TABLE 4 MEGA-RIB, MULTI-RIB, R-PANEL TECHNICAL PROPERTIES<br />
Test<br />
Air leakage, ASTM E1680<br />
APPROVALS, LISTINGS<br />
2004 Florida State Building Code, structural,<br />
non-structural<br />
ICC-ES Evaluation Report ER-5896<br />
Miami-Dade Notice of Acceptance, (NOA) -<br />
NOA #<strong>07</strong>-1219.<strong>13</strong>, Expires 20<strong>13</strong><br />
Texas Department of Insurance Windstorm<br />
Approval<br />
Underwriters Laboratories, Inc. (UL)<br />
• Multi-Rib, R-Panel, 5V-Crimp, Mega-Rib, Max-<br />
Rib, U-Panel have been approved for use in<br />
the following Underwriters Laboratories, Inc.<br />
(UL) design numbers: P225, P227, P230, P237,<br />
P250, P259, P265, P266, P268, P508, P510, P512,<br />
P514, P516, P518, P701, P711, P712, P7<strong>13</strong>, P717,<br />
P720, P722, P723, P726, P731, P732, P734, P736,<br />
P739, P740, P801, P815, P819, P824, P825, P828<br />
Visit <strong>McElroy</strong> <strong>Metal</strong>, Inc., online at www.mcelroymetal.com<br />
to obtain technical bulletins,<br />
approvals and listings by various agencies.<br />
PHYSICAL/TECHNICAL PROPERTIES<br />
See Tables 4 and 5. Technical bulletins are<br />
available online at www.mcelroymetal.com.<br />
FIRE PERFORMANCE<br />
See Table 3. For additional fire resistive assemblies<br />
and component protection information,<br />
consult <strong>McElroy</strong> Engineering Department.<br />
5. Installation<br />
PREPARATORY WORK<br />
Deliver products in manufacturer’s original,<br />
unopened, undamaged containers with identification<br />
labels intact. Inspect for damage or<br />
moisture and notify <strong>McElroy</strong> <strong>Metal</strong>, Inc., within<br />
48 hours of discovery.<br />
A forklift or crane can be used to handle<br />
unopened bundles to 25' (8 m) in length. For<br />
forklift unloading, spread forks to maximum<br />
width and place at center line weight distribution<br />
of bundle. For crane unloading, use a<br />
spreader bar to evenly distribute the bundle’s<br />
weight. Do not use cable supports as they will<br />
damage the panels.<br />
When moving individual panels, grasp<br />
panel edges and carry lengthwise, parallel to<br />
the ground. Protect the finish from scratching<br />
or abrasion.<br />
Store bundled material dry and above<br />
ground. Do not use plastic tarp, but protect<br />
from weather conditions by other means. Allow<br />
for proper air circulation to prevent moisture<br />
buildup under the tarp. Elevate one end of the<br />
bundles to allow for moisture runoff. If panels<br />
Static Pressure Air Infiltration Air Infiltration<br />
Specimen Differential Rate Rate<br />
Mega-Rib, 26 gage - 6.24 psf (- 297 Pa) - 6.24 cfm/lf 0.011 cfm/sf<br />
Mega-Rib, 26 gage + 6.24 psf (+ 297 Pa) + 6.24 cfm/lf 0.0<strong>07</strong> cfm/sf<br />
Mega-Rib, 26 gage ± 1.57 psf (± 75.2 Pa) ± 1.57 cfm/lf 0.004 cfm/sf<br />
Multi-Rib, 26 gage - 6.24 psf (- 297 Pa) 0.0<strong>07</strong> cfm/lf 0.002 cfm/sf<br />
Multi-Rib, 26 gage + 6.24 psf (+ 297 Pa) 0.004 cfm/lf 0.001 cfm/sf<br />
Multi-Rib, 26 gage - 1.57 psf (- 75.2 Pa) 0.004 cfm/lf 0.001 cfm/sf<br />
Multi-Rib, 26 gage + 1.57 psf (+ 75.2 Pa) 0.000 cfm/lf 0.000 cfm/sf<br />
R-Panel, 26 gage - 6.24 psf (- 297 Pa) 0.011 cfm/lf 0.004 cfm/sf<br />
R-Panel, 26 gage + 6.24 psf (+ 297 Pa) 0.0<strong>07</strong> cfm/lf 0.002 cfm/sf<br />
R-Panel, 26 gage - 1.57 psf (- 75.2 Pa) 0.0<strong>07</strong> cfm/lf 0.002 cfm/sf<br />
R-Panel, 26 gage + 1.57 psf (+ 75.2 Pa) 0.001 cfm/lf 0.001 cfm/sf<br />
Test Susceptibility to Leakage, FM 4471<br />
Specimen Rate Test Duration Result<br />
Mega-Rib, 24 gage Water Spray Leakage 5 gal/sf/hr 15 minutes Passed<br />
Water Depth<br />
Static Water Leakage 6" (152 mm) 7 days Passed<br />
Test<br />
Water Penetration, ASTM E1646<br />
Static Pressure Test Water<br />
Specimen Differential Rate Duration Infiltration<br />
Mega-Rib, 26 gage 12.0 psf (575 Pa) 5 gal/sf/hr 15 minutes None<br />
Multi-Rib, 26 gage 12.0 psf (575 Pa) 5 gal/sf/hr 15 minutes None<br />
R-Panel, 26 gage 12.0 psf (575 Pa) 5 gal/sf/hr 15 minutes None<br />
<strong>McElroy</strong> <strong>Metal</strong>, Inc.<br />
become wet, remove all panels from bundles<br />
and dry each individually.<br />
Prolonged panel storage is not recommended.<br />
If conditions do not permit immediate<br />
installation, take extra care to protect<br />
sheets from developing rust or watermarks.<br />
Verify that site conditions are acceptable<br />
for installation. Do not proceed with installation<br />
until unacceptable conditions are corrected.<br />
Handle and store product according<br />
to <strong>McElroy</strong> <strong>Metal</strong>, Inc., recommendations.<br />
METHODS<br />
Install panels plumb, true and in correct alignment<br />
with structural framing in accordance<br />
with shop drawings and manufacturer’s<br />
instructions. Install panels in vertical installations<br />
using manufacturer’s noncorroding fasteners<br />
color matched to panel. Sight-exposed<br />
noncorroding fasteners color matched to trim<br />
are permitted. Replace products having<br />
other than minor finish damage.<br />
PRECAUTIONS<br />
Before ordering materials, have proposed<br />
installation reviewed by technical services<br />
staff. Protect installed products from damage<br />
by subsequent construction activities.<br />
Field cutting panels and driving of fasteners<br />
will create metal shavings. These must be<br />
removed from the panel surface. Failure to do<br />
so will cause rust stains on the panel surface<br />
and will void the warranty.<br />
BUILDING CODES<br />
Installation must comply with the requirements<br />
of all applicable local, state and national code<br />
jurisdictions. Current data on building code<br />
requirements and product compliance may<br />
be obtained from <strong>McElroy</strong> technical support<br />
specialists.<br />
6. Availability & Cost<br />
AVAILABILITY<br />
<strong>McElroy</strong> <strong>Metal</strong>, Inc., has 10 manufacturing<br />
facilities and 20 service centers located<br />
throughout the United States to serve the<br />
construction market. Contact <strong>McElroy</strong> <strong>Metal</strong>,<br />
Inc., for more information.<br />
COST<br />
Project-specific cost information may be<br />
obtained from a local <strong>McElroy</strong> distributor or<br />
directly from <strong>McElroy</strong> <strong>Metal</strong>, Inc.<br />
7. Warranty<br />
<strong>McElroy</strong> <strong>Metal</strong>, Inc., makes available limited<br />
warranties. For specific information regarding<br />
SPEC-DATA ª and MANU-SPEC ª are registered trademarks of Reed Elsevier Inc. The ten part SPEC-DATA format conforms to the editorial style<br />
of The Construction Specifications Institute and is used with their permission. The manufacturer is responsible for technical accuracy. ©2008 Reed Construction Dataª. All Rights Reserved.