Function<br />

Model<br />

Load current (set current range) 3<br />

200V class<br />

Motor<br />

400V class<br />

Ambient temperature<br />

Operating<br />

Relative humidity<br />

environment<br />

Vibration<br />

Height<br />

Ambient atmosphere<br />

Current setting accuracy<br />

Start time<br />

Set time range<br />

3<br />

Shock time 3<br />

Power supply voltage (A1-A2)<br />

Maximum motor circuit voltage<br />

Current detecting system<br />

Standard<br />

Main unit parts<br />

Protection functions<br />

(not including overload)<br />

Trip output relay<br />

Relay operation<br />

Reverse phase<br />

Open phase<br />

Phase unbalance<br />

Contact capacity<br />

Minimum application load 2<br />

Operational mode<br />

at time of trip<br />

Non-operational mode<br />

at time of trip<br />

Trip status<br />

Reset method<br />

Set level<br />

Contact capacity<br />

Alarm output relay<br />

Minimum application load 2<br />

Operation<br />

Mechanical<br />

Output relay life<br />

Electrical<br />

Test functions<br />

Between the circuit and case<br />

Withstand voltage Between contacts<br />

Between circuit<br />

Mass<br />

Power consumption<br />

Attachable DIN rail<br />

Normal state<br />

At the time of trip<br />

Normal state<br />

At the time of trip<br />

Self-holding<br />

Automatic reset<br />

TSBSD10<br />

0.510A<br />

0.1 1 2.2kW<br />

0.2 1 3.7kW<br />

TSBSD60<br />

560A<br />

3.711kW<br />

5.522kW<br />

1050<br />

45-85% with no condensation<br />

Less than 5.9m/s 2<br />

Less than 1000m<br />

No corrosive gas or dust<br />

10% (full scale)<br />

0.312.0s<br />

0.33.0s<br />

AC85-250V, 50/60Hz or DC85V-250V<br />

AC600V, 50/60Hz<br />

3 phase CT system<br />

Trips 0.1s after phase reversal detected<br />

Trips 3s after open phase detected<br />

Trips 8s after phase unbalance (maximum value 2x minimum value) current detected<br />

1a1b contact, AC250V 3A (in case of resistance load)<br />

DC24V, 4mA<br />

Relay is not excited (no operation)<br />

Relay is excited (operation)<br />

After start-up there is a 0.5s delay; then relay is excited (operation)<br />

Relay is not excited (no operation)<br />

Self-holding/automatic resetting selectable<br />

RESET button is on or power is off<br />

Resets 1s after tripping<br />

50-100% of set load current value<br />

1a contact, AC250V 3A (in the case of resistance load)<br />

DC24V, 4mA<br />

When the alarm level is exceeded for more than 1s, it will switch from close to flicker or from open to close .<br />

10,000,000 times<br />

100,000 times<br />

Operation check of shock time and output relay<br />

AC2000V, 60Hz, 1 minute (power supply circuits and contact circuits)<br />

AC1000V, 60Hz, 1 minute<br />

AC2000V, 60Hz, 1 minute (power supply circuits and contact circuits)<br />

0.2kg<br />

Less than 4.0VA (less than 3.0W)<br />

Available<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

TSB3CT100<br />

100A<br />

CT External<br />

Reference<br />

Motor<br />

Model<br />

Rated primary current<br />

Rated secondary current<br />

Rated load<br />

Mass<br />

Combined unit model<br />

200V class<br />

400V class<br />

1518.5kW<br />

3045kW<br />

TSB3CT200<br />

200A<br />

5A<br />

5VA<br />

0.9kg<br />

TSBSD10<br />

2237kW<br />

5590kW<br />

<br />

TSB3CT300<br />

300A<br />

4575kW<br />

110132kW<br />