifi c power temperature difference between inferior and exterior of enclosure.<br />

6/34


ICT / ICL / AI<br />

Air/air exchangers<br />

Dimensions (mm)<br />

FIG. 1<br />

Top mounting: dimensions<br />

600 26<br />

360<br />

340<br />

115 370<br />

300<br />

ø 8<br />

290<br />

360<br />

20<br />

70 310 70<br />

600<br />

Accessories (top mounting)<br />

c Intermediate frame for coupling the MMI64 exchanger to the 600 mm wide<br />

and 400 mm deep enclosures.<br />

c Ref. MMI64.<br />

26<br />

360<br />

Frame MMI64<br />

6/35


Air/water exchangers<br />

In details<br />

1<br />

2<br />

5<br />

3<br />

4<br />

AIR/WATER EXCHANGERS<br />

References<br />

Cooling power L35/W<br />

10/200 l/h<br />

Voltage<br />

Dimensions (mm)<br />

Height Width Depth<br />

Mounting<br />

ICL1800AG 1800 W 230 V 50/60 Hz 830 360 113 Side<br />

ICT1800AG 1800 W 230 V 50/60 Hz 310 600 365 Top<br />

6/36


Maximum Safety<br />

1 Available in two<br />

versions: Top and side<br />

mounting.<br />

2 The exchangers<br />

come with an adjustable<br />

thermostat that controls<br />

the inside temperature of<br />

the enclosure:<br />

c It avoids the installation<br />

of an auxiliary control<br />

thermostat.<br />

c It guarantees the<br />

correct reading of the<br />

inside temperature of the<br />

enclosure.<br />

Temperature adjustment<br />

range: +20 to +50 ºC.<br />

ANTI-LEAK<br />

detection system<br />

3 It has an electricallyoperated<br />

valve in the<br />

water inlet which,<br />

controlled by the<br />

thermostat, adjusts<br />

temperature and avoids<br />

possible condensation.<br />

It has an anti-leak<br />

detection system that<br />

cuts off the water supply<br />

if it detects a loss in the<br />

circuit.<br />

4 The IP54<br />

watertightness is<br />

guaranteed.<br />

The recirculation fan<br />

of the enclosure inside<br />

air is on permanently,<br />

which maintains an<br />

even temperature inside<br />

the enclosure and thus<br />

avoids the appearance of<br />

hot spots.<br />

5 Comfortable and easy to assemble and<br />

disassemble. Fast access to the inside makes for easy<br />

cleaning and maintenance of the unit.<br />

Because it is water cooled, there is no outside air<br />

circuit, and no filters are needed, thus reducing<br />

periodical maintenance.<br />

6/37


ICT / ICL / AG<br />

Air/water exchangers<br />

Top and side mounting<br />

General features:<br />

c Main components: control system, exchange cassette, circulation fans for<br />

internal circuit.<br />

c The temperature required in the enclosure can be controlled within a range of<br />

+25 to +50 ºC.<br />

c The alarm which detects an interruption in the water circuit triggers closing<br />

of an N/O contact. This contact can be used to actuate a pilot light or<br />

siren, or it can be connected to a PLC input. In the event of the alarm being<br />

triggered, the water supply is automatically cut off.<br />

c System to evacuate condensation water to the outside.<br />

Conditions of use:<br />

c The air-water exchangers can be used even if the external temperature is<br />

superior to the temperature required within the enclosure.<br />

c The enclosure should be airtight in order to prevent entry of external air,<br />

IP54 minimum.<br />

Reference<br />

ICT1800AG<br />

ICL1800AG<br />

Cooling specifications<br />

Specific power A 35 W 10-200 l/h 1800 W 1800 W<br />

Max. water pressure 1 MPa 1 MPa<br />

Exterior circuit airflow 250 m 3 /h 350 m 3 /h<br />

Adjustment Yes Yes<br />

Type Thermostatic Thermostatic<br />

Temperature control range 25-50 °C 25-50 °C<br />

Nature of the fluid Water Water<br />

<strong>Electric</strong>al specifications<br />

Power supply voltage 230 V 50/60 Hz 230 V 50/60 Hz<br />

Start-up/rated intensity 1/0.5 A 1/0.5 A<br />

<strong>Electric</strong>al power absorbed 90 W 90 W<br />

Type of alarm Dry contact Dry contact<br />

Physical features<br />

External dimensions A B C (mm) 310 600 365 830 355 110<br />

IP (EN 60529) IP54 IP54<br />

Weight 26 kg 19 kg<br />

Noise level 64 dB (A) 62 dB (A)<br />

Mounting Top Side<br />

6/38


=<br />

=<br />

ICT / ICL / AG<br />

Air/water exchangers<br />

Dimensions<br />

FIG. 1<br />

Top mounting exchanger<br />

Top mounting Ref.: ICT1800AG<br />

Included with unit:<br />

=<br />

=<br />

497<br />

430<br />

c Drilling template.<br />

40.5 61.5<br />

c Installation accessories.<br />

c Installation and operating<br />

instructions.<br />

268 236 236<br />

280<br />

332<br />

Front of the enclosure<br />

600<br />

310<br />

Water inlet-outlet<br />

Condensation water outlet<br />

FIG. 2<br />

Side mounting Ref.: ICL1800AG<br />

Included with unit:<br />

Side mounting exchanger<br />

300<br />

20<br />

c Drilling template.<br />

105<br />

c Installation accessories.<br />

c Installation and operating<br />

instructions.<br />

c For internal or external mounting.<br />

830<br />

180<br />

300<br />

410<br />

750<br />

150<br />

ø 8<br />

113<br />

360<br />

FIG. 3<br />

Curves<br />

Power absorbed at a water fl ow rate for 100 l/h Power absorbed at a water fl ow rate for 200 l/h Power absorbed at a water fl ow rate for 300 l/h<br />

Power Potencia exchanged disipada por by el the intercambiador exchangers (W)<br />

3500<br />

Td = Temperatura deseada en el interior del armario<br />

3000<br />

Td=50°C<br />

2500 Td=45°C<br />

Td=40°C<br />

2000 Td=35°C<br />

1500 Td=30°C<br />

Td=25°C<br />

1000 Td=20°C<br />

500<br />

0<br />

5 10 15 20 25 30<br />

Water Temperatura temperature del agua ºC °C<br />

Potencia Power exchanged disipada por by el the intercambiador exchangers (W) (W)<br />

4000<br />

4000<br />

3500<br />

3500 Td=50°C<br />

Td=50°C<br />

3000<br />

3000 Td=45°C<br />

Td=45°C<br />

Td=40°C<br />

2500 Td=40°C<br />

2500<br />

Td=35°C<br />

Td=35°C<br />

2000<br />

2000 Td=30°C<br />

Td=30°C<br />

1500<br />

1500 Td=25°C<br />

Td=25°C<br />

1000 Td=20°C<br />

500<br />

Td=20°C<br />

1000<br />

500<br />

0<br />

5 10 15 20 25 30<br />

0 5 10 15 20 25 30<br />

Water temperature ºC<br />

Temperatura del agua °C<br />

Water Temperatura temperature del agua ºC°C<br />

Power Potencia exchanged disipada por by el the intercambiador exchangers (W)<br />

Example: for water at 100 l/h at 15 ºC with a preferred temperature of 35 ºC<br />

Power = 1400 W<br />

6/39


6/40<br />

Cooling units<br />

CLL/CLT standard control


The inside and outside air circuits are perfectly<br />

separated and maintain IP54 watertightness of the<br />

enclosure.<br />

Two fans guarantee air circulation in each one of the<br />

circuits:<br />

c Internal circuit fan. It is on permanently, which<br />

maintains an even temperature inside the enclosure,<br />

avoids the appearance of hot spots and guarantees<br />

a correct reading of the inside temperature of the<br />

enclosure by the set-point thermostat.<br />

c External circuit fan.<br />

The inside thermostat controls the fan and starts<br />

it up when the temperature of the air inside the<br />

enclosure is above the maximum value displayed.<br />

Easy access to the condenser allows simplified<br />

cleaning through blowing.<br />

Disassemble of the cooling units is not necessary for<br />

the high temperature compressor and external fan<br />

maintenances.<br />

The air conditioning units<br />

come with an adjustable<br />

thermostat that controls<br />

the inside temperature of<br />

the enclosure:<br />

c It avoids the installation<br />

of an auxiliary control<br />

thermostat.<br />

c It guarantees the<br />

correct reading of the<br />

inside temperature of<br />

the enclosure.<br />

Temperature adjustment<br />

range: +20 ºC to +50 ºC<br />

(supplied factory-adjusted<br />

to 35 ºC).<br />

ENVIRONMENTALLY<br />

friendly<br />

c The top mounting models feature a condensation<br />

water automatic evaporation system with an<br />

exclusive safety system that switches off the<br />

apparatus or issues an alarm if the condensation<br />

water level is exceeded.<br />

c They also feature an exclusive voluntary unloading<br />

system that makes it possible to empty the water<br />

from the condensation tray.<br />

c Available in two<br />

versions: top and side<br />

mounting versions.<br />

c The power of<br />

mechanically regulated<br />

cooling units ranges<br />

from 240 to 3100 W.<br />

There is always<br />

equipment which is<br />

suited to your needs.<br />

c Comfortable and<br />

easy to assemble and<br />

disassemble.<br />

c The side installation<br />

models can be semirecessed<br />

with the<br />

use of the specific<br />

accessory.<br />

They are equipped with an<br />

automatic reset pressostat<br />

and a contact thermostat that<br />

detects the overpressure in<br />

the compressor circuit and<br />

interrupts it and the outside<br />

circuit fan, thus avoiding<br />

possible faults.<br />

Fitted with a fault warning<br />

relay, it provides the possibility<br />

of operating an alarm indicator,<br />

shutting down the apparatus.<br />

Fitted with high pressure<br />

compressors that allow<br />

them to work at outside<br />

temperatures of up to +55 ºC.<br />

Environmentally friendly.<br />

Use of R134a ecological gas.<br />

6/41


COOLING UNITS<br />

Selection guide<br />

SIDE-MOUNTING<br />

References<br />

Power EN 14511<br />

L35 - L35<br />

Voltage in V-Hz Dimensions (mm) Adjustment<br />

CLL240 240 W (819 Btu/h) 230-50/60 450 350 140 Thermostat<br />

CLL370 370 W (1260 Btu/h) 230-50/60 620 300 170 Thermostat<br />

CLL760 760 W (2594 Btu/h) 230-50/60 800 350 195 Thermostat<br />

CLL1050 1050 W (3584 Btu/h) 230-50/60 900 400 195 Thermostat<br />

CLLMP1100 1100 W (3755 Btu/h) 230-50/60 1010 400 240 Microprocessor<br />

CLLMP1400 1400 W (4780 Btu/h) 230-50/60 1010 400 240 Microprocessor<br />

CLLMP1400T<br />

1400 W (4780 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

1010 400 240 Microprocessor<br />

CLL1650 1650 W (5631 Btu/h) 230-50/60 1000 400 220 Thermostat<br />

CLL1650T<br />

1800 W (6143 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

1000 400 220 Thermostat<br />

CLLMP1800T<br />

1800 W (6145 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

1010 400 240 Microprocessor<br />

6/42


COOLING UNITS<br />

Selection guide<br />

TOP-MOUNTING<br />

References<br />

Power EN 14511<br />

L35 - L35<br />

Voltage in V-Hz Dimensions (mm) Adjustment<br />

CLT760 760 W (2.594 Btu/h) 230-50/60 340 600 350 Thermostat<br />

CLT1050 1050 W (3.584 Btu/h) 230-50/60 400 700 400 Thermostat<br />

CLTMP1400 1400 W (4.780 Btu/h) 230-50/60 415 750 412 Microprocessor<br />

CLT1460 1460 W (4.984 Btu/h) 230-50/60 400 700 400 Thermostat<br />

CLT1650 1650 W (5.631 Btu/h) 230-50/60 430 700 400 Thermostat<br />

CLTMP1800T<br />

1800 W (6.145 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

415 750 412 Microprocessor<br />

CLT1650T<br />

2000 W (6.826 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

430 700 400 Thermostat<br />

CLT2450T<br />

2450 W (8.368 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

470 800 450 Thermostat<br />

CLT3100T<br />

3100 W (10.583 Btu/h)<br />

3 400 V 50 Hz/<br />

3 440 V 60 Hz<br />

470 800 450 Thermostat<br />

6/43


CLL<br />

Cooling units<br />

Mechanical control<br />

Side mounting<br />

Cooling units for electronic switchboards:<br />

c Respect for the environment by using the ecological gas R134a.<br />

c Cooling power of 240 W to 3100 W.<br />

c Possibility of partial flush mounting for all side mounting models.<br />

General features:<br />

c Temperature setting can be adjusted from +20 to +50 ºC.<br />

c As standard, the units are fitted with an automatic reset pressure switch. A<br />

value higher than safety pressure value (on the high pressure circuit) actuates<br />

compressor and external fan switch-off.<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

c The equipment is fitted with switches enabling an alarm report.<br />

c Cooling power of 240 W to 3100 W.<br />

CLL760<br />

c Possibility of partial flush mounting.<br />

Reference CLL240 CLL370 CLL760<br />

Voltage<br />

230 V 50/60 Hz<br />

Cooling power (50/60 Hz) acording to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

240 W (819 Btu/h)<br />

190 W (649 Btu/h)<br />

370/390 W (1263/1331 Btu/h)<br />

300/310 W (1024/1058 Btu/h)<br />

760/810 W (2594/2765 Btu/h)<br />

610/640 W (2082/2184 Btu/h)<br />

Dimensions<br />

Height<br />

Width<br />

Depth<br />

450 mm<br />

350 mm<br />

140 mm + (15 mm inside)<br />

620 mm<br />

300 mm<br />

170 mm<br />

800 mm<br />

350 mm<br />

195 mm<br />

Current<br />

Start-up<br />

Nominal<br />

2.8 A<br />

0.7 A<br />

5.8/6.7 A<br />

1.5/1.8 A<br />

7.7/8.8 A<br />

2/2.3 A<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

140 W<br />

160 W<br />

290/330 W<br />

330/380 W<br />

380/440 W<br />

440/500 W<br />

EER energetic performance<br />

L35 - L35 1.7 1.3/1.2 2.0/1.8<br />

Temperature regulator Thermostat<br />

Temperature setting range 20 - 45 °C 20 - 50 °C<br />

Maximum external temperature 50 °C 55 °C<br />

Noise level 58 dB (A) 65 dB (A) 67 dB (A)<br />

Airflow<br />

Internal circuit<br />

External circuit<br />

Alarm type contact free power<br />

160 m 3 /h<br />

320 m 3 /h<br />

160/175 m 3 /h<br />

210/230 m 3 /h<br />

350/385 m 3 /h<br />

350/385 m 3 /h<br />

Inverter contact<br />

Weight 15 kg 21 kg 33 kg<br />

Cooling gas R134a (0.25 kg) R134a (0.3 kg) R134a (0.5 kg)<br />

Internal IP circuit 54 54 54<br />

External IP circuit 34 34 34<br />

External circuit filter Optional Yes<br />

Mounting model<br />

Side<br />

Recommended protection (fuse curve) T1.6 A T3 A T3 A<br />

6/44


CLL<br />

Cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

CLL240: Dimensions<br />

Cut-out dimensions<br />

Ref. CLL240<br />

External mounting<br />

Partial fl ush mounting<br />

FIG. 2<br />

Side mounting: dimensions<br />

26<br />

P<br />

Ref. CLL370 and CLL760<br />

C<br />

E<br />

H<br />

G<br />

Q<br />

30<br />

A<br />

= =<br />

B<br />

K<br />

ø S<br />

M<br />

60<br />

R<br />

L<br />

N<br />

D<br />

F<br />

Dimensions in mm CLL370 CLL760<br />

A 260 266<br />

B 0 52<br />

C 80 116<br />

D 40 193,5<br />

E 300 375<br />

F 540 413<br />

G 60 80<br />

H 620 800<br />

K 136 136<br />

L 300 350<br />

M 240 294<br />

N - -<br />

P 170 195<br />

Q 35 149<br />

R 0 24<br />

S 8 8<br />

FIG. 3<br />

Curves<br />

CLL240 50/60 Hz CLL370 50 Hz CLL370 60 Hz<br />

400<br />

700<br />

700<br />

350<br />

Ti [ ºC ]<br />

600<br />

Ti [ ºC ]<br />

600<br />

Ti [ ºC ]<br />

Pf [ W ]<br />

300<br />

250<br />

200<br />

150<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

500<br />

400<br />

300<br />

200<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

500<br />

400<br />

300<br />

200<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

100<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50/60 Hz<br />

100<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

100<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

CLL760 50 Hz<br />

1400<br />

CLL760 60 Hz<br />

1400<br />

Pf [ W ]<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

400<br />

200<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

400<br />

200<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

6/45


CLL<br />

Cooling units<br />

Side mounting<br />

Cooling units for switchboards:<br />

c Respect for the environment by using the ecological gas R134a.<br />

c Automatic evaporation of condensation water on all top mounting models.<br />

c Cooling power of 240 W to 3100 W.<br />

c Possibility of partial flush mounting for all side mounting models.<br />

General features:<br />

c Temperature setting can be adjusted from +20 to +50 ºC.<br />

c As standard, the units are fitted with an automatic reset pressure switch.<br />

A value higher than safety pressure value (on the high pressure circuit)<br />

activates compressor and external fan switch-off.<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

CLL1650<br />

c The equipment is fitted with switches enabling an alarm report.<br />

c Cooling power of 240 W to 3100 W.<br />

c Possibility of partial flush mounting.<br />

Reference CLL1050 CLL1650 CLL1650T<br />

Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />

Cooling power (50/60 Hz) according to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

1050/1100 W<br />

(3584/3755 Btu/h)<br />

840/890 W (2867/3038 Btu/h)<br />

1650/1700 W (5631/5802 Btu/h)<br />

1300/1400 W (4438/4779 Btu/h)<br />

1800/1900 W (6143/6485 Btu/h)<br />

1400/1500 W (4779/5121 Btu/h)<br />

Dimensions<br />

Height<br />

Width<br />

Depth<br />

900 mm<br />

400 mm<br />

195 mm<br />

1000 mm<br />

400 mm<br />

220 mm<br />

Current<br />

Start-up<br />

Nominal<br />

10.1/11.6 A<br />

2.7/3 A<br />

16.1/18.5 A<br />

4.2/4.9 A<br />

6.8/7.9 A<br />

2.1/2.5 A<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

550/580 W<br />

580/660 W<br />

800/920 W<br />

920/1100 W<br />

1200/1400 W<br />

1400/1600 W<br />

EER energetic performance<br />

L35 - L35 2.1/1.9 2.1/1.9 1.5/1.4<br />

Temperature setting range Thermostat<br />

Control range 20 - 50 °C<br />

Max. external ambient temperature 55 °C<br />

Noise level 67 dB (A) 67 dB (A) 69 dB (A)<br />

Airflow<br />

Internal circuit<br />

External circuit<br />

350/385 m 3 /h<br />

510/560 m 3 /h<br />

550/600 m 3 /h<br />

620/680 m 3 /h<br />

Alarm contact Potential-free<br />

Weight 39 kg 42 kg 46 kg<br />

Cooling gas R134a (0.7 kg) R134a (0.75 kg)<br />

Internal IP circuit 54 54 54<br />

External IP circuit 34 34 34<br />

External circuit filter Yes<br />

Mounting model Side<br />

Recommended protection (fuse curve) T4 A T6 A T3 A<br />

6/46


CLL<br />

Cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

Side mounting: dimensions<br />

26<br />

P<br />

C<br />

E<br />

H<br />

G<br />

Q<br />

30<br />

A<br />

= =<br />

B<br />

K<br />

ø S<br />

M<br />

60<br />

R<br />

L<br />

N<br />

D<br />

F<br />

Dimensions in mm CLL1050 CLL1650 CLL1650T<br />

A 300 300 300<br />

B 0 0 0<br />

C 135 135 135<br />

D 30 30 30<br />

E 465 475 475<br />

F 840 840 840<br />

G 100 100 100<br />

H 900 1000 1000<br />

K 180 180 180<br />

L 400 400 400<br />

M 320 320 320<br />

N - 470 470<br />

P 195 220 220<br />

Q 35 25 25<br />

R 195 195 195<br />

S 0 10 10<br />

FIG. 2<br />

Curves<br />

CLL1050 50 Hz CLL1050 60 Hz CLL1650 50 Hz<br />

1800<br />

1800<br />

3000<br />

Pf [ W ]<br />

1600<br />

1400<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1600<br />

1400<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2600<br />

2200<br />

1800<br />

1400<br />

1000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

400<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

400<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

CLL1650 60 Hz CLL1650T 50 Hz CLL1650T 60 Hz<br />

3000<br />

3200<br />

3200<br />

Pf [ W ]<br />

2600<br />

2200<br />

1800<br />

1400<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2800<br />

2400<br />

2000<br />

1600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2800<br />

2400<br />

2000<br />

1600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1000<br />

1200<br />

1200<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

6/47


CLT<br />

Cooling units<br />

Top mounting<br />

Cooling units for electrical switchboards:<br />

c Respect for the environment by using the ecological gas R134a.<br />

c Automatic evaporation of condensation water.<br />

c Cooling power of 760 W to 3100 W.<br />

General features:<br />

c Temperature setting can be adjusted from +20 to +50 ºC.<br />

CLT1050<br />

c As standard, the units are fitted with an automatic reset pressure switch.<br />

A value higher than safety pressure value (on the high pressure circuit)<br />

actuates compressor and external fan switch-off.<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

c The equipment is fitted with switches enabling an alarm report.<br />

c System of automatic recovery and evaporation of condensates.<br />

Reference CLT760 CLT1050 CLT1460<br />

Voltage<br />

230 V 50/60 Hz<br />

Cooling power (50/60 Hz) according to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

760/810 W (2594/2765 Btu/h)<br />

610/640 W (2082/2184 Btu/h)<br />

1050/1100 W (3584/3755 Btu/h)<br />

840/890 W (2867/3038 Btu/h)<br />

1460/1500 W (4983/5121 Btu/h)<br />

1200/1200 W (4096/4096 Btu/h)<br />

Dimensions<br />

Height<br />

Width<br />

Depth<br />

340 mm<br />

600 mm<br />

350 mm<br />

400 mm<br />

700 mm<br />

400 mm<br />

Current<br />

Starting current<br />

Rated current<br />

7.7/8.8 A<br />

2/2.3 A<br />

10.1/11.6 A<br />

2.7/3 A<br />

14.1/16.2 A<br />

3.7/4.3 A<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

380/440 W<br />

440/500 W<br />

550/580 W<br />

580/660 W<br />

730/810 W<br />

810/930 W<br />

EER energetic performance<br />

L35 - L35 2.0/1.8 2.1/1.9 2.1/1.9<br />

Control type thermostatic<br />

Thermostat<br />

Temperature setting range 20 - 50 °C<br />

Maximum external temperature 55 °C<br />

Noise level 67 dB (A) 69 dB (A)<br />

Airflow<br />

Internal circuit<br />

External circuit<br />

Alarm type free power<br />

350/385 m 3 /h<br />

350/385 m 3 /h<br />

400/440 m 3 /h<br />

620/680 m 3 /h<br />

Inverter contact<br />

Weight 33 kg 41 kg 45 kg<br />

Cooling gas R134a (0.5 kg) R134a (0.7 kg) R134a (0.75 kg)<br />

Internal IP circuit 54 54 54<br />

External IP circuit 34 34 34<br />

External circuit filter Yes<br />

Mounting model<br />

Top<br />

Recommended protection (fuse curve) T3 A T4 A T6 A<br />

6/48


CLT<br />

Cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

Top-mounting Ref.: CLT760-CTL1050-CTL1460<br />

J<br />

26<br />

A<br />

B<br />

ø 8<br />

K<br />

250<br />

300<br />

C<br />

M*<br />

D<br />

E<br />

H<br />

F<br />

G<br />

Drilling template for top mounting without<br />

intermediate frame<br />

Reference A B C D E F G H I K M<br />

CLT760 108 350 350 40 136 292 80 600 600 340 600<br />

CLT1050 118 420 400 45 180 328 90 700 700 400 700<br />

CLT1460 118 420 400 45 180 328 90 700 700 400 700<br />

FIG. 2<br />

Curves<br />

CLT760 50 Hz CLT760 60 Hz CLT1050 50 Hz<br />

1400<br />

1400<br />

1800<br />

Pf [ W ]<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1600<br />

1400<br />

1200<br />

1000<br />

800<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

400<br />

400<br />

600<br />

200<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

200<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

400<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

CLT1050 60 Hz CLT1460 50 Hz CLT1460 60 Hz<br />

1800<br />

2400<br />

2400<br />

Pf [ W ]<br />

1600<br />

1400<br />

1200<br />

1000<br />

800<br />

600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2100<br />

1800<br />

1500<br />

1200<br />

900<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2100<br />

1800<br />

1500<br />

1200<br />

900<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

400<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

6/49


CLT<br />

Cooling units<br />

Top mounting<br />

Cooling units for electrical switchboards:<br />

c Respect for the environment by using the ecological gas R134a.<br />

c Automatic evaporation of condensation water.<br />

c Cooling power of 760 W to 3100 W.<br />

General features:<br />

c Temperature setting can be adjusted from +20 to +50 ºC.<br />

CLT1650<br />

c As standard, the units are fitted with an automatic reset pressure switch.<br />

A value higher than safety pressure value (on the high pressure circuit)<br />

actuates compressor and external fan switch-off.<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

c The equipment is fitted with switches enabling an alarm report.<br />

c System of automatic recovery and evaporation of condensates.<br />

Reference CLT1650 CLT1650T<br />

Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />

Cooling power (50/60 Hz) according to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

1650/1700 W (5631/5802 Btu/h)<br />

1300/1400 W (4438/4779 Btu/h)<br />

1650/2100 W (6826/7169 Btu/h)<br />

1600/1700 W (5462/5803 Btu/h)<br />

Dimensions<br />

Height<br />

Width<br />

Depth<br />

430 mm<br />

700 mm<br />

400 mm<br />

Current<br />

Starting current<br />

Rated current<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

16.1/18.5 A<br />

4.2/4.5 A<br />

800/920 W<br />

920/1100 W<br />

6.8 /7.9 A<br />

2.1/2.5 A<br />

1200/1400 W<br />

1400/1700 W<br />

EER energetic performance<br />

L35 - L35 2.1/1.9 1.7/1.5<br />

Temperature regulator<br />

Thermostat<br />

Temperature setting range 20 - 50 °C<br />

Maximum external temperature 55 °C<br />

Noise level 67 dB (A) 69 dB (A)<br />

Airflow<br />

Internal circuit<br />

External circuit<br />

Alarm type free power<br />

550/600 m 3 /h<br />

620/680 m 3 /h<br />

Inverter contact<br />

Weight 47 kg 60 kg<br />

Cooling gas<br />

R134a (1.0 kg)<br />

Internal IP circuit 54<br />

External IP circuit 34<br />

External circuit filter<br />

Yes<br />

Mounting model<br />

Top<br />

Recommended protection (fuse curve) T6 A T3 A<br />

6/50


CLT<br />

Cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

Top mounting Ref.: CLT1650-CLT1650T<br />

J<br />

26<br />

A<br />

B<br />

ø 8<br />

K<br />

250<br />

300<br />

C<br />

M*<br />

D<br />

E<br />

H<br />

F<br />

G<br />

Drilling template for top mounting without<br />

intermediate frame<br />

Reference A B C D E F G H I K M<br />

CLT1650 118 420 400 45 180 328 90 700 700 430 700<br />

CLT1650T 118 420 400 45 180 328 90 700 700 430 700<br />

FIG. 2<br />

Curves<br />

CLT1650 50 Hz<br />

CLT1650 60 Hz<br />

3000<br />

3000<br />

Pf [ W ]<br />

2600<br />

2200<br />

1800<br />

1400<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2600<br />

2200<br />

1800<br />

1400<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

1000<br />

1000<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

3200<br />

CLT1650T 50 Hz<br />

3200<br />

CLT1650T 60 Hz<br />

Pf [ W ]<br />

2800<br />

2400<br />

2000<br />

1600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2800<br />

2400<br />

2000<br />

1600<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1200<br />

1200<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

6/51


CLT<br />

Cooling units<br />

Top mounting<br />

Cooling units for electrical switchboards:<br />

c Respect for the environment by using the ecological gas R134a.<br />

c Automatic evaporation of condensation water.<br />

c Cooling power of 760 W to 3100 W.<br />

General features:<br />

c Temperature setting can be adjusted from +20 to +50 ºC.<br />

c As standard, the units are fitted with an automatic reset pressure switch.<br />

A value higher than safety pressure value (on the high pressure circuit)<br />

actuates compressor and external fan switch-off.<br />

CLT3100T<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

c The equipment is fitted with switches enabling an alarm report.<br />

c System of automatic recovery and evaporation of condensates.<br />

Reference CLT2450T CLT3100T<br />

Voltage<br />

Cooling power (50/60 Hz) according to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

Dimensions<br />

Height<br />

Width<br />

Depth<br />

2450/2600 W (8362/8876 Btu/h)<br />

2000/2100 W (6828/7169 Btu/h)<br />

3 400 V 50 Hz / 3 440 V 60 Hz<br />

470 mm<br />

800 mm<br />

450 mm<br />

3100/3300 W (10580/11266 Btu/h)<br />

2500/2600 W (8532/8876 Btu/h)<br />

Current<br />

Start-up<br />

Nominal<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

8.4/10.1 A<br />

2.6/3.2 A<br />

1500/1800 W<br />

1800/2100 W<br />

9.6/11.3 A<br />

3.0/3.5 A<br />

1700/2000 W<br />

2000/2300 W<br />

EER energetic performance<br />

L35 - L35 1.6/1.5 1.8/1.7<br />

Temperature regulator Thermostat<br />

Control range 20 - 50 °C<br />

Max. external ambient temperature 55 °C<br />

Noise level<br />

69 dB (A)<br />

Internal IP circuit 750/820 m 3 /h<br />

External IP circuit 1200/1310 m 3 /h<br />

Alarm type contact free power<br />

Inverter contact<br />

Weight 65 kg<br />

Cooling gas R134a (1.5 kg) R134a (1.7 kg)<br />

Internal IP circuit 54<br />

External IP circuit 34<br />

External circuit filter Yes<br />

Mounting model Top<br />

Recommended protection (fuse curve) T4 A T4 A<br />

6/52


CLT<br />

Cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

Top mounting Ref.: CLT2450T-CLT3100T<br />

26<br />

800<br />

26<br />

220<br />

360<br />

ø 10<br />

*<br />

470<br />

300<br />

300<br />

450<br />

70<br />

140<br />

380<br />

140<br />

800<br />

800*<br />

* Maximum overall dimensions of the intermediate frame<br />

FIG. 2<br />

Curves<br />

CLT2450T 50 Hz<br />

CLT2450T 60 Hz<br />

4000<br />

4000<br />

Pf [ W ]<br />

3500<br />

3000<br />

2500<br />

2000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

3500<br />

3000<br />

2500<br />

2000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

1500<br />

1500<br />

1000<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

1000<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

5500<br />

CLT3100T 50 Hz<br />

5500<br />

CLT3100T 60 Hz<br />

4900<br />

4900<br />

Pf [ W ]<br />

4300<br />

3700<br />

3100<br />

2500<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

4300<br />

3700<br />

3100<br />

2500<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1900<br />

1900<br />

1300<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

1300<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

6/53


CLL / CLT<br />

Accessories<br />

Frames for partial flush mounting<br />

c For partial flush mounting of the CLL cooling units.<br />

Reference<br />

MECL370<br />

MECL760<br />

MECL1050<br />

MECL1650<br />

To fit the units<br />

CLL370<br />

CLL760<br />

CLL1050<br />

CLL1650/1650T<br />

Partial fl ush unit mounting<br />

Frame for partial mounting<br />

Reference T V V* W* X Y<br />

MECL370 320 635 646 346 80 90<br />

MECL760 370 815 826 396 95 100<br />

MECL1050 420 915 926 446 95 100<br />

MECL1650 420 1015 1026 446 120 100<br />

* Maximum dimensions of the frame<br />

T<br />

* V<br />

U<br />

26<br />

X<br />

Y<br />

*20<br />

* W<br />

26<br />

X<br />

Y<br />

6/54


CLL / CLT<br />

Accessories<br />

Intermediate frame for top mounting<br />

c For mounting the CLT760 cooling unit on the top of enclosures<br />

width = 600 mm<br />

depth = 400 mm<br />

c Colour grey RAL-7032.<br />

c Dimensions: 60 595 360 mm.<br />

Reference<br />

MMI64<br />

Characteristics<br />

To fit enclosures 600 mm<br />

wide and 400 mm deep.<br />

26<br />

360<br />

Replacement filter<br />

Reference<br />

Characteristics<br />

FCLIC<br />

To fit to all cooling units<br />

6/55


6/56<br />

Cooling units<br />

CLLMP/CLTMP electronic control


c Available in two<br />

versions: top- and<br />

side-mounting.<br />

c Power from 1100 W to<br />

1800 W allowing you to<br />

install the equipment<br />

that best suits your<br />

needs in each case.<br />

Comfortable and<br />

easy to assemble and<br />

disassemble.<br />

The side-mounted air<br />

conditioners feature<br />

an exclusive quickinstallation<br />

system:<br />

c Two retractable<br />

handles facilitate the<br />

installation of the air<br />

conditioner by a single<br />

operator.<br />

c They have an exclusive<br />

quick-fixing system<br />

without screws that<br />

facilitates mounting<br />

on the enclosure and<br />

guarantees the IP54<br />

degree of protection.<br />

c The electrical<br />

connection is carried<br />

out with removable<br />

connectors supplied<br />

with the cooling unit.<br />

One single machining<br />

size.<br />

The machining sizes are<br />

the same for all sidemounted<br />

cooling units.<br />

c Fast access to<br />

the inside makes<br />

unit cleaning and<br />

maintenance easy.<br />

c Its design renders<br />

filters unnecessary<br />

in most cases. It is<br />

possible to install a<br />

filter in the exterior<br />

circuit for particularly<br />

polluted atmospheres.<br />

c The design of the<br />

aluminium slats of<br />

the condenser makes<br />

maintenance easier<br />

and less frequent.<br />

ENVIRONMENTALLY<br />

friendly<br />

The inside and outside<br />

air circuits are perfectly<br />

separated and maintain<br />

the enclosure’s IP54<br />

watertightness.<br />

Two fans guarantee air<br />

circulation in each of the<br />

circuits:<br />

c Recirculation fan<br />

for air inside the<br />

enclosure.<br />

The internal circuit fan<br />

is always on, thereby<br />

maintaining a uniform<br />

temperature inside<br />

the enclosure and<br />

preventing hot spots.<br />

c Fan to circulate<br />

the air outside the<br />

enclosure.<br />

The inside thermostat<br />

controls the fan and<br />

starts it up when the<br />

temperature of the air<br />

inside the enclosure<br />

is above the required<br />

temperature.<br />

Electronic regulation<br />

provides:<br />

c Precise control of the<br />

operating temperature:<br />

– Start-up of the compressor<br />

at +1 °C above the preset<br />

temperature.<br />

– Switching off of the<br />

compressor at -5 °C below<br />

the preset temperature.<br />

c Door contact<br />

management.<br />

c Manual alarm reset.<br />

c Manual rearming of the<br />

alarms.<br />

c Control of the idle and<br />

operation times of the<br />

compressor.<br />

All models, side-and<br />

top-mounting, have an<br />

automatic evaporation<br />

system for the<br />

condensation water.<br />

Use of R134 ecological<br />

gas.<br />

Temperature adjustment<br />

range from +20 to +50 °C.<br />

6/57


CLLMP<br />

Electronically-controlled cooling units<br />

Side mounting<br />

CLLMP1400<br />

General characteristics:<br />

c Main components: high temperature compressor, two fans mounted on<br />

removable support, two exchange cassettes, ecological cooling fluid HFC<br />

R134a, electronic control and evaporation device (with anti-corrosion finish)<br />

for side and top models.<br />

c Temperature setting can be adjusted from +20 to +50 ºC (pre-adjustment<br />

and temperature recommended: 35 ºC).<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

c Electronic control by microprocessor enables:<br />

v Adjustment of set temperature.<br />

v Door contact control.<br />

v Data is stored in the memory in the event of a power cut:<br />

– Minimum compressor operating time.<br />

– Minimum compressor idle time.<br />

v Compressor switch-on at set temperature +1 ºC.<br />

v Compressor switch-off at set temperature –5 ºC.<br />

v Alarm management.<br />

v Alarm reset by “acknowledgement” (manual reset).<br />

Operating conditions:<br />

c Operating temperature: +20 to +55 ºC.<br />

c An optional filter is required in cases of installation in the following<br />

applications: intensive welding, hot metal forging, fibres and textiles, crushing,<br />

rubber processing and other difficult environments.<br />

c The air conditioner incorporates two retractable handles to facilitate transport.<br />

c The air conditioner incorporates a quick attachment device. A circular screw/<br />

cage nut assembly ensures locking of the unit from the exterior.<br />

c <strong>Electric</strong>al connection is by plug-in connectors, included with the unit.<br />

c Do not obstruct, even partially, air inlets and outlets.<br />

c The unit should be installed spaced at least 30 cm from walls and at least<br />

10 cm from floor level.<br />

Reference CLLMP1100 CLLMP1400 CLLMP1400T CLLMP1800T<br />

Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />

Cooling power (50/60 Hz) according to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

Dimensions<br />

Height Width Depth<br />

Current<br />

Start-up<br />

Nominal<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

EER energetic performance<br />

L35 - L35<br />

1100/1200 W<br />

(3755/4097 Btu/h)<br />

880/930 W<br />

(3004/3175 Btu/h)<br />

12.1/13.9 A<br />

3.2/3.7 A<br />

600/690 W<br />

690/790 W<br />

1400/1500 W<br />

(4780/5121 Btu/h)<br />

1200/1300 W<br />

(4097/4438 Btu/h)<br />

1400/1500 W<br />

(4780/5121 Btu/h)<br />

1200/1300 W<br />

(4097/4438 Btu/h)<br />

1,010 mm 400 mm 240 mm<br />

18.1/22.2 A<br />

4.8/5.8 A<br />

900/1,100 W<br />

1100/1300 W<br />

3.7/4.3 A<br />

1.2/1.4 A<br />

700/810 W<br />

810/930 W<br />

1800/1900 W<br />

(6145/6485 Btu/h)<br />

1400/1500 W<br />

(4780/5121 Btu/h)<br />

5.3/6.3 A<br />

1.8/2.1 A<br />

1000/1200 W<br />

1200/1300 W<br />

1.8/1.7 1.6/1.4 2.0/1.9 1.8/1.7<br />

Temperature regulator Microprocessor (with display and diagnosis)<br />

Temperature setting range 20 - 50 °C<br />

Max. external ambient temperature 55 °C<br />

Noise level 62 dB (A) 64 dB (A) 66 dB (A) 69 dB (A)<br />

Airflow<br />

Internal circuit<br />

External circuit<br />

Alarm type free power<br />

575/600 m 3 /h<br />

860/900 m 3 /h<br />

860/900 m 3 /h<br />

860/900 m 3 /h<br />

860/900 m 3 /h<br />

860/900 m 3 /h<br />

885/900 m 3 /h<br />

1050/1160 m 3 /h<br />

Inverter contact<br />

Weight 45 kg 46 kg 47 kg 50 kg<br />

Cooling gas R134a (0.85 kg) R134a (0.85 kg) R134a (0.85 kg) R134a (0.85 kg)<br />

Internal IP circuit 54 54 54 54<br />

External IP circuit 34 34 34 34<br />

External circuit filter Optional<br />

Mounting model Side<br />

Recommended protection (fuse curve) T6 A T8 A T2 A T3 A<br />

6/58


CLLMP<br />

Electronically-controlled cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

Drilling template for side mounting<br />

Drilling template for side mounting<br />

FIG. 2<br />

Curves<br />

CLLMP1100 50 Hz CLLMP1100 60 Hz CLLMP1400T 50 Hz<br />

2000<br />

1800<br />

2000<br />

1800<br />

2200<br />

2000<br />

Ti [ ºC ]<br />

Ti [ ºC ]<br />

1600<br />

1400<br />

50<br />

45<br />

1600<br />

1400<br />

50<br />

45<br />

40<br />

1800<br />

1600<br />

1200<br />

40<br />

35<br />

1200<br />

35<br />

30<br />

1400<br />

1000<br />

800<br />

30<br />

25<br />

20<br />

1000<br />

800<br />

25<br />

20<br />

1200<br />

1000<br />

Pf [ W ]<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

600<br />

400<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

400<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

800<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

CLLMP1400T 60 Hz<br />

Pf [ W ]<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

CLLMP1400 50 Hz<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

CLLMP1400 60 Hz<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

800<br />

800<br />

800<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

CLLMP1800T 50 Hz<br />

3000<br />

2800<br />

2600<br />

2400<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

800<br />

Pf [ W ]<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

CLLMP1800T 60 Hz<br />

3000<br />

Ti [ ºC ]<br />

2800<br />

2600<br />

2400<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

1200<br />

1000<br />

800<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

6/59


CLTMP<br />

Electronically-controlled cooling units<br />

Top mounting<br />

CLTMP1400<br />

General characteristics:<br />

c Main components: high temperature compressor, two fans mounted on<br />

removable support, two exchange cassettes, ecological cooling fluid HFC<br />

R134a, electronic control and evaporation device (with anti-corrosion finish)<br />

for side and top models.<br />

c Temperature setting can be adjusted from +20 to +50 ºC (pre-adjustment<br />

and temperature recommended: 35 ºC).<br />

c Internal and external air circuits are totally independent and IP54 sealing is<br />

assured between external ambient air and air within the enclosure.<br />

c The internal circuit fan which runs continuously, prevents formation of hot<br />

spots and improves thermal dissipation of the enclosure.<br />

c Electronic control by microprocessor enables:<br />

v Adjustment of set temperature.<br />

v Door contact control.<br />

v Data is stored in the memory in the event of a power cut:<br />

– Minimum compressor operating time.<br />

– Minimum compressor idle time.<br />

v Compressor switch-on at set temperature +1 ºC.<br />

v Compressor switch-off at set temperature –5 ºC.<br />

v Alarm management.<br />

v Alarm reset by “acknowledgement” (manual reset).<br />

Operating conditions:<br />

c Operating temperature: +20 to +55 ºC.<br />

c An optional filter is required in cases of installation in the following<br />

applications: intensive welding, hot metal forging, fibres and textiles,<br />

crushing, rubber processing and other difficult environments.<br />

c The air conditioner incorporates two retractable handles to facilitate<br />

transport.<br />

c The air conditioner incorporates a quick attachment device. A circular<br />

screw/cage nut assembly ensures locking of the unit from the exterior.<br />

c <strong>Electric</strong>al connection is by plug-in connectors, included with the unit.<br />

c Do not obstruct, even partially, air inlets and outlets.<br />

c The unit should be installed spaced at least 30 cm from walls and at least<br />

10 cm from floor level.<br />

Reference CLTMP1400 CLTMP1800T<br />

Voltage 230 V 50/60 Hz 3 400 V 50 Hz / 3 440 V 60 Hz<br />

Cooling power (50/60 Hz) according to EN 14511<br />

L35 - L35<br />

L35 - L50<br />

1400/1500 W (4780/5121 Btu/h)<br />

1200/1300 W (4097/4438 Btu/h)<br />

1800/1900 W (6145/6485 Btu/h)<br />

1400/1500 W (4780/5121 Btu/h)<br />

Dimensions<br />

Height Width Depth<br />

415 mm 750 mm 412 mm<br />

Intensity<br />

Starting current<br />

Rated current<br />

<strong>Electric</strong>al power absorbed<br />

L35 - L35<br />

L35 - L50<br />

18.1/22.2 A<br />

4.8/5.8 A<br />

900/1100 W<br />

1100/1300 W<br />

5.3/6.3 A<br />

1.8/2.1 A<br />

1000/1200 W<br />

1200/1300 W<br />

EER energetic performance<br />

L35 - L35 1.6/1.4 1.8/1.7<br />

Temperature regulator<br />

Microprocessor (with display and diagnosis)<br />

Temperature setting range 20 - 50 °C<br />

Max. external ambient temperature 55 °C<br />

Noise level 64 dB (A) 69 dB (A)<br />

Airflow<br />

Internal circuit<br />

External circuit<br />

Alarm type free power<br />

860/900 m 3 /h<br />

860/900 m 3 /h<br />

885/900 m 3 /h<br />

1050/1160 m 3 /h<br />

Inverter contact<br />

Weight 48 kg 50 kg<br />

Cooling gas R134a (0.95 kg) R134a (0.95 kg)<br />

Internal IP circuit 54<br />

External IP circuit 34<br />

External circuit filter Optional<br />

Mounting model<br />

Top<br />

Recommended protection (fuse curve) T8 A T3 A<br />

6/60


CLTMP<br />

Electronically-controlled cooling units<br />

Dimensions (mm)<br />

FIG. 1<br />

Drilling template for top mounting<br />

Drilling template for top mounting<br />

FIG. 2<br />

Curves<br />

CLTMP1400 60 Hz<br />

CLTMP1400 50 Hz<br />

Pf [ W ]<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

2200<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

800<br />

800<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

600<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

CLTMP1800T 50 Hz<br />

3000<br />

2800<br />

2600<br />

2400<br />

2200<br />

Pf [ W ]<br />

2000<br />

1800<br />

1600<br />

1400<br />

1200<br />

1000<br />

800<br />

Ti [ ºC ]<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 50 Hz<br />

CLTMP1800T 60 Hz<br />

3000<br />

Ti [ ºC ]<br />

2800<br />

2600<br />

50<br />

2400<br />

45<br />

2200<br />

40<br />

2000<br />

35<br />

1800<br />

30<br />

1600<br />

25<br />

1400<br />

20<br />

1200<br />

1000<br />

800<br />

20 25 30 35 40 45 50 55<br />

Te [ ºC ] f = 60 Hz<br />

Te: ambient air temperature (°C)<br />

Ti: temperature inside enclosure (°C)<br />

Pf: cooling power (W)<br />

6/61


CLLMP / CLTPM<br />

Accessories<br />

Filter unit<br />

c For installation in the outside circuit of the side cooling units.<br />

Reference CLLMP...<br />

c Reference: CFCLL.<br />

CFCLL<br />

c Replacement filter.<br />

Reference: CFLL.<br />

CFLL<br />

6/62


CLLMP / CLTPM<br />

Accessories<br />

Side panels prepared for air conditioners<br />

c Set of 2 side panels for fixing inside or outside the enclosure. One<br />

pre-knocked panel for the direct fi xing of the CLLMP side-mounted<br />

cooling units…<br />

Reference Height Depth<br />

2PLOL186CLM 1,800 600<br />

2PLOL188CLM 1,800 800<br />

2PLOL206CLM 2,000 600<br />

2PLOL208CLM 2,000 800<br />

6/63


6/64<br />

Insulated resistance heaters<br />

Heating safely


c Available in two versions: by convection and with fan.<br />

c Alternating or direct current.<br />

c Powers from 10 W to 550 W.<br />

It has a plastic covering<br />

to prevent direct contact<br />

with the aluminium<br />

radiator.<br />

c The resistors equipped<br />

with fan guarantee<br />

air recirculation and<br />

an even temperature<br />

inside the enclosure.<br />

c High-flow, silent fans.<br />

c Small size.<br />

c Fast electrical connection by means of snap-on<br />

terminals.<br />

c Fast and simple fixing to the 35 mm DIN rail.<br />

c Maintenance-free.<br />

c Protected from direct contact with the aluminium<br />

radiator.<br />

c <strong>Electric</strong>al connection protected from direct contact<br />

by means of a plastic terminal block cover.<br />

c Equipped with a PTC-type heating element.<br />

c Surface temperature below +70 ºC.<br />

c The configuration of the aluminium section produces<br />

a chimney effect. High natural convection.<br />

c Low energy consumption thanks to the autoadjustment<br />

of the PTC resistor.<br />

Certifications<br />

c EC Marking.<br />

c Compliant with UL and VDE across the range.<br />

6/65


RESISTANCE<br />

HEATERS<br />

Selection guide<br />

INSULATED RESISTANCE HEATERS<br />

Reference Power W Voltage V<br />

Terminal block<br />

Type of connection<br />

Cable<br />

RC10/12-36AI 10 12-36 DC X<br />

RC10AI 10 110-250 AC X<br />

RC20/12-36AI 21 12-36 DC X<br />

RC20AI 21 110-250 AC X<br />

RC50/12-36AI 55 12-36 DC X<br />

RC50AI 55 110-250 AC X<br />

RC50/270-420AI 55 270-420 AC X<br />

RC100/12-36AI 102 12-36 DC X<br />

RC100AI 102 110-250 AC X<br />

RC100/270-420AI 102 270-420 AC X<br />

RC150/12-36AI 147 12-36 DC X<br />

RC150AI 147 110-250 AC X<br />

6/66


RESISTANCE<br />

HEATERS<br />

Selection guide<br />

INSULATED RESISTANCE HEATERS WITH FAN<br />

Reference Power W Voltage V<br />

Type of connection<br />

Terminal block<br />

Cable<br />

RCV170 170 230 AC X<br />

THERMOFANS<br />

Reference Power W Voltage V<br />

Typo of connection<br />

Terminal block<br />

Cable<br />

TMV350-550/120 400/550 120 AC X<br />

TMV350/550 400/550 230 AC X<br />

TMV350 350 230 AC X<br />

6/67


RC ... AI<br />

Resistance heaters<br />

Insulated<br />

RC10AI - RC20AI<br />

10 W and 20 W insulated resistance<br />

heaters<br />

General characteristics:<br />

c Compact resistance heater which prevents the condensation of water and<br />

ice inside the enclosures.<br />

c Innovative design for better natural convection and high thermal<br />

performance.<br />

c Compact, smaller resistance heater.<br />

c Extruded aluminium body.<br />

c Features an insulated UL94 V0 plastic cover in light grey to avoid direct<br />

contact with the heating elements (PTC) and the aluminium radiator.<br />

c Surface temperature limited to less than 70 °C.<br />

c Equipped with a connection cable.<br />

c Double safety insulated (plastic).<br />

c PTC technology range.<br />

c Quick clip-fixing onto the 35 mm DIN rail.<br />

c Compliant with UL and VDE EC Marking.<br />

Usage conditions:<br />

c The resistance heaters should be used together with a temperature<br />

regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />

installed).<br />

c The enclosure must be sealed in order to prevent the penetration of<br />

external air.<br />

c The electrical protection devices must be installed between the supply<br />

source and the resistance heaters themselves.<br />

Characteristics<br />

Reference<br />

RC10AI RC10/12-36AI RC20AI RC20/12-36AI<br />

Heating power at 0 °C 10 W 21 W<br />

Power supply voltage 110-250 V AC/DC 12-36 V AC/DC 110-250 V AC/DC 12-36 V AC/DC<br />

Heating element<br />

PTC<br />

Surface temperature<br />


RC ... AI<br />

Resistance heaters<br />

Dimensions (mm)<br />

FIG. 1<br />

Connections<br />

Reference<br />

L (mm)<br />

RC10AI 98<br />

RC20AI 98<br />

75<br />

Clip clip de on<br />

35 fijación mm<br />

DIN para rail carril<br />

DIN de<br />

35 mm<br />

98<br />

38<br />

1 2<br />

1 2<br />

6/69


RC ... AI<br />

Resistance heaters<br />

RC50AI - RC100AI - RC150AI<br />

55 W - 100 W - 147 W insulated<br />

resistance heaters<br />

General characteristics:<br />

c Compact resistance heater which prevents the condensation of water and<br />

ice inside the enclosures.<br />

c Innovative design for better natural convection and high thermal<br />

performance.<br />

c Compact, smaller resistance heater.<br />

c Extruded aluminium body.<br />

c Features an insulated UL94 V0 plastic cover in light grey to avoid direct<br />

contact with the heating elements (PTC) and the aluminium radiator.<br />

c Surface temperature limited to less than 70 °C.<br />

c Fitted with 2.5 mm 2 quick-connection terminals.<br />

c Double safety insulated (plastic).<br />

c PTC technology range.<br />

c Quick clip-fixing onto the 35 mm DIN rail (EN 50022).<br />

c Certifications compliant with UL and VDE and EC Marking.<br />

Usage conditions:<br />

c The resistance heaters should be used together with a temperature<br />

regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />

installed).<br />

c The enclosure must be sealed in order to prevent the penetration of<br />

external air.<br />

c The electrical protection devices must be installed between the supply<br />

source and the resistance heaters themselves.<br />

Characteristics<br />

Reference<br />

RC50AI<br />

RC50/12-36AI<br />

RC50/<br />

270-420AI<br />

RC100AI<br />

RC100/<br />

12-36AI<br />

RC100/<br />

270-420AI<br />

RC 150AI<br />

Heating power at 0 °C 55 W 102 W 147 W<br />

Power supply voltage<br />

110-250 V<br />

AC/DC<br />

12-36 V<br />

AC/DC<br />

270-420 V<br />

AC/DC<br />

110-250 V<br />

AC/DC<br />

12-36 V<br />

AC/DC<br />

Heating element<br />

PTC<br />

Surface temperature<br />


RC ... AI<br />

Resistance heaters<br />

Dimensions (mm)<br />

FIG. 1<br />

Reference<br />

L (mm)<br />

RC50AI 110<br />

RC50/12-36AI 110<br />

RC50/270-420AI 110<br />

RC100AI 110<br />

RC100/12-36AI 110<br />

RC100/270-420AI 150<br />

RC150AI 150<br />

RC150/12-36AI 150<br />

FIG. 2<br />

Diagram<br />

Heating power diagram - Ambient temperature<br />

Heating power (W)<br />

RC150AI<br />

RC100AI<br />

RC50AI<br />

Ambient temperature (°C)<br />

6/71


RCV<br />

Resistance heaters with fan<br />

RCV170<br />

General characteristics:<br />

c Compact resistance heater which prevents the condensation of water and<br />

ice inside the enclosures.<br />

c Includes an axial fan to ensure uniform heating inside the enclosure.<br />

c Compact, smaller resistance heater.<br />

c Extruded aluminium body.<br />

c Features an insulated UL94 V0 plastic cover in black to avoid direct contact<br />

with the heating elements (PTC) and the aluminium radiator.<br />

c Surface temperature limited to less than 50 °C.<br />

c Fitted with 2.5 mm 2 quick-connection terminals.<br />

c Double safety insulated (plastic).<br />

c PTC technology range.<br />

c Quick clip-fixing onto the 35 mm DIN rail (EN 50022).<br />

c Certifications compliant with UL and VDE and EC Marking.<br />

Usage conditions:<br />

c The resistance heaters should be used together with a temperature<br />

regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />

installed).<br />

c The enclosure should be sealed in order to prevent the penetration of<br />

external air.<br />

c An electrical protection device should be installed on the supply side of the<br />

unit.<br />

Characteristics<br />

Reference<br />

RCV170<br />

Heating power at 0 °C<br />

177 W<br />

Power supply voltage<br />

230 V AC 50-60 Hz<br />

Heating element<br />

PTC<br />

Surface temperature<br />

Max. of 50 ºC in the enclosure, 100 ºC in the upper protection grill (for an external temperature of 20 °C/68 °F)<br />

Service life 40000 h to 40 °C<br />

Airflow 13.8 m 3 /h<br />

<strong>Electric</strong>al connection 2 poles of 2.5 mm 2<br />

Fixing Clip for the 35 mm DIN rail (EN 50022)<br />

Cover<br />

Plastic UL94 V0<br />

Operating position<br />

Vertical<br />

Operating temperature<br />

–40 to +70 °C (–10 to +158 °F)<br />

IP Protection/Class<br />

IP20II (double insulation)<br />

Certifications<br />

VDE and UL in process<br />

6/72


RCV<br />

Resistance heaters with fan<br />

Dimensions (mm)<br />

FIG. 1<br />

RCV170<br />

6/73


6/74<br />

Standard heating resistors<br />

Traditional convection


The Himel heating<br />

resistors for electrical<br />

or electronic enclosures<br />

are equipped with PTCtype<br />

heating elements<br />

(Positive Temperature<br />

Coefficient). The use of<br />

these semi-conductors<br />

as heating elements<br />

means that:<br />

c The aluminium surface<br />

temperature of the<br />

diffuser stabilises at<br />

+75 ºC (for an ambient<br />

temperature of –5 ºC).<br />

c <strong>Electric</strong>al energy<br />

consumption is<br />

reduced.<br />

The design of the profile<br />

of the Himel heating<br />

resistors produces a<br />

“chimney” effect. Thus,<br />

a uniform temperature<br />

is achieved inside the<br />

enclosure.<br />

The resistors are secured<br />

by means of fast-fixing<br />

clips on the 35 mm DIN<br />

rails.<br />

The 10 and 20 W resistors<br />

are equipped with a 2 <br />

0.75 300 mm electrical<br />

connection cable.<br />

Higher power resistors<br />

are equipped with fastconnection<br />

terminals.<br />

Their broad range of<br />

powers, from 10 to<br />

400 W, means that any<br />

solution is possible.<br />

Models from 250 and<br />

400 W with a built-in fan.<br />

6/75


RESISTANCE<br />

HEATERS<br />

Selection guide<br />

RESISTANCE HEATERS<br />

Reference Power (W) Voltage (V)<br />

Terminal block<br />

Connection type<br />

Cable<br />

RC10/12-36 10 12-36 DC X<br />

RC10 10 110-250 AC X<br />

RC20/12-36 20 12-36 DC X<br />

RC20 20 110-250 AC X<br />

RC20/270-420 20 270-420 AC X<br />

RC55/12-36 55 12-36 DC X<br />

RC55 55 110-250 AC X<br />

RC55/270-420 55 270-420 AC X<br />

RC100/12-36 90 12-36 DC X<br />

RC100 90 110-250 AC X<br />

RC100/270-420 90 270-420 AC X<br />

RC150/12-36 150 12-36 DC X<br />

RC150 150 110-250 AC X<br />

RC150/270-420 150 270-420 AC X<br />

6/76


RESISTANCE<br />

HEATERS<br />

Selection guide<br />

RESISTANCE HEATERS WITH FAN<br />

References Power (W) Voltage (V)<br />

Terminal block<br />

Connection type<br />

Cable<br />

RCV250 250 230 AC X<br />

RCV400 400 230 AC X<br />

RCV200P/115 200 115 AC X<br />

RCV200P 200 230 AC X<br />

6/77


RC / RCV / TMV<br />

Resistance heaters<br />

Resistance heaters<br />

c Range of resistance heaters from 10 to 400 W ensuring the proper heating of the<br />

enclosure to prevent condensation.<br />

General characteristics:<br />

c Extruded aluminium body.<br />

c Surface temperature limited to less than 75 °C with an ambient temperature<br />

of –5 °C.<br />

c 500 mm-long power supply cable with silicone insulation (except for the<br />

RCV400, R55, 90 and 150 models, which are equipped with a connection<br />

terminal block).<br />

Usage conditions:<br />

c The resistance heaters should be used together with a temperature<br />

regulator (thermostat TS140 or TS170, hygrostat HS300 also can be<br />

installed).<br />

c The enclosure should be sealed in order to prevent the penetration of external<br />

air.<br />

c The electrical protection devices must be installed between the supply<br />

source and the resistance heaters themselves.<br />

Reference Power (W) Voltage (V) Start-up current (A) Nominal current (A) Class Dimensions (mm)<br />

RC10/12-36 10 12-36 DC II 25 50 50<br />

RC10 10 110-250 AC 0.80 0.60 II 25 50 50<br />

RC20/12-36 20 12-36 DC II 25 50 75<br />

RC20 20 110-250 AC 1 1.05 II 25 50 75<br />

RC20/270-420 20 270-420 AC II 25 50 75<br />

RC55/12-36 55 12-36 DC II 70 50 140<br />

RC55 55 110-250 AC 1.50 0.24 II 70 50 140<br />

RC55/270-420 55 270-420 AC II 70 50 140<br />

RC90/12-36 90 12-36 DC II 70 50 140<br />

RC90 90 110-250 AC 2.40 0.40 II 70 50 140<br />

RC90/270-420 90 270-420 AC II 70 50 140<br />

RC150/12-36 150 12-36 DC II 70 50 220<br />

RC150 150 110-250 AC 4.50 0.65 II 70 50 220<br />

RC150/270-420 150 270-420 AC II 70 50 220<br />

RC250 250 220-230 1.10 1.10 II 70 50 220<br />

RC400 400 220-230 1.70 1.70 II 70 50 220<br />

6/78


RC / RCV / TMV<br />

Resistance heaters<br />

Resistance heaters with fan<br />

c The fan maintains an even temperature inside the electric switchboard.<br />

Reference Power (W) Voltage (V)<br />

Start-up<br />

current (A)<br />

Nominal<br />

current (A)<br />

Class<br />

Dimensions (mm)<br />

RCV250 250 230 CA 1.20 1.20 I 180 85 95<br />

RCV400 400 230 CA 1.80 1.80 I 80 80 248<br />

Plain resistance heater with fan<br />

Reference Power (W) Voltage (V)<br />

Start-up<br />

current (A)<br />

Nominal<br />

current (A)<br />

Class<br />

Dimensions (mm)<br />

RCV200P 200 230 CA - 0.90 I 120 120 47<br />

RCV200P/115 200 115 CA - 1.80 I 120 120 47<br />

Thermofans<br />

c This device combines a the heating power of a resistor with the<br />

operation of an axial fan, offering optimal heat distribution inside the<br />

enclosure.<br />

c Fixing onto a DIN rail.<br />

c Adjustable temperature from 10 to 50 °C for TMV350, and from 0 to 60 °C<br />

for TMV350/550.<br />

TMV350<br />

c Power-on indicator lamp.<br />

Reference Power ( W) Voltage (V) Dimensions (mm)<br />

TMV350 350 230 CA 200 45 180<br />

TMV350/550 400/550 230 CA 180 85 95<br />

TMV350-550/120 400/550 120 CA 180 85 95<br />

TMV350/550<br />

6/79


Selection guide<br />

Control devices<br />

Temperature under control<br />

Compact thermostats (adjustable)<br />

NO (blue button): with normally open contact, when the temperature increases, the<br />

contact closes, activating the fan to extract the heat.<br />

NC (red button): with normally closed contact, when the temperature falls below<br />

the preset value, the contact closes, activating the resistance heater to prevent<br />

condensation.<br />

c Broad range of temperature control.<br />

c Small size.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

c Easy access terminals.<br />

c High-power connection.<br />

24 V DC electronic thermostat (adjustable)<br />

It can control 24 V direct-current electrical equipment by means of a potential-free<br />

inverter contact. Resistors, fan, etc. may be connected.<br />

They have a PTC temperature probe for more precise control and low hysteresis.<br />

c High DC switching capacity.<br />

c Low hysteresis (greater temperature precision).<br />

c Switching by means of an inverter contact.<br />

c Simple fixing by clip onto the 35 mm DIN/EN rail.<br />

Dual thermostat (adjustable)<br />

To control two units independently and simultaneously: a resistance heater and a fan.<br />

NC (red button): normally closed contact (NC) for resistance heater control.<br />

NO (blue button): normally open contact (NO) for fan control.<br />

c Double thermostats in the same housing, with separate adjustment and operation.<br />

c Easy access terminals.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

NO/NC Thermostat (adjustable)<br />

Its NO/NC inverter contact controls a resistance heater or a fan.<br />

c Switching by means of two NO/NC contacts.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

c Easy access terminals.<br />

c High-power connection.<br />

6/80


Hygrometer (adjustable)<br />

Combination of thermostat and hygrostat in the same unit to control relative<br />

humidity.<br />

The resistance heaters or fans are switched on when the two limit values are<br />

exceeded.<br />

c Adjustable temperature and relative humidity of the air.<br />

c High switching capacity.<br />

c Visual operation indication.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

c Easy access terminals.<br />

Compact fixed thermostats<br />

c Preset factory temperature:<br />

v Red button: 5, 10 and 15 °C.<br />

v Blue button: 25, 30 and 35 °C.<br />

c Small size.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

c Easy access terminals.<br />

c High-power connection.<br />

Fixed dual thermostat<br />

c To control two units independently and simultaneously:<br />

v NO/NC: fan and resistor.<br />

v NO/NO: fan and alarm.<br />

v NC /NC: resistance and alarm.<br />

c Preset factory values.<br />

c Double thermostats in the same housing, with separate operation.<br />

c Easy access terminals.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

Fixed hygrostat<br />

c Factory-adjusted relative humidity: 60% RH.<br />

c Switching by means of an NO contact.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

c Easy access terminals.<br />

c High-power connection.<br />

Hygrostat (adjustable)<br />

It is used to adjust the relative humidity in the enclosure by controlling resistance<br />

heaters or fans.<br />

The hygrostat prevents condensation and the corrosion of components.<br />

c Adjustable relative humidity.<br />

c Switching by means of an inverter contact.<br />

c Simple fixing by clip onto the 35 mm DIN rail.<br />

c Easy access terminals.<br />

c High-power connection.<br />

6/81


CONTROL<br />

DEVICES<br />

Selection guide<br />

THERMOSTATS<br />

References<br />

Power supply<br />

voltage<br />

(V)<br />

Control<br />

Contact<br />

type<br />

Application<br />

Control<br />

element<br />

Switching<br />

power<br />

(ohmic load)<br />

TS140<br />

TS140F °F NC<br />

TS141 °C NO<br />

-<br />

TS141F °F NO<br />

°C NC Resistance<br />

heaters<br />

Ventilation<br />

systems<br />

Bimetal<br />

30 W DC<br />

250 V AC 10 A<br />

120 V AC 15 A<br />

TS170 °C Switch<br />

Resistance<br />

heaters or<br />

ventilation<br />

systems<br />

250 V AC 10 A<br />

DOUBLE THERMOSTAT<br />

References<br />

Power supply<br />

voltage<br />

(V)<br />

Control<br />

Contact<br />

type<br />

Application<br />

Control<br />

element<br />

Switching<br />

power<br />

(ohmic load)<br />

TDS1401 - °C NC+NO<br />

Resistance<br />

heaters and<br />

ventilation<br />

systems<br />

Bimetal<br />

250 V AC 10 A<br />

120 V AC 15 A<br />

ELECTRONIC THERMOSTAT<br />

References<br />

Power supply<br />

voltage<br />

(V)<br />

Control<br />

Contact<br />

type<br />

Application<br />

Control<br />

element<br />

Switching<br />

power<br />

(ohmic load)<br />

TSE200 24 DC °C 2 NO<br />

Resistance<br />

heaters and<br />

ventilation<br />

systems<br />

Electronic<br />

NO or NC:<br />

24 V DC<br />

2 8 A<br />

FIXED THERMOSTAT<br />

References<br />

Fixed<br />

adjustment<br />

Contact type<br />

Application<br />

Switching power<br />

(ohmic load)<br />

TS140F5 5 °C/41 °F NC<br />

TS140F10 10 °C/50 °F NC<br />

TS140F15 15 °C/59 °F NC<br />

Resistance heaters<br />

250 V AC 10 A<br />

120 V AC 15 A<br />

DC 30 W<br />

TS141F25 25 °C/77 °F NO<br />

TS141F30 30 °C/86 °F NO<br />

TS141F35 35 °C/95 °F NO<br />

Ventilation systems<br />

250 V AC 10 A<br />

120 V AC 15 A<br />

DC 30 W<br />

6/82


CONTROL<br />

DEVICES<br />

Selection guide<br />

FIXED DUAL THERMOSTAT<br />

References Fixed adjustment Contact type<br />

Switching<br />

power<br />

(ohmic load)<br />

TSD1401F10/35<br />

TSD1401F35/45<br />

TSD1401F5/15<br />

10 °C/50 °F<br />

35 °C/95 °F<br />

35 °C/95 °F<br />

45 °C/113 °F<br />

5 °C/41 °F<br />

15 °C/59 °F<br />

NC<br />

NO<br />

NO<br />

NO<br />

NC<br />

NC<br />

250 V AC 10 A<br />

120 V AC 15 A<br />

DC 30 W<br />

HYGROMETER<br />

References<br />

Power supply<br />

voltage<br />

(V)<br />

Control<br />

Contact<br />

type<br />

Application<br />

Control<br />

element<br />

Switching<br />

power<br />

(ohmic load)<br />

THS3000 230 CA % RH, °C Switch<br />

Resistance<br />

heaters and<br />

ventilation<br />

systems<br />

Bimetal<br />

240 V AC 8 A<br />

120 V AC 8 A<br />

HYGROSTAT<br />

References<br />

Power supply<br />

voltage<br />

(V)<br />

Control<br />

Contact<br />

type<br />

Application<br />

Control<br />

element<br />

Switching<br />

power (ohmic<br />

load)<br />

HS300 - % RH Switch<br />

Resistance<br />

heaters and<br />

ventilation<br />

systems<br />

Bimetal<br />

230 V AC 5 A<br />

FIXED HYGROSTAT<br />

References Fixed adjustment Contact type<br />

HS300F60 60% RH Switch<br />

Max. control<br />

current<br />

250 V AC 5 A<br />

DC 20 W<br />

6/83


TS<br />

Control devices<br />

Thermostat TS140<br />

c Thermostat (normally closed contact (NC) for the control of resistance<br />

heaters.<br />

c Thermostat use increases service life of resistors, switching them only when<br />

required by the temperature.<br />

c Fixing onto a DIN rail.<br />

c IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Adjustable temperature from 0 to 60 °C.<br />

c Connection: 2 x 2.5 mm 2 terminals.<br />

Reference Dimensions (mm) Max. control current<br />

TS140 60 33 43 250 V 10 A<br />

TS140F 60 33 43 250 V 10 A<br />

FIG. 1<br />

Technical specifications<br />

carga load<br />

2<br />

V<br />

υ<br />

Sensor element<br />

Contact type<br />

Contact resistance<br />

Service life<br />

Bimetal<br />

Normally closed (NC), snap action contact<br />

< 10 m<br />

> 100000 cycles<br />

L<br />

N<br />

1<br />

Load Carga = resistance = resistencia<br />

Max. switching capacity<br />

250 V AC 10 A (ohmic load)<br />

120 V AC 15 A (ohmic load)<br />

250/120 V AC 2 A<br />

(inductive load cos = 0.6)<br />

DC 30 W<br />

Connection<br />

Terminals with two 2.5 mm poles<br />

Mounting Clip for the 35 mm DIN rail , EN 50022<br />

Cover<br />

V0 thermoplastic UL94, light grey<br />

Dimensions<br />

60 33 43 mm<br />

Weight<br />

40 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

–20 to +80 °C (–4 to +176 °F)<br />

Degree of protection<br />

IP20<br />

Hysteresis 7 °K<br />

Adjustable temperature From 0 to 60 °C<br />

6/84


TS<br />

Control devices<br />

Thermostat TS141<br />

c Thermostat (normally open – NO contact) for control of fans.<br />

c This thermostat allows the regulation of temperature in the enclosure,<br />

starting the fan only in case fresh air is required. As a result, service life of<br />

the fan is increased and its filter stays cleaner.<br />

c DIN rail fixing.<br />

c Degree of protection IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Adjustable temperature from 0 to 60 ºC.<br />

c Connection: 2 2.5 mm 2 terminals.<br />

Reference Dimensions (mm) Max. control current<br />

TS141 60 33 43 250 V 10 A<br />

TS141F 60 33 43 250 V 10 A<br />

FIG. 1<br />

Technical specifications<br />

carga load<br />

2<br />

Sensor element<br />

Contact type<br />

Contact resistance<br />

Bimetal<br />

Normally open (NO), snap action contact<br />

< 10 m<br />

V<br />

υ<br />

Service life<br />

> 100000 cycles<br />

L<br />

N<br />

1<br />

Load Carga = fan = ventilador<br />

250 V AC 10 A (ohmic load)<br />

Max. switching capacity<br />

120 V AC 15 A (ohmic load)<br />

250/120 V AC 2 A (inductive load cos = 0.6)<br />

DC 30 W<br />

Connection<br />

Terminals with two 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

60 33 43 mm<br />

Weight<br />

40 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

–20 to +80 °C (–4 to +176 °F)<br />

Degree of protection<br />

IP20<br />

Hysteresis 7 °K<br />

Adjustable temperature From 0 to 60 °C<br />

6/85


TS<br />

Control devices<br />

Thermostat TS170<br />

c Thermostat (contact switch) to control the fan or resistance heaters.<br />

c With this device, the internal temperature of the panel may be regulated by<br />

switching on a resistor or a fan.<br />

c Fixing on a DIN rail.<br />

c IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Adjustable temperature from 10 to 60 °C.<br />

c Connection: 4 2.5 mm 2 terminals.<br />

Reference Dimensions (mm) Max. control current<br />

TS170 67 50 44 (NA) 5 A/(NC) 10 A<br />

FIG. 1<br />

Technical specifications<br />

Load 2<br />

Load 3<br />

> <br />

Sensor element<br />

Contact type<br />

Contact resistance<br />

Service life<br />

Max. switching capacity<br />

Bimetal<br />

Switch contact, snap action<br />

< 10 m<br />

> 100000 cycles<br />

250 V AC 10 A (ohmic load)<br />

Max. opening contact<br />

250 V AC 4 A (inductive load cos = 0.6)<br />

DC 30 W<br />

L<br />

N<br />

Load (2) =resistance<br />

Load (3) = fan<br />

Connection<br />

Terminals with four 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

67 50 44 mm<br />

Weight<br />

100 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

–20 to +80 °C (–4 to +176 °F)<br />

Degree of protection<br />

IP20<br />

Hysteresis 7 °K<br />

Adjustable temperature From 5 to 60 °C<br />

6/86


TS<br />

Control devices<br />

Dual thermostat TSD1401<br />

c Dual temperature regulator.<br />

c Two thermostats in one single enclosure.<br />

c Separate control and operation.<br />

c Fixing clip for the 35 mm DIN rail.<br />

c IP20.<br />

c Dual thermostat (two thermostats in one single box). With the red button<br />

(normally closed contact- NC), the resistance heater can be regulated.<br />

A fan, signalling system or alarm can be controlled with the blue button<br />

(normally open contact- NO).<br />

This thermostat allows the simultaneous control of a resistance heater and a<br />

fan, making an independent temperature adjustment possible.<br />

Reference Dimensions (mm) Max. control current<br />

TSD1401 67 50 44<br />

250 V AC 10 A<br />

120 V AC 15 A<br />

FIG. 1<br />

N1 L1 11<br />

Technical specifications<br />

Sensor element<br />

Bimetal<br />

A<br />

12<br />

V<br />

Contact type<br />

Contact resistance<br />

Service life<br />

1 normally open (NO), 1 normally closed (NC), snap action<br />

< 10 m<br />

> 100000 cycles<br />

N2<br />

L2<br />

B<br />

23<br />

24<br />

V<br />

Max. switching capacity<br />

250 V AC 10 A (ohmic load)<br />

120 V AC 15 A (ohmic load)<br />

250/120 V AC 2 A<br />

(inductive load cos = 0,6)<br />

DC 30 W<br />

Connection<br />

Terminals with six 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

67 50 44 mm<br />

Weight<br />

90 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

–20 to +80 °C (–4 to +176 °F)<br />

Degree of protection<br />

IP20<br />

Hysteresis 7 °K<br />

Adjustable temperature From 0 to 60 °C<br />

6/87


TS<br />

Control devices<br />

Thermostat TSE200<br />

c Electronic temperature regulator.<br />

c 24 V DC supply.<br />

c Fixing by clip for 35 mm DIN rail.<br />

c IP20.<br />

c Thermostat with volt-free 2 dry contact switching relay.<br />

c Allows high number of switching operations with improved temperature<br />

accuracy (± 2 °K) thanks to its PTC probe.<br />

c The miniature communication relays installed in the thermostat are powerful<br />

(230 A) and safe.<br />

c Possibility of having a thermostat with open-contact switches or inverted<br />

switches.<br />

Reference Dimensions (mm) Max. rated current<br />

TSE200 67 50 44<br />

NA o NC:<br />

24 V DC 2 8 A<br />

FIG. 1<br />

Technical specifications<br />

+24 V<br />

_<br />

+<br />

11<br />

12<br />

21<br />

V<br />

Adjustable temperature From 0 to +60 °C<br />

Hysteresis 2 °K ± 2 °K<br />

Sensor element<br />

PTC probe<br />

Connection<br />

Terminals with six 2.5 mm 2 poles<br />

Contact type<br />

2 normally open (NO), snap action contact<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

ABS according to UL94 V0<br />

22<br />

Operating temperature<br />

0 to +60 °C (–32 to +140 °F)<br />

Degree of protection<br />

Dimensions<br />

Weight<br />

IP20<br />

67 50 44 mm<br />

80 g<br />

6/88


TS<br />

Control devices<br />

Fixed thermostats TS140F<br />

c Thermostat (normally closed contact - NC) to control resistance heaters.<br />

c DIN rail fixing.<br />

c Degree of protection IP20.<br />

c V0 self-extinguishing thermoplastic material as per UL94.<br />

c Factory-adjusted temperature.<br />

c Connection: 2 2.5 mm 2 terminals.<br />

Reference Fixed adjustment Max. control current<br />

TS140F5 5 °C/41 °F<br />

TS140F10 10 °C/50 °F<br />

TS140F15 15 °C/59 °F<br />

250 V AC 10 A 120 V AC 15 A<br />

DC 30 W<br />

FIG. 1<br />

Technical specifications<br />

Load carga1<br />

2<br />

V<br />

υ<br />

Sensor element<br />

Contact type<br />

Contact resistance<br />

Service life<br />

Bimetal<br />

Normally closed (NC), snap action contact Normally closed (NC),<br />

snap action contact<br />

< 10 m<br />

> 100000 cycles<br />

L<br />

N<br />

Load Carga = resistance = resistencia<br />

1<br />

Max. switching capacity<br />

250 V AC 10 A (ohmic load)<br />

120 V AC 15 A (ohmic load)<br />

250/120 V AC 2 A<br />

(inductive load cos = 0.6)<br />

DC 30 W<br />

Connection<br />

Terminals with two 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail 35 mm, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

60 33 43 mm<br />

Weight<br />

40 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

Degree of protection<br />

–20 to +80 °C (–4 to +176 °F)<br />

IP20<br />

6/89


TS<br />

Control devices<br />

Fixed thermostats TS141F<br />

c Thermostat (normally open - NO contact) to control fans.<br />

c Degree of protection IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Factory-adjusted temperature.<br />

c Connection: 2 2.5 mm 2 terminals.<br />

c DIN rail fixing.<br />

Reference Fixed adjustment Max. control current<br />

TS141F25 25 °C/77 °F 250 V AC 10 A<br />

TS141F30 30 °C/86 °F<br />

120 V AC 15 A<br />

TS141F35 35 °C/95 °F<br />

DC 30 W<br />

FIG. 1<br />

Technical specifications<br />

Sensor element Bimetal<br />

carga<br />

2<br />

V<br />

υ<br />

Contact type Normally open (NO), snap action contact<br />

Contact resistance<br />

< 10 m<br />

Service life<br />

> 100000 cycles<br />

L<br />

N<br />

Load<br />

Carga<br />

= fan<br />

= ventilador<br />

1<br />

250 V AC 10 A (ohmic load)<br />

Max. switching capacity<br />

120 V AC 15 A (ohmic load)<br />

250/120 V AC 2 A (inductive load cos = 0.6)<br />

DC 30 W<br />

Connection<br />

Terminals with two 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

60 33 43 mm<br />

Weight<br />

40 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

–20 to + 80 °C (–4 to +176 °F)<br />

Degree of protection<br />

IP20<br />

Hysteresis 7 °K<br />

6/90


TS<br />

Control devices<br />

Fixed dual thermostat TSD1401F<br />

c Dual temperature regulator.<br />

c Two thermostat in one enclosure with separated setting and operation.<br />

c 35 mm DIN rail clip fixing.<br />

c Factory-adjusted temperature.<br />

c This unit allows trip control of a fan and a resistance heater, independent<br />

setting and operation.<br />

Reference Contact type Fixed adjustment<br />

TSD1401F10/35<br />

TSD1401F35/45<br />

TSD1401F5/15<br />

NC:<br />

NO:<br />

NO:<br />

NO:<br />

NC:<br />

NC:<br />

10 ºC/50 ºF<br />

35 ºC/95 ºF<br />

35 ºC/95 ºF<br />

45 ºC/113 ºF<br />

5 ºC/41 ºF<br />

15 ºC/59 ºF<br />

Technical specifications<br />

FIG. 1<br />

N1 L1 11<br />

Sensor element<br />

Contact type<br />

Contact resistance<br />

Service life<br />

Bimetal<br />

Snap action<br />

< 10 m<br />

> 100000 cycles<br />

N2<br />

L2<br />

A<br />

B<br />

12<br />

23<br />

24<br />

V<br />

V<br />

Max. switching capacity<br />

250 V AC 10 A (ohmic load)<br />

120 V AC 15 A (ohmic load)<br />

250/120 V AC 2 A (inductive load<br />

cos = 0.6)<br />

DC 30 W<br />

Connection<br />

Terminals with six 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

67 50 44 mm<br />

Weight<br />

90 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

–20 to +80 °C (–4 to +176 °F)<br />

Degree of protection<br />

IP20<br />

Hysteresis 7 °K<br />

6/91


TS<br />

Control devices<br />

Hygrometer THS3000<br />

c The device independently measures the temperature and humidity within<br />

the electrical enclosure. The resistance heater is switched on when either of<br />

the limiting values set for the two parameters is exceeded: the temperature<br />

rises and the relative humidity RH falls. The hygrometer switch should be<br />

preferably be installed in the upper part of the enclosure at a minimum<br />

distance of 50 cm from the resistance heater.<br />

c DIN rail fixing.<br />

c Degree of protection IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Adjustable temperature from 0 to 60 ºC.<br />

c Adjsutable relative humidity from 50 to 90%.<br />

FIG. 1<br />

c Hysteresis: 2 °C, 3% RH.<br />

c Service life: >100000 cycles.<br />

Reference Dimensions (mm) Max. control current<br />

T°<br />

RH<br />

THS3000 67 50 43<br />

250 V AC 8 A<br />

12 V DC 8 A<br />

35 V DC 5 A<br />

1 2 3 4 5<br />

Carga Load<br />

L 230 V<br />

50 Hz<br />

N<br />

Technical specifications<br />

Power supply voltage<br />

230 V AC 50/60 Hz<br />

Switching precision<br />

Temperature 2 °K (±1 °K)<br />

Switching precision Humidity 4% (±1%)<br />

Response time<br />

Approx. 160 sec.<br />

Contact type<br />

Switch<br />

Contact resistance<br />

< 10 m<br />

Service life<br />

> 100000 cycles<br />

Max. switching capacity<br />

240 V AC 8 A (ohmic load)<br />

240/120 V AC 4 A<br />

(inductive load cos = 0.6)<br />

240 V DC 0.1 A<br />

48 V DC 0.8 A<br />

24 V DC 8 A<br />

Connection<br />

Terminals with five 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

67 50 43 mm<br />

Weight<br />

200 g<br />

Fitting position<br />

Vertical<br />

Operating temperature<br />

Degree of protection<br />

Power-on indicator<br />

–20 to +60 °C (–4 to +140 °F)<br />

IP20<br />

LED<br />

6/92


TS<br />

Control devices<br />

Hygrostat HS300<br />

c This device only measures the relative humidity inside the enclosure.<br />

c It is used to switch on the resistance heater when the humidity rises above<br />

the set value.<br />

c DIN rail fixing.<br />

c Degree of protection IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Adjustable relative humidity from 30 to 90%.<br />

Reference Dimensions (mm) Max. control current<br />

HS300 67 50 37 250 V AC 5 A<br />

FIG. 1<br />

Technical specifications<br />

Control<br />

35% to 95% RH<br />

Switching precision Humidity 4% (±3%)<br />

carga Load 1<br />

3<br />

Permissible air velocity<br />

15 m/sec<br />

carga Load 2<br />

1<br />

4<br />

V<br />

ϕ<br />

Contact type<br />

Contact resistance<br />

Service life<br />

Switch<br />

< 10 m<br />

50000 cycles<br />

Min. switching power<br />

20 V AC/DC 100 mA<br />

L<br />

N<br />

Load Carga 1 = 1 resistance = resistencia (dehumidifier) (deshumidificador)<br />

Load Carga 2 = 2 humidifier = humidificador<br />

Max. switching capacity<br />

230 V AC 5 A (ohmic load)<br />

230/120 V AC 0.2 A<br />

(inductive load cos Ø = 0.6<br />

50 V DC 1 A/75 V DC 0.5 A<br />

(inductive load L/R = 3 ms)<br />

Connection<br />

Terminals with three 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail , EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

67 50 37 mm<br />

Weight<br />

100 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

Degree of protection<br />

–20 to +60 °C (–4 to +140 °F)<br />

IP20<br />

6/93


TS<br />

Control devices<br />

Fixed hygrostat HS300F<br />

c This device only measures the relative humidity inside the enclosure.<br />

c It can be used to start up a resistance heater when this relative humidity<br />

exceeds the preset value.<br />

c DIN rail fixing.<br />

c Degree of protection IP20.<br />

c V0 self-extinguishing thermoplastic as per UL94.<br />

c Factory-adjusted relative humidity.<br />

Reference Fixed adjustment Max. control current<br />

HS300F60<br />

60% RH<br />

250 V AC 5 A<br />

DC 20 W<br />

FIG. 1<br />

Technical specifications<br />

Switching precision Humidity 4% (±3%)<br />

carga 1<br />

3<br />

Permissible air velocity<br />

15 m/sec<br />

carga 2<br />

1<br />

4<br />

V<br />

ϕ<br />

Contact type<br />

Contact resistance<br />

Service life<br />

Switch<br />

< 10 m<br />

50000 cycles<br />

L<br />

N<br />

Load 1 = resistance (dehumidifier)<br />

Carga 1 = resistencia (deshumidificador)<br />

Load<br />

Carga<br />

2<br />

2<br />

=<br />

=<br />

humidifier<br />

humidificador<br />

Min. switching power<br />

Max. switching capacity<br />

20 V AC/DC 100 mA<br />

250 V AC 5 A (ohmic load)<br />

250 V AC 0,2 A (inductive load cos = 0.6)<br />

DC 20 W<br />

Connection<br />

Terminals with three 2.5 mm 2 poles<br />

Mounting Clip for the 35 mm DIN rail, EN 50022<br />

Cover<br />

V0 UL94 thermoplastic, light grey<br />

Dimensions<br />

67 50 37 mm<br />

Weight<br />

100 g<br />

Fitting position<br />

Non-defined<br />

Operating temperature<br />

Degree of protection<br />

–20 to +60 °C (–4 to +140 °F)<br />

IP20<br />

6/94


HEAT CALCULATION<br />

Thermal management for electrical control panels<br />

Due to the miniaturisation of the components, the generalisation of electronics,<br />

and the appearance of new electronically-based power products, temperature<br />

control has become an increasingly important necessity that must be taken<br />

into account when designing electrical and/or electronic control panels, as is<br />

being done with the IP degree of protection.<br />

Reliability and the search for minimal breakdown rates are two determining<br />

factors in process industries where hourly operation costs for the installations<br />

are extremely high; the smallest breakdown can immediately result in<br />

losses totalling hundreds of thousands of pesetas. The service life of the<br />

components depends on the temperature and humidity conditions in the<br />

enclosure.<br />

The solutions to these problems are varied, and can depend on environmental<br />

conditions, the type of components in the electrical control panel<br />

and, of course, their cost!<br />

In certain cases, it is enough to oversize the enclosure or to use fans. In<br />

other cases, where ambient temperatures are higher, heat exchangers or<br />

cooling units must be used.<br />

Himel offers a wide range of solutions adapted to all situations.<br />

To air<br />

Natural dissipation (through the enclosure walls).<br />

In some cases, using a larger enclosure can solve the heating problem.<br />

Natural ventilation<br />

Providing fresh exterior air through ventilation outlet grilles improves heat<br />

dissipation through natural convection.<br />

Nevertheless, this solution can only be used in low-dust environments when<br />

the power to be dissipated is low.<br />

If At > Dt<br />

If At < Dt<br />

At = ambient temperature.<br />

Dt = internal desired temperature.<br />

6/95


HEAT CALCULATION<br />

Thermal management for electrical control panels<br />

To ventilate<br />

Ventilation<br />

Using a fan to circulate air within the enclosure can even out the temperature<br />

and prevent hot spots which could be harmful to certain components.<br />

Forced ventilation<br />

HIMEL fans are designed to remove large quantities of heat generated by<br />

electrical control panel components. This signifi cantly increases component<br />

longevity, thus ensuring the durability and correct operation of the installation.<br />

The fans, which are easy to install and maintain, as well as economical, are<br />

an effective solution to the problem of rising temperatures in electrical control<br />

panels.<br />

Due to their IP degree of protection, they can be used both in industrial<br />

environments and in the tertiary sector.<br />

To cool<br />

Air/air exchangers<br />

HIMEL air-air exchangers combine performance and simplicity: the movement<br />

of hot air from the enclosure and cool air from the surrounding environment<br />

by means of two fans circulating on either side of sealed divider walls<br />

prevents dust and humidity from penetrating the enclosure. Warm air from the<br />

panel heats these walls, which are then cooled by the colder external air. The<br />

heat transfer always takes place from the warmer to the cooler area. For this<br />

reason, these devices can only be used if the ambient temperature is at least<br />

5ºC lower than the required internal temperature of the enclosure.<br />

The aluminium exchange battery is at the heart of the system. This element<br />

can be cleaned as it is easily removed.<br />

In addition, the continuous operation of an internal fan prevents hot spots<br />

in the electrical control panel. The temperature is regulated by switching the<br />

external circuit fan on and off.<br />

Undesired effects on the components installed in poorly-cooled environments.<br />

6/96


HEAT CALCULATION<br />

Thermal management for electrical control panels<br />

To cool<br />

Air/water exchangers<br />

The operating principle of HIMEL air/water exchangers is similar to that of the<br />

air/air exchangers: the cool external air is replaced by cold water supplied by<br />

the piping of the installation itself on the industrial site.<br />

Due to this fl uid exchange, much larger quantities of heat can be removed,<br />

and the temperature within the electrical control panel can be adjusted to<br />

below that of the ambient air.<br />

Temperature within the panel is regulated by modulating the water fl ow.<br />

The water circuit is protected by a supply shut-off device ensuring the safety<br />

of your electrical installation.<br />

Cooling units<br />

HIMEL cooling units can be used in the most severe environments, where<br />

temperatures can reach 55ºC. These units are particularly suitable when<br />

the required temperature of the enclosure must be lower than the ambient<br />

temperature, or when large quantities of heat must be removed. As in the<br />

case of the exchangers, they do not affect the IP rating of the panel.<br />

Due to the fi lter located at the intake of the external air circuit, they can<br />

operate even when the ambient air is very dusty or greasy. This device is easy<br />

to replace and ensures that the effi ciency of the equipment is maintained<br />

throughout its entire service life.<br />

The cooling units have an enclosure temperature control system and an alarm<br />

function which is triggered in the event of a malfunction.<br />

To heat<br />

Resistance heaters<br />

There are two reasons to use resistance heaters:<br />

c To heat the electrical control enclosure when the ambient temperature is<br />

too low for the components to operate correctly.<br />

c To prevent water condensation from forming.<br />

Condensation can cause short circuits, premature contact oxidation,<br />

corrosion of metal parts (particularly those of the enclosure), and it can<br />

signifi cantly reduce the service life of electrical and electronic components.<br />

Condensation occurs when the temperature quickly drops below the dew<br />

point. This can be prevented by simply maintaining the temperature within the<br />

enclosure at a few degrees above the ambient temperature.<br />

The design of the HIMEL heaters facilitates natural convection and ensures a<br />

both uniform and rapid heating of the enclosure.<br />

6/97


HEAT CALCULATION<br />

Thermal calculation and mounting suggestions<br />

Determining the temperature control equipment<br />

The temperature control calculation consists of comparing the power<br />

dissipated by the operating components with the power exchanged<br />

spontaneously by the enclosure walls. It enables calculation of the internal<br />

temperature in the enclosure without use of a temperature control system and<br />

therefore determination of whether or not one should be installed, taking into<br />

account the required external and internal temperatures.<br />

The following presents a simple method of making such a selection.<br />

Example: OLN<br />

Ref.: OLN208/40<br />

Height = 2000<br />

Width = 800<br />

Depth = 400<br />

1 ENCLOSURE CHARACTERISTICS<br />

Enclosure<br />

position<br />

Placement as specified by IEC 890<br />

Accessible from all sides<br />

Formula for calculation of S (m 2 )<br />

(A)<br />

Height<br />

(B)<br />

Width<br />

(C)<br />

Depth<br />

S = 1.8 A (B+C) + 1.4 B C<br />

Placed against a wall.<br />

S = 1.4 B (A+C) + 1.8 C A<br />

End, in the case of coupling<br />

End, in the case of coupling and placed against<br />

a wall<br />

Intermediate in the case of coupling<br />

S = 1.4 C (A+B) + 1.8 B A<br />

S = 1.4 A (B+C) + 1.4 B C<br />

S = 1.8 3 B 3 A + 1.4 3 B 3 C + C 3 A<br />

Installation type:<br />

enclosure placed against<br />

a wall.<br />

S = 4.13 m 2<br />

Intermediate in the case of coupling and placed<br />

against a wall<br />

Intermediate in the case of coupling and placed<br />

against a wall with the upper part covered<br />

S = 1.4 B (A+C) + C A<br />

S = 1.4 B A + 0.7 B C + C A<br />

S = m 2<br />

Assume that the components<br />

dissipate 800 W.<br />

Pd = 800 W<br />

2 POWER DISSIPATED BY OPERATING COMPONENTS<br />

This is obtained by totalling the power dissipated by each component<br />

installed.<br />

If the individual values are unknown, use the tables on page which provide<br />

average values.<br />

Pd = W<br />

Temperature conditions<br />

are as follows:<br />

Te max<br />

= 35 °C<br />

Te mín<br />

= 15 °C<br />

3 CHARACTERISTICS OF AMBIENT AIR<br />

Maximum ambient temperature.<br />

Minimum ambient temperature.<br />

Average relative humidity.<br />

Te max<br />

= °C<br />

Te mín<br />

= °C<br />

Td max<br />

= 40 °C<br />

Td mín<br />

= 15 °C<br />

Cooling is required<br />

Ti max<br />

= 70 °C<br />

Ti mín<br />

= 15 °C<br />

4 REQUIRED INTERNAL AVERAGE TEMPERATURES<br />

These are characterised by the type of components and the characteristics<br />

of the ambient air.<br />

Maximum internal temperature (desired).<br />

Minimun internal temperature (desired).<br />

Td mín<br />

Td max<br />

=<br />

=<br />

°C<br />

°C<br />

5 FINAL ENCLOSURE TEMPERATURE WITHOUT TEMPERATURE CONTROL SYSTEM<br />

Maximum internal temperature Ti Pd<br />

max<br />

= + Te<br />

K S max<br />

Ti mín<br />

= °C<br />

Minimun internal temperature Ti min<br />

= Te min<br />

(voltage-free panel).<br />

K = 5.5 W/m 2 ºK for a metal enclosure.<br />

K = 3.5 W/m 2 ºK for a polyester enclosure.<br />

K = 3.7 W/m 2 ºK for a stainless steel enclosure.<br />

K = 12 W/m 2 ºK for an aluminium enclosure.<br />

Ti max<br />

= °C<br />

6/98


HEAT CALCULATION<br />

Thermal calculation and mounting suggestions<br />

6 DETERMINATION OF THE TYPE OF TEMPERATURE CONTROL SYSTEM AND ITS POWER PSYST<br />

Td mín<br />

< Ti mín<br />

Td mín<br />

> Ti mín<br />

Td max<br />

< Ti max<br />

Td max<br />

> Ti max<br />

Temperature control system not required,<br />

but circulation fan could be installed to<br />

even out temperature.<br />

Temperature control system required:<br />

resistance heater.<br />

1 Permanent switchboard operation<br />

Psyst = K S (Td mín<br />

– Te mín<br />

) – Pd<br />

2 Intermittent operation:<br />

Temperature control system required: either<br />

fan, exchanger or cooling unit.<br />

Psis = Pd – K S (Td max<br />

– Te max<br />

)<br />

Psis = 800 – 5.5 4.13 (40 – 35) ± 690 W<br />

Temperature control system not required, but a<br />

circulation fan could be installed to eliminate hot<br />

spots.<br />

Psyst = K S (Td mín<br />

– Te mín<br />

)<br />

Ventilating<br />

Temperature conditions Solution Advantages of solution Constraints of solution<br />

Avoid hot spots. Install circulation fans in the enclosure. Highly economical maintenance-free<br />

solution. Simple installation. Installation IP<br />

maintained.<br />

Quantity of heat removed is relatively low.<br />

Cooling<br />

Temperature conditions Solution Advantages of solution Constraints of solution<br />

Oversize the enclosure.<br />

Economical maintenance-free solution.<br />

Simple installation. Installation IP<br />

maintained.<br />

Quantity of heat removed is relatively low.<br />

Increased dimensions.<br />

Final temperature required in the enclosure<br />

Ts (max) at least 5 °C higher than the<br />

maximum ambient temperature Te (max).<br />

Install ventilation louvres.<br />

Highly economical maintenance-free<br />

solution. Simple installation.<br />

Quantity of heat removed is low, depending on<br />

arrangement of components. IP downgraded<br />

(dust penetration).<br />

Td max ≥ Te max + 5 °C<br />

Install fresh air inlet fans.<br />

D =<br />

Psyst<br />

3.1 m 3 /h<br />

(Tsmax-Temax)<br />

Economical maintenance-free solution,<br />

simple to install. Quantity of heat removed<br />

high. Temperature control possible.<br />

Regular filter maintenance. IP slightly<br />

downgraded.<br />

Use an air/air exchanger.<br />

q =<br />

Psyst<br />

wk<br />

(Tsmax-Temax)<br />

Simple installation. Installation IP<br />

maintained. Temperature control as<br />

standard. Simple maintenance.<br />

Regular filter maintenance.<br />

Final temperature required in the enclosure<br />

Ts (max) at least 5 ºC lower than the<br />

maximun ambient temperature Te (max).<br />

Use a cooling unit.<br />

Simple installation. Enables evacuation<br />

of large quantities of heat, even when<br />

ambient temperature is high. Installation IP<br />

maintain. Temperature regulation.<br />

Regular filter maintenance. Can not be used<br />

above ambient temperature 55 °C.<br />

Td max ≤ Te max + 5 °C<br />

Use an air/water exchanger.<br />

Simple installation. Enables evacuation<br />

of large quantities of heat, even when<br />

ambient temperature is high. Installation IP<br />

maintain. Temperature control as standard.<br />

No filter to maintain.<br />

Water circuit required. Water consumption cost<br />

if mains supply used.<br />

Heating<br />

Temperature conditions Solution Advantages of solution Constraints of solution<br />

External temperature lower than the<br />

minimum temperature admissible by<br />

components.<br />

Condensation risk.<br />

Heating by resistance heater.<br />

Heating by resistance heater to maintain<br />

temperature above the dew point<br />

temperature.<br />

Economical, reliable.Temperature in<br />

enclosure can be controlled.<br />

Economical, reliable, Humidity in enclosure<br />

can be controlled.<br />

Energy consumption. Space occupied in<br />

enclosure.<br />

Energy consumption. Space occupied in<br />

enclosure.<br />

6/99


ClimaSys: calculation support service<br />

PROclima 4.0<br />

PROclima 4.0<br />

We have developed the PROclima programme to facilitate the calculation<br />

and selection of temperature control equipment for enclosures containing<br />

electrical or electronic equipment.<br />

The programme calculates the thermal balance inside the enclosure and<br />

recommends the most suitable solution based on the values entered.<br />

Data entry<br />

Entry of the data for the installation necessary to calculate the “thermal<br />

balance”.<br />

The steps to follow are:<br />

1 Input of the project and customer data.<br />

2 Input of the temperature data.<br />

3 Input of the electrical data of the installation (voltage for selecting the<br />

solution and intensity for the calculation of the dissipation in the busbars).<br />

4 Input of the power dissipated by the electrical components inside the<br />

enclosure; if the programme is not known, provide the means for its<br />

calculation:<br />

– By entering the type and quantity of the installed components.<br />

– In the case of manoeuvres during operation, by reading the interior/exterior<br />

temperature.<br />

5 Select the enclosure model and the method of installation.<br />

Results<br />

6 Select the control system (fans, exchangers, etc.).<br />

7 View and print the result.<br />

Printing and drawing up of the thermal study report<br />

Once the calculation has been made, a report can be printed, which details<br />

all the calculation data, the results obtained, as well as the equipment<br />

recommended to maintain the internal temperature of the enclosure under the<br />

conditions indicated.<br />

The report provides the machining template to scale, as well as the<br />

dimensions and electrical characteristics of the recommended equipment.<br />

6/100


1 Input the project and customer<br />

data (optional).<br />

5 Select the enclosure model<br />

and the method of installation<br />

(compulsory).<br />

2 Input the internal and external<br />

temperature data of the enclosures<br />

(compulsory).<br />

6 Select the control system (fans,<br />

exchangers, etc.) (compulsory).<br />

3 Input the electrical data of the<br />

installation (compulsory).<br />

4 Input the power dissipated by the<br />

electrical components inside the<br />

enclosure (compulsory).<br />

7 View and print the result.<br />

6/101


HEAT CALCULATION<br />

Calculation support software<br />

Calculation and selection assistance software<br />

PROclima software<br />

c Calculation and selection programme for temperature control equipment for<br />

enclosures containing electrical or electronic equipment.<br />

c The programme performs the calculations presented on pages 6/98 and<br />

6/99, as well as the dissipation surface areas, based on the dimensions of<br />

the enclosure and its position with respect to the walls.<br />

c Available on CD-ROM in two languages: Spanish and English.<br />

c Minimum requirements: PC that is IBM PC 486 SX compatible, 33 MHz,<br />

with 8 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA<br />

graphics card (640 480 pixels).<br />

c Recommended requirements: PC that is IBM Pentium 90 MHz compatible,<br />

with 16 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA<br />

graphics card (800 600 pixels).<br />

c Required components: Microsoft DOS version 5.0 or later, Microsoft<br />

Windows version 3.1 or later, Microsoft Windows NT version 3.51.944 or<br />

later.<br />

Project phases with the PROclima software<br />

c General project data.<br />

Customer, technical manager, name, place, and date of project.<br />

c Selection of enclosure model.<br />

Range, dimensions, placement.<br />

c Temperature data:<br />

v Minimum and maximum temperatures, possible external temperatures.<br />

v Minimum and maximum temperatures desired inside the enclosure.<br />

v Altitude.<br />

v Relative humidity.<br />

c Dissipated power assessment.<br />

It is theoretically known or can be recreated from a database:<br />

v Enter the dissipated power of the components.<br />

v And/or select all the electrical and electronic elements installed inside the<br />

enclosure to then calculate an approximate value.<br />

The thermal balance consists of comparing the energy dissipated by the<br />

components of the installation with the energy dissipated spontaneously by<br />

the walls of the enclosure.<br />

It makes it possible to defi ne the external temperature of the enclosure<br />

without a temperature control element and to justify the installation of<br />

equipment.<br />

c Selection of the temperature control element.<br />

A screen makes it possible to select the control system (fan, exchanger,<br />

cooling unit, resistance heaters) to proportion with the programme.<br />

After the calculation, the power, specifi cations, and reference numbers<br />

of the temperature control element and the respective accessories are<br />

needed.<br />

The programme provides a project summary that can be printed.<br />

6/102


HEAT CALCULATION<br />

Calculation example<br />

Data<br />

Enclosure characteristics<br />

c Dimensions<br />

Height: 2000 mm<br />

Width: 800 mm<br />

Depth: 500 mm<br />

c Location: against a wall<br />

c Material: enclosure in painted sheet steel<br />

c Thermal power dissipated by operating components<br />

Pd: 950 W<br />

c Environment and temperature data:<br />

Maximum temperature expected outside the enclosure<br />

Te max<br />

: 25 ºC<br />

Minimum temperature expected outside the enclosure<br />

Te min<br />

: 25 ºC<br />

Minimum temperature dissipated inside the enclosure<br />

Te max<br />

: 35 ºC<br />

Minimum temperature dissipated outside the enclosure<br />

Te min<br />

: 25 ºC<br />

Atmosphere characteristics: little pollution with low dust levels<br />

Selection and calculation:<br />

The maximum required temperature (Ts max<br />

) inside the enclosure is 10 ºC higher<br />

than the maximum value expected outside (Ti max<br />

).<br />

It is possible to cool the enclosure using fi ltered ventilation systems.<br />

Calculation of the fan required:<br />

Usage formulas:<br />

Psis = Pd – (k S (Ts max<br />

– Te max<br />

)<br />

Flow = f Psis / (Td max<br />

– Te max<br />

)<br />

Pd: thermal power dissipated by operating components<br />

S = 1.4 L (H+P) + 1.8 P H = 4.6 m 2 . Conforming to standard IEC 890.<br />

K = Constant defi ned by the material used to construct the enclosure<br />

K = 5.5 W/m 2 ºC for a painted steel sheet enclosure<br />

K = 3.5 W/m 2 ºC for a polyester enclosure<br />

K = 3.7 W/m 2 ºC for a stainless steel enclosure<br />

For the calculation, it is necessary to know the altitude above sea level of the installation site:<br />

Altitude above sea level: 800 m<br />

f = Coeffi cient related to the altitude above sea level (value)<br />

0 to 100 m f = 3.1<br />

100 to 250 m f = 3.2<br />

250 to 500 m f = 3.3<br />

500 to 750 m f = 3.4<br />

750 to 1000 m f = 3.5<br />

................<br />

In our example:<br />

Psis = 950 – 5.5 4.6 (35 – 25) = 497 W<br />

Flow = 3.5 697/(35 – 25) = 244 m 3 /h<br />

Selecting from the quick-selection table of fans<br />

1 fan with standard VF300 fi lter + 1 outlet grille with standard FS615 + fi lter<br />

1 thermostat TS141F35<br />

They provide a 302 m 3 /h fl ow rate<br />

The minimum expected exterior temperature is less than the minimum required temperature<br />

inside the enclosure.<br />

It is necessary to install resistance heaters:<br />

Calculation of the resistance necessary:<br />

Usage formulas:<br />

W = 5.5 4.6 (15 – 10) = 127 W<br />

In our example:<br />

W = 5.5 4.6 (15 – 10) = 127 W<br />

Selecting from the quick-selection table of resistance heaters<br />

1 resistance heater Ref. RC150AI + 1 thermostat Ref. TS140F15<br />

6/103


HEAT CALCULATION<br />

Dissipation surface area<br />

Dissipation surface area of the metal<br />

enclosures: CRN-CRNG<br />

Accessible on all sides<br />

Installation mode<br />

Against a wall<br />

At one end of a row<br />

At one end of a row, against a wall<br />

Intermediate in a row<br />

Intermediate in a row, against a wall<br />

Intermediate in a row, against a wall,<br />

closed covered top<br />

Enclosure model<br />

CRN / CRNG<br />

Dimensions in mm<br />

A B C<br />

Type of installation conforming to IEC 890<br />

■ 250 200 150 0.20 0.18 0.18 0.16 0.17 0.15 0.13<br />

■ 300 250 150 0.27 0.24 0.25 0.22 0.23 0.20 0.18<br />

■ 300 250 200 0.31 0.28 0.29 0.26 0.27 0.24 0.20<br />

■ 300 300 150 0.31 0.27 0.29 0.25 0.27 0.23 0.20<br />

■ 300 300 200 0.35 0.32 0.33 0.29 0.31 0.27 0.23<br />

■ 300 400 200 0.44 0.39 0.41 0.40 0.39 0.34 0.28<br />

■ 400 300 150 0.39 0.34 0.36 0.32 0.34 0.29 0.26<br />

■ 400 300 200 0.44 0.40 0.41 0.36 0.38 0.33 0.29<br />

■ 400 400 200 0.54 0.48 0.51 0.45 0.48 0.42 0.36<br />

■ 400 600 250 0.82 0.73 0.78 0.69 0.74 0.65 0.54<br />

■ 400 600 300 0.90 0.80 0.85 0.76 0.80 0.71 0.58<br />

■ 500 400 150 0.58 0.50 0.55 0.47 0.52 0.44 0.40<br />

■ 500 400 200 0.65 0.57 0.61 0.53 0.57 0.49 0.44<br />

■ 500 400 250 0.73 0.65 0.68 0.60 0.63 0.55 0.48<br />

■ 500 500 250 0.85 0.75 0.80 0.70 0.75 0.65 0.56<br />

■ 600 400 150 0.68 0.58 0.64 0.55 0.61 0.51 0.47<br />

■ 600 400 200 0.76 0.66 0.71 0.62 0.66 0.57 0.51<br />

■ 600 400 250 0.84 0.75 0.78 0.69 0.72 0.63 0.56<br />

■ 600 500 150 0.81 0.69 0.77 0.65 0.74 0.62 0.56<br />

■ 600 500 200 0.90 0.78 0.85 0.73 0.80 0.68 0.61<br />

■ 600 500 250 0.99 0.87 0.93 0.81 0.87 0.75 0.66<br />

■ 600 600 250 1.13 0.98 1.07 0.92 1.01 0.86 0.76<br />

■ 600 600 300 1.22 1.08 1.15 1.01 1.08 0.94 0.81<br />

■ 600 800 300 1.52 1.33 1.45 1.36 1.38 1.19 1.02<br />

■ 700 500 200 1.02 0.88 0.97 0.83 0.91 0.77 0.70<br />

■ 700 500 250 1.12 0.98 1.05 0.91 0.98 0.84 0.75<br />

■ 800 600 200 1.32 1.13 1.26 1.06 1.19 1.00 0.92<br />

■ 800 600 250 1.43 1.24 1.35 1.16 1.27 1.08 0.98<br />

■ 800 600 300 1.55 1.36 1.45 1.26 1.36 1.16 1.04<br />

■ 800 800 200 1.66 1.41 1.60 1.34 1.54 1.28 1.17<br />

■ 800 800 300 1.92 1.66 1.82 1.57 1.73 1.47 1.30<br />

■ 800 1000 300 2.29 1.97 1.45 1.36 1.38 1.19 1.02<br />

■ 1000 600 250 1.74 1.50 1.64 1.40 1.54 1.30 1.20<br />

■ 1000 600 300 1.87 1.63 1.75 1.51 1.63 1.39 1.27<br />

1000 800 200 2.02 1.70 1.94 1.62 1.86 1.54 1.43<br />

■ 1000 800 250 2.17 1.85 2.07 1.75 1.97 1.65 1.51<br />

■ 1000 800 300 2.32 2.00 2.20 1.88 2.08 1.76 1.59<br />

■ 1000 1000 300 2.76 2.36 2.64 2.24 2.52 2.12 1.91<br />

■ 1000 1200 300 3.20 2.72 3.08 2.75 2.96 2.48 2.23<br />

■ 1200 800 300 2.71 2.33 2.57 2.18 2.42 2.04 1.87<br />

■ 1200 1000 300 3.23 2.75 3.08 2.60 2.94 2.46 2.25<br />

Surface areas are expressed in m 2 .<br />

6/104


HEAT CALCULATION<br />

Dissipation surface area<br />

Dissipation surface area of the metal enclosures:<br />

CMO and OLN<br />

Accessible on all sides<br />

Installation mode<br />

Against a wall<br />

At one end of a row<br />

At one end of a row, against a wall<br />

Intermediate in a row<br />

Intermediate in a row, against a wall<br />

Intermediate in a row, against a wall,<br />

closed covered top<br />

Enclosure reference<br />

number<br />

Dimensions in mm<br />

A B C<br />

Type of installation conforming to IEC 890<br />

CMO1010/30 1000 1000 300 2.76 2.36 2.64 2.36 2.52 2.12 1.91<br />

CMO128/30 1200 800 300 2.71 2.33 2.57 2.28 2.42 2.04 1.87<br />

CMO1210/30 1200 1000 300 3.23 2.75 3.08 2.72 2.94 2.46 2.25<br />

CMO1212/40 1200 1200 400 4.13 3.55 3.94 3.55 3.74 3.17 2.83<br />

CMO146/30 1400 600 300 2.52 2.18 2.35 2.09 2.18 1.85 1.72<br />

CMO146/40 1400 600 400 2.86 2.52 2.63 2.39 2.41 2.07 1.90<br />

CMO148/30 1400 800 300 3.11 2.66 2.94 2.59 2.77 2.32 2.16<br />

CMO148/40 1400 800 400 3.47 3.02 3.25 2.93 3.02 2.58 2.35<br />

CMO1410/40 1400 1000 400 4.09 3.53 3.86 3.46 3.64 3.08 2.80<br />

CMO1412/40 1400 1200 400 4.70 4.03 4.48 4.00 4.26 3.58 3.25<br />

CMO166/30 1600 600 300 2.84 2.46 2.65 2.34 2.46 2.08 1.95<br />

CMO166/40 1600 600 400 3.22 2.83 2.96 2.67 2.70 2.32 2.15<br />

CMO168/30 1600 800 300 3.50 2.99 3.31 2.90 3.12 2.61 2.44<br />

CMO168/40 1600 800 400 3.90 3.39 3.65 3.26 3.39 2.88 2.66<br />

CMO1610/30 1600 1000 300 4.16 3.52 3.97 3.45 3.78 3.14 2.93<br />

CMO1610/40 1600 1000 400 4.95 3.95 4.34 3.86 4.08 3.44 3.16<br />

CMO1612/30 1600 1200 300 4.82 4.06 4.63 4.01 4.44 3.67 3.42<br />

CMO1612/40 1600 1200 400 5.28 4.51 5.02 4.45 4.77 4.00 3.66<br />

CMO186/30 1800 600 300 3.17 2.74 2.95 2.59 2.74 2.30 2.18<br />

CMO186/40 1800 600 400 3.58 3.14 3.29 2.95 3.00 2.57 2.40<br />

CMO188/30 1800 800 300 3.90 3.32 3.68 3.20 3.47 2.89 2.72<br />

CMO188/40 1800 800 400 4.34 3.76 4.05 3.60 3.76 3.18 2.96<br />

CMO188/50 1800 800 500 4.77 4.20 4.41 4.00 4.05 3.48 3.20<br />

CMO188/60 1800 800 600 5.21 4.63 4.78 4.39 4.34 3.77 3.43<br />

CMO1810/40 1800 1000 400 5.10 4.38 4.81 4.25 4.52 3.80 3.52<br />

CMO1810/50 1800 1000 500 5.56 4.84 5.20 4.68 4.84 4.12 3.77<br />

CMO1812/40 1800 1200 400 5.86 4.99 5.57 4.90 5.28 4.42 4.08<br />

CMO1812/50 1800 1200 500 6.35 5.48 5.99 5.36 5.63 4.76 4.34<br />

CMO1816/40 1800 1600 400 7.38 6.22 7.09 6.19 6.80 5.65 5.20<br />

CMO1816/50 1800 1600 500 7.92 6.77 7.56 6.73 7.20 6.05 5.49<br />

CMO206/30 2000 600 300 3.49 3.01 3.25 2.84 3.01 2.53 2.41<br />

CMO206/40 2000 600 400 3.94 3.46 3.62 3.23 3.30 2.82 2.65<br />

CMO208/30 2000 800 300 4.30 3.66 4.06 3.51 3.82 3.18 3.01<br />

CMO208/40 2000 800 400 4.77 4.13 4.45 3.94 4.13 3.49 3.26<br />

CMO208/50 2000 800 500 5.24 4.60 4.84 4.36 4.44 3.80 3.52<br />

CMO208/60 2000 800 600 5.71 5.07 5.23 4.78 4.75 4.11 3.78<br />

CMO2010/40 2000 1000 400 5.60 4.80 5.28 4.64 4.96 4.16 3.88<br />

CMO2010/50 2000 1000 500 6.10 5.30 5.70 5.10 5.30 4.50 4.15<br />

CMO2012/40 2000 1200 400 6.43 5.47 6.11 5.34 5.79 4.83 4.50<br />

CMO2012/50 2000 1200 500 6.96 6.00 6.56 5.84 6.16 5.20 4.78<br />

CMO2012/60 2000 1200 600 7.49 6.53 7.01 6.34 6.53 5.57 5.06<br />

CMO2016/40 2000 1600 400 8.10 6.82 7.78 6.75 7.46 6.18 5.73<br />

CMO2016/50 2000 1600 500 8.68 7.40 8.28 7.32 7.88 6.60 6.04<br />

CMO2016/60 2000 1.600 600 9.26 7.98 8.78 7.89 8.30 7.02 6.35<br />

6/105


HEAT CALCULATION<br />

Dissipation surface area<br />

Dissipation surface area of the metal<br />

enclosures: OLN<br />

Enclosure reference<br />

number<br />

Dimensions in mm<br />

A B C<br />

Type of installation conforming to IEC 890<br />

OLN126/40 1200 600 400 2.50 2.21 2.30 2.02 2.11 1.82 1.66<br />

OLN126/60 1200 600 600 3.70 2.81 2.81 2.52 2.52 2.23 1.98<br />

OLN126/80 1200 600 800 3.70 3.41 3.31 3.02 2.93 2.64 2.30<br />

OLN128/40 1200 800 400 3.04 2.66 2.85 2.46 2.66 2.27 2.05<br />

OLN128/60 1200 800 600 3.70 3.31 3.41 3.02 3.12 2.74 2.40<br />

OLN128/80 1200 800 800 4.35 3.97 3.97 3.58 3.58 3.20 2.75<br />

OLN146/40 1400 600 400 2.86 2.52 2.63 2.30 2.41 2.07 1.90<br />

OLN146/60 1400 600 600 3.53 3.19 3.19 2.86 2.86 2.52 2.27<br />

OLN146/80 1400 600 800 4.20 3.86 3.75 3.42 3.30 2.97 2.63<br />

OLN148/40 1400 800 400 3.47 3.02 3.25 2.80 3.02 2.58 2.35<br />

OLN148/60 1400 800 600 4.20 3.75 3.86 3.42 3.53 3.08 2.74<br />

OLN148/80 1400 800 800 4.93 4.48 4.48 4.03 4.03 3.58 3.14<br />

OLN166/60 1600 600 600 3.96 3.58 3.58 3.19 3.19 2.81 2.56<br />

OLN166/80 1600 600 800 4.70 4.32 4.19 3.81 3.68 3.30 2.96<br />

OLN168/60 1600 800 600 4.70 4.19 4.32 3.81 3.94 3.42 3.09<br />

OLN168/80 1600 800 800 5.50 4.99 4.99 4.48 4.48 3.97 3.52<br />

OLN186/40 1800 600 400 3.58 3.14 3.29 2.86 3.00 2.57 2.40<br />

OLN186/50 1800 600 500 3.98 3.55 3.62 3.19 3.26 2.83 2.62<br />

OLN186/60 1800 600 600 4.39 3.96 3.96 3.53 3.53 3.10 2.84<br />

OLN186/80 1800 600 800 5.21 4.78 4.69 4.20 4.06 3.62 3.29<br />

OLN188/40 1800 800 400 4.34 3.76 4.05 3.47 3.76 3.18 2.96<br />

OLN188/50 1800 800 500 4.77 4.20 4.41 3.84 4.05 3.48 3.20<br />

OLN188/60 1800 800 600 5.21 4.63 4.78 4.20 4.34 3.77 3.43<br />

OLN1810/40 1800 1000 400 5.10 4.38 4.81 4.09 4.52 3.80 3.52<br />

OLN1810/40/2P 1800 1000 400 5.10 4.38 4.81 4.09 4.52 3.80 3.52<br />

OLN1810/50 1800 1000 500 5.56 4.84 5.20 4.48 4.84 4.12 3.77<br />

OLN1810/50/2P 1800 1000 500 5.56 4.84 5.20 4.48 4.84 4.12 3.77<br />

OLN1810/60 1800 1000 600 6.02 5.30 5.59 4.87 5.16 4.44 4.02<br />

OLN1810/60/2P 1800 1000 600 6.02 5.30 5.59 4.87 5.16 4.44 4.02<br />

OLN1812/40/2P 1800 1200 400 5.86 4.99 5.57 4.70 5.28 4.42 4.08<br />

OLN1812/50/2P 1800 1200 500 6.35 5.48 5.99 5.12 5.63 4.76 4.34<br />

OLN1812/60/2P 1800 1200 600 6.84 5.98 6.41 5.54 5.98 5.11 4.61<br />

OLN203/50 2000 300 500 3.09 2.85 2.69 2.45 2.29 2.05 1.95<br />

OLN203/60 2000 300 600 3.49 3.25 3.01 2.77 2.53 2.29 2.17<br />

OLN203/80 2000 300 600 4.30 4.06 3.66 3.51 3.02 2.78 2.61<br />

OLN206/40 2000 600 400 3.94 3.46 3.62 3.14 3.30 2.82 2.65<br />

OLN206/50 2000 600 500 4.38 3.90 3.98 3.50 3.58 3.10 2.89<br />

OLN206/60 2000 600 600 4.82 4.34 4.34 3.86 3.86 3.38 3.13<br />

OLN206/80 2000 600 800 5.71 5.23 5.07 4.59 4.43 3.95 3.62<br />

OLN208/40 2000 800 400 4.77 4.13 4.45 3.81 4.13 3.49 3.26<br />

OLN208/50 2000 800 500 5.24 4.60 4.84 4.20 4.44 3.80 3.52<br />

OLN208/60 2000 800 600 5.71 5.07 5.23 4.59 4.7 4.11 3.78<br />

OLN208/80 2000 800 800 6.66 6.02 6.02 5.38 5.38 4.74 4.29<br />

OLN2010/40 2000 1000 400 5.60 4.80 5.28 4.48 4.96 4.16 3.88<br />

OLN2010/40/2P 2000 1000 400 5.60 4.80 5.28 4.48 4.96 4.16 3.88<br />

OLN2010/50 2000 1000 500 6.10 5.30 5.70 4.90 5.30 4.50 4.15<br />

OLN2010/50/2P 2000 1000 500 6.10 5.30 5.70 4.90 5.30 4.50 4.15<br />

OLN2010/60 2000 1000 600 6.60 5.80 6.12 5.32 5.64 4.84 4.42<br />

OLN2010/60/2P 2000 1000 600 6.60 5.80 6.12 5.32 5.64 4.84 4.42<br />

OLN2010/80 2000 1000 800 7.60 6.80 6.96 6.16 6.32 5.52 4.96<br />

OLN2010/80/2P 2000 1000 800 7.60 6.80 6.96 6.16 6.32 5.52 4.96<br />

OLN2012/40/2P 2000 1200 400 6.43 5.47 6.11 5.15 5.79 4.83 4.50<br />

OLN2012/50/2P 2000 1200 500 6.96 6.00 6.56 5.60 6.16 5.20 4.78<br />

OLN2012/60/2P 2000 1200 600 7.49 6.53 7.01 6.05 6.53 5.57 5.06<br />

OLN2012/80/2P 2000 1200 800 8.54 7.58 7.90 6.94 7.26 6.30 5.63<br />

OLN226/60 2200 600 600 5.26 4.73 4.73 4.20 4.20 3.67 3.42<br />

OLN226/80 2200 600 800 6.22 5.69 5.51 4.98 4.81 4.28 3.94<br />

OLN228/60 2200 800 600 6.22 5.51 5.69 4.98 5.16 4.46 4.12<br />

OLN228/80 2200 800 800 7.23 6.53 6.53 5.82 5.82 5.12 4.67<br />

OLN2210/60 2200 1000 600 7.18 6.30 6.65 5.77 6.12 5.24 4.82<br />

OLN2210/80 2200 1000 800 8.25 7.37 7.54 6.66 6.84 5.96 5.40<br />

OLN2210/80/2P 2200 1000 800 8.25 7.37 7.54 6.66 6.84 5.96 5.40<br />

OLN2212/60/2P 2200 1200 600 8.14 7.08 7.61 6.55 7.08 6.02 5.52<br />

OLN2212/80/2P 2200 1200 800 9.26 8.21 8.56 7.50 7.86 6.80 6.13<br />

6/106


HEAT CALCULATION<br />

Dissipation surface area of the polyester<br />

enclosures: POLYMEL<br />

Enclosure reference<br />

number<br />

Dimensions in mm<br />

A B C<br />

Type of installation conforming to IEC 890<br />

PLM3025 308 255 160 0.29 0.23 0.26 0.27 0.25 0.22 0.19<br />

PLM32 310 215 160 0.26 0.23 0.24 0.21 0.22 0.19 0.17<br />

PLM43 430 330 200 0.50 0.45 0.47 0.41 0.43 0.38 0.33<br />

PLM54 530 430 200 0.72 0.63 0.68 0.59 0.64 0.55 0.49<br />

PLM64 647 436 250 0.95 0.84 0.89 0.77 0.82 0.71 0.63<br />

PLM75 747 536 300 1.35 1.19 1.26 1.10 1.17 1.01 0.90<br />

PLM86 847 636 300 1.69 1.48 1.59 1.38 1.49 1.28 1.14<br />

PLM108 1056 800 350 2.46 2.14 2.32 2.00 2.18 1.86 1.67<br />

Dissipation surface area of the polyester<br />

enclosures: PLA<br />

Enclosure reference number<br />

Dimensions in mm<br />

A B C<br />

Type of installation conforming to IEC 890<br />

PLA553 500 500 320 0.96 0.86 0.90 0.86 0.83 0.73 0.62<br />

PLA554 500 500 420 1.12 1.02 1.04 1.02 0.95 0.85 0.71<br />

PLA573 500 750 320 1.30 1.15 1.24 1.18 1.17 1.02 0.85<br />

PLA574 500 750 420 1.49 1.34 1.41 1.39 1.33 1.18 0.96<br />

PLA5103 500 1000 320 1.64 1.44 1.57 1.50 1.51 1.31 1.08<br />

PLA5104 500 1000 420 1.87 1.67 1.78 1.75 1.70 1.50 1.20<br />

PLA5123 500 1250 320 1.97 1.72 1.91 1.82 1.85 1.60 1.32<br />

PLA5124 500 1250 420 2.24 1.99 2.15 2.11 2.07 1.82 1.45<br />

PLA753 750 500 320 1.33 1.18 1.24 1.15 1.14 0.99 0.88<br />

PLA754 750 500 420 1.54 1.39 1.41 1.34 1.28 1.13 0.99<br />

PLA773 750 750 320 1.78 1.56 1.68 1.56 1.59 1.36 1.20<br />

PLA774 750 750 420 2.02 1.80 1.89 1.80 1.77 1.54 1.32<br />

PLA7103 750 1000 320 2.23 1.93 2.13 1.96 2.04 1.74 1.51<br />

PLA7104 750 1000 420 2.51 2.21 2.38 2.25 2.25 1.95 1.66<br />

PLA7123 750 1250 320 2.68 2.30 2.58 2.37 2.49 2.11 1.83<br />

PLA7124 750 1250 420 2.99 2.61 2.86 2.70 2.74 2.36 2.00<br />

PLA1053 1000 500 320 1.70 1.50 1.57 1.44 1.44 1.24 1.13<br />

PLA1054 1000 500 420 1.95 1.75 1.78 1.67 1.61 1.41 1.27<br />

PLA1073 1000 750 320 2.26 1.96 2.13 1.93 2.01 1.71 1.54<br />

PLA1074 1000 750 420 2.55 2.25 2.38 2.21 2.21 1.91 1.69<br />

PLA10103 1000 1000 320 2.82 2.42 2.70 2.42 2.57 2.17 1.94<br />

PLA10104 1000 1000 420 3.14 2.74 2.98 2.74 2.81 2.41 2.11<br />

PLA10123 1000 1250 320 3.39 2.89 3.26 2.92 3.13 2.63 2.35<br />

PLA10124 1000 1250 420 3.74 3.24 3.57 3.28 3.41 2.91 2.54<br />

PLA1253 1250 500 320 2.07 1.82 1.91 1.72 1.75 1.50 1.39<br />

PLA1254 1250 500 420 2.36 2.11 2.15 1.99 1.94 1.69 1.55<br />

PLA1273 1250 750 320 2.74 2.37 2.58 2.30 2.42 2.05 1.88<br />

PLA1274 1250 750 420 3.07 2.70 2.86 2.61 2.65 2.28 2.06<br />

PLA12103 1250 1000 320 3.42 2.92 3.26 2.89 3.10 2.60 2.37<br />

PLA12104 1250 1000 420 3.78 3.28 3.57 3.24 3.36 2.86 2.57<br />

PLA12123 1250 1250 320 4.09 3.47 3.93 3.47 3.77 3.15 2.87<br />

PLA12124 1250 1250 420 4.49 3.87 4.28 3.87 4.07 3.45 3.08<br />

PLA1553 1500 500 320 2.44 2.14 2.25 2.01 2.05 1.75 1.64<br />

PLA1554 1500 500 420 2.78 2.48 2.53 2.31 2.27 1.97 1.83<br />

PLA1573 1500 750 320 3.23 2.78 3.03 2.68 2.84 2.39 2.22<br />

PLA1574 1500 750 420 3.60 3.15 3.35 3.02 3.10 2.65 2.43<br />

PLA15103 1500 1000 320 4.01 3.41 3.82 3.35 3.63 3.03 2.80<br />

PLA15104 1500 1000 420 4.42 3.82 4.17 3.74 3.92 3.32 3.02<br />

PLA15123 1500 1250 320 4.80 4.05 4.61 4.02 4.42 3.67 3.39<br />

PLA15124 1500 1250 420 5.24 4.49 4.99 4.45 4.74 3.99 3.62<br />