4.3 Recommended Cable Types<br />
The following section lists recommended cable types for both the DDA power supply circuit and the DDA communication circuit.<br />
The lists are not inclusive of all cable types and cable manufacturers and should serve only as a guideline when choosing<br />
cables. Other cable types can be selected that meet the requirements of the DDA system.<br />
Recommended cable types for the DDA power supply circuit (individual cable pair):<br />
General requirements:<br />
• shielded, twisted pair<br />
• 24 picofarads/foot or less. See note below.<br />
• minimum 0.010 in. (0.25 mm) insulation thickness<br />
NOTE:<br />
For the power supply circuit, the return conductor is<br />
connected to the shield at the safety barrier ground<br />
terminal. When determining the capacitance of cable<br />
for the power supply circuit, use the manufacturer’s<br />
capacitance specifications shown for one conductor<br />
and the other conductor connected to the shield.<br />
WIRE SIZE CAPACITANCE MANUFACTURER CABLE # NOTES<br />
(AWG)<br />
(Pf/foot)<br />
16 40 ALPHA 2471 (16 AWG ok)<br />
18 44 BELDEN 8760<br />
18 49 BELDEN 9460<br />
16 49 CAROL C2536 (16 AWG ok)<br />
18 44 CAROL C2521<br />
18 43 DEKORON 1T52-8820T<br />
20 49 BELDEN 8762<br />
20 49 BELDEN 9464<br />
20 40 CAROL C2519<br />
20 45 CAROL C2520<br />
20 46 MANHATTAN M39047<br />
20 42 DEKORON 1T52-0810T<br />
22 16 ALPHA 6072 (extra wire pair)<br />
22 47 BELDEN 8761<br />
22 47 BELDEN 9461<br />
22 36 CAROL C2518<br />
22 47 CAROL C2514<br />
22 38 DEKORON 1T52-2810T (0.020 in. insulation)<br />
24 23 BELDEN 9841<br />
24 42 BELDEN 8641<br />
24 42 CAROL C2513<br />
24 40 DEKORON 1T52-A800T<br />
20